Eaton Remote Monitoring Device (RMD) Installation and Operation Manual P-164000516—Rev 02
5.
Connect the Cat5 cable to the RJ45 Ethernet connector on the PXG card. Refer to the applicable Eaton
UPS Installation and Operation manual for the UPS Minislot location and wiring access information (see
For
More Information
section).
NOTE
Ensure the Status indicator of the PXG card is illuminated (this may take approximately
two minutes) before plugging in the RMD power source.
6.
After the Status indicator of the PXG card has illuminated, connect the charger cord micro USB connector
to the micro USB connector on the RMD (see
Figure 4
). Connect the transformer side of the charger cord
to a 120 Vac service outlet. The RMD should start automatically with the Eaton logo being displayed. Then
the power pushbutton on the front of the RMD will illuminate green and the current status of the UPS
should be displayed. If the display does not start, let the battery charge for 30 minutes and start manually
(see paragraph
Powering the RMD
).
Figure 4. Location of RMD Components
Power Pushbutton
4.3” Display
Screen
Front View
Back View
Side View
Ethernet 10/100
(RJ45)
Audible Alarm
End View
Speaker/Buzzer
Micro USB
Installation