Power Xpert Branch Circuit Monitor:
Meter Base - Basic and Energy Code Series
Instruction Leaflet
IL150001EN
Effective May 2019
•
Humidity 5-95% noncondensing
•
UL file # E185559, UL Standard UL61010-1
•
CNL evaluation to CAN/C22.2 No 1010.1.92
•
CE mark
•
EMC EN61326 – IEC61000-4-X level 3
•
Emissions conducted and radiated as part of PXBCM system.
•
FCC part 15 class B
•
CISPR 11/22 class B
External Circuit Connections
•
Com1/2
RS485 Modbus Slave RTU:
•
9600 – 115.2K(default) baud
•
–D, +D, Com/Shield
•
Use RS485 cable – 4K’=<19.2Kb,2K’ above
•
LAN
Ethernet RJ45 CAT5 10/100 base T
•
Use STP Cat5+ for full EMC compliance
•
MMP1-4
Meter Module ports:
•
2 pair cable 1 pair power, 2nd coms
•
Use PXBCM-MMP-CBLnn –CBLEnn cables
•
Each MMP is separately isolated
•
Power Supply
mains 100-277VAC L:N
•
Up to 347 VAC L:N possible with control power transformer
•
+/-10%, CAT III, 47-63 Hz , 6W
•
Double insulated
•
320VAC Surge filter clamp L:N, L:G, N:G -
Do not high pot!
•
Provide external line fuse or breaker sized to protect wiring
•
3 position fixed terminal block 1/2/3 = PE/N/L, supporting 12
AWG (2.5mm) wire.
A detailed product identification label is on the left side of each
Meter Base. This information can also be viewed through the
PXBCM web configuration with a browser via the LAN Ethernet port.
Figure 2. Example PXBCM-MB Product ID Label.
The MB may be pow-
ered through a single-
phase connection to
the panel mains. The
power connection
(marked Power Supply
on the MB) must be
equipped with both a
disconnect switch and
fuse or breaker to pro-
tect the wire.
Protective
earth
Neutral
Fuse block
Line
Disconnect
switch
Com1 RS485
Modbus RTU
LAN Ethernet
RJ45 CAT5+ STP
MMP 1-4 Meter
Module ports
Figure 3. PXBCM-MB external circuit connections.
Please refer to the PXBCM Install Guide
IB150003EN for complete system detail:
www.
eaton.com/pxbcm
Figure 4. Meter Base mounting details.
5.65 in
(143.5 mm)
5.5 in
(139.7 mm)
Com2 RS485
Modbus RTU