Instruction Leaflet IL040029EN
Effective December 2017
PowerXL DH1 Series VFD
EATON
www.eaton.com
13
Input power and motor cable stripping lengths
Power connection tightening torque
Notes
���
Strip the motor and power cables as shown above.
���
Both UL
®
and IEC tools may be used.
���
Applies to strained wire, solid wire, or ferrule installations.
���
FR0 is not available till June 2018.
Frame
Size
Power Wiring in Inches (mm)
Motor Wiring in Inches (mm)
A1
B1
C1
D1
A2
B2
C2
D2
FR0
���
0.39
(10)
5.12
(130)
0.39
(10)
5.12
(130)
0.39
(10)
3.15
(80)
0.39
(10)
1.97
(50)
FR1 0.39
(10)
1.77
(45)
0.39
(10)
1.38
(35)
0.39
(10)
1.77
(45)
0.39
(10)
1.38
(35)
FR2 0.59
(15)
1.77
(45)
0.59
(15)
1.77
(45)
0.59
(15)
1.57
(40)
0.59
(15)
1.57
(40)
FR3 0.59
(15)
1.57
(40)
0.59
(15)
1.97
(50)
0.59
(15)
1.57
(40)
0.59
(15)
1.97
(50)
FR4 0.98
(25)
2.56
(65)
0.98
(25)
4.72
(120)
0.98
(25)
2.56
(65)
0.98
(25)
4.72
(120)
FR5 1.10
(28)
6.10
(155)
1.10
(28)
9.45
(240)
1.10
(28)
6.10
(155)
1.10
(28)
9.45
(240)
FR6
0.98
(25)
4.72
(120)
0.98
(25)
7.87
(200)
0.98
(25)
4.72
(120)
0.98
(25)
7.87
(200)
Frame
Size
Power wire
in-lb (Nm)
Ground wire
in-lb (Nm)
Control wire
in-lb (Nm)
FR0
���
5.3 (0.6)
14 (1.6)
4.5 (0.5)
FR1 5.3
(0.6)
10
(1.1)
4.5
(0.5)
FR2 15.6
(1.8)
10
(1.1)
4.5
(0.5)
FR3
40 (4.5)
10 (1.1)
4.5 (0.5)
FR4
95 (10.7)
14 (1.6)
4.5 (0.5)
FR5 354
(40.0)
35
(4.0)
4.5
(0.5)
FR6 480
(54.2)
35
(4.0)
4.5
(0.5)