3
Technical Data
TD150015EN
Effective September 2017
PXM4/6/8K Meter Color Touchscreen
Display Quick Start Guide
EATON www.eaton.com
For best results, use the default communication settings for the
PXM4/6/8K Meter and PXM4/6/8K Meter Color Touchscreen Display
(115.2 kbps, 1 start bit, 1 stop bit, no parity).
otee:
N
By default, the PXM4/6/8K Meter Color Touchscreen Display is preset
for a PXM4/6/8K Meter slave address of “01”. To accommodate a differ-
ent slave address, the User MUST Change the PXM4/6/8K Meter Color
Touchscreen Display’s “PLC DEFAULT STATION”. This number MUST match
the rotary switch located on the side of the meter.
Figure 7. Changing the PLC Default Station.
Meter Firmware Requirements
•
The minimum meter firmware version required for compatibility is
13.3.6.1.
Technical Information
•
320 x 234 pixel backlit LCD touch screen display.
•
Power: 24 Vdc input.
•
For meters manufactured prior to November 2015, an exter-
nal power supply is required for the PXM4/6/8K Meter Color
Touchscreen Display.
•
Recommended power supplies: PSG60E (85-264 Vac input);
PSG60F (320-575 Vac input).
Display Measurements
•
Height: 5.66 in. (144 mm);
•
Width: 7.24 in. (184 mm);
•
Depth: 1.97 in. (50 mm);
•
Weight: 1.48 lb (670 g);
•
Cutout dimensions: 5.21 x 6.79 in. (132.4 x 172.4 mm).
Ratings
•
Front bezel IP rating: IP65;
•
Operating temperature: 0 ~ 50°C (32 ~ 122°F);
•
Storage temperature: -20 ~ 60°C (-4 ~ 140°F);
•
Ambient humidity: 10% ~ 90% RH (0 ~ 40°C [32 ~ 104°F]),
10% ~ 55% RH (41 ~ 50°C [105.8 ~ 122°F]).