©2015 Eaton Corporation
All rights reserved
14
RE Series Enclosure Installation Guide Issue 8
STEP 2 - DOOR EARTH BONDING
Locate the door bottom earth stud (closest to the
bottom hinge). Fit earth lead to door as shown in
Fig 2.0. Tighten to 6Nm.
Repeat this step at the rear of the rack
Secure other end of earth lead as shown in Fig
STEP 3 - 19-INCH RAIL EARTH
BONDING
Remove the side panel to improve access.
Fit earth assembly as shown in Fig 3.0 and
tighten assembly using a torque of
M6 Plain washers (X2)
M6 Serrated hex flange
M6 Earth lead
Fig 2.0
M6 X 12 Setscrew
M6 Serrated hex flange
M6 Earth lead (350mm) -
connect to corner gusset
Fig 3.0
M6 Plain washer
M6 Shake proof washer
Use the same process
for earth bonding the
19-inch mounting rails
in an 800mm wide
rack as shown in Fig
Fig 4.0
Installation Guide