1.5.2 RAMO5
The RAMO5 motor starters have been tested in accordance with UL 60947-
4-2 and are approved as “listed”.
Table 3:
RAMO5
Table 4:
Short circuit current rating for individual and group protection
RAMO5 motor starters can be installed and operated under the following
conditions: The device is suitable for use on a circuit capable of delivering not
more than 65000 A rms symmetrical amperes, 480 V:
•
When protected by 30-A fuses or
•
when protected by a circuit breaker having an interrupting rating not less
than 65000 A rms symmetrical amperes, 480 V, 32 A maximum.
Only for use with flexible cable connected drives is at the discretion of the
AHJ.
Installation may be limited to NFPA 79 applications.
Property
Value
Input voltage
480 V AC
Output voltage
480 V AC
Rated operational voltage for brake control
180/207 V DC
230/480 V AC
400/480 V AC
Input current
6.6 A
Output current
6.6 A
Phases
3
Frequency
50/60 Hz
Control voltage, external
24 V DC
Field bus input voltage
30 V DC
Motor protection
integrated
Thermistor monitoring
integrated
SCCR
Protection class
IP65 / NEMA 12
Ambient temperature, maximum
55
°
C
With fuse (UL listed)
Circuit-breaker (UL listed)
With built-in
repair switch
Without built-
in local
disconnect
switch
With built-in
repair switch
Without built-
in local
disconnect
switch
Voltage
480 V AC
480 V AC
480 V AC
480 V AC
Short-circuit current, maximum
30 A
30 A
32 A
32 A
Interrupting Rating
10 kA
65 kA
10 kA
10 kA
→
Devices with an integrated repair switch are approved for use as
motor disconnects (lockout/tagout).
Содержание Rapid Link 5
Страница 1: ...Manual Rapid Link 5 RAMO5 RASP5 05 20 MN034004EN ...
Страница 4: ...II ...
Страница 38: ...1 Rapid Link 5 system 1 10 Service and warranty 34 Rapid Link 5 RAMO5 RASP5 05 20 MN034004EN www eaton com ...
Страница 118: ...3 Installation 3 7 Isolation test 114 Rapid Link 5 RAMO5 RASP5 05 20 MN034004EN www eaton com ...
Страница 196: ...8 Parameter list 8 4 Parameter groups for RASP5 192 Rapid Link 5 RAMO5 RASP5 05 20 MN034004EN www eaton com ...
Страница 246: ...10 Error Messages 10 2 Error Messages 242 Rapid Link 5 RAMO5 RASP5 05 20 MN034004EN www eaton com ...