5 RAMO5 Motor starter
5.4 Special technical data
122
Rapid Link 5 · RAMO5 · RASP5
10/19 MN034004EN
www.eaton.com
5.4 Special technical data
The following tables show the technical data of the RAMO5 Motor Control
Unit in the individual power classes with the allocated motor output.
→
The motor output allocation is based on the rated operational
current.
→
The motor output designates the respective active power
output to the drive shaft of a normal, four pole, internally or
externally ventilated three-phase asynchronous motor with
1500 min
-1
(at 50 Hz) and 1800 min
-1
(at 60 Hz).
Symbol
Unit
RAMO5-D…
RAMO5-W…
Instance
Direct starter
L1
→
U, L2
→
V, L3
→
W.
Reversing starter
FWD: L1
→
U, L2
→
V, L3
→
W
REV: L1
→
W, L2
→
V, L3
→
U.
Block diagram
Rated operational current (I
e
)
I
e
A
6.6
Adjustable motor protection
A
0.3 - 6.6
Assigned motor output at
400 V, 50 Hz
440 - 460 V, 60 Hz
P
kW
0.18 - 3
P
HP
0.25 - 4
Power side (primary side)
Number of phases
3
Rated voltage
U
LN
V
380 V - 10 % - 480 V + 10 %, 45 - 66 Hz
Input current
I
LN
A
0.3 - 6.6
Braking
Control voltage
(external brake)
U
V
RAMO5-xxx1…: 180 V DC
RAMO5-xxx2…: 230/277 V AC
RAMO5-xxx4…: 400/480 V AC
Load current (external brake)
I
A
0.6 A, max. 6 A for 120 ms
Heat dissipation at
rated current (I
e
)
P
v
W
max. 8 W, depending on motor current and brake
Weight (without/with manual override
switch)
m
kg
1.6/1.8
Reaction time
Motor On (automatic)
1)
t
ON
ms
Motor 20-35, brake 20-35
Motor Off (automatic)
1)
t
OFF
ms
Motor 20-35, brake 20-35
Switch off the motor (quick stop)
t
Off
ms
Motor 20-35, brake 20-35
Switch on Q1
t
ON
ms
2 - 20
Switch off Q1
t
OFF
ms
2 - 20
Minimum pulse duration I1/I2
t
ON
ms
5
1) without bus runtime, depending on PLC
Содержание Rapid Link RAMO5
Страница 1: ...Manual Rapid Link 5 RAMO5 RASP5 10 19 MN034004EN ...
Страница 4: ...II ...
Страница 10: ...6 Rapid Link 5 RAMO5 RASP5 10 19 MN034004EN www eaton com ...
Страница 122: ...4 Operation 4 3 Manual control 118 Rapid Link 5 RAMO5 RASP5 10 19 MN034004EN www eaton com ...
Страница 136: ...5 RAMO5 Motor starter 5 7 Configure special settings 132 Rapid Link 5 RAMO5 RASP5 10 19 MN034004EN www eaton com ...
Страница 158: ...8 PC tool 8 2 Parameter Editor 154 Rapid Link 5 RAMO5 RASP5 10 19 MN034004EN www eaton com ...
Страница 164: ...9 Control Unit 9 2 Extended parameter set 160 Rapid Link 5 RAMO5 RASP5 10 19 MN034004EN www eaton com ...
Страница 194: ...10 Parameter list 10 4 Parameter groups for RASP 190 Rapid Link 5 RAMO5 RASP5 10 19 MN034004EN www eaton com ...
Страница 208: ...11 Communications 11 5 OP Bus 204 Rapid Link 5 RAMO5 RASP5 10 19 MN034004EN www eaton com ...
Страница 216: ...12 Error messages 12 3 RASP Error list 212 Rapid Link 5 RAMO5 RASP5 10 19 MN034004EN www eaton com ...