background image

P13.1.2

Application

0

2 = Advanced

P2.2.19

Run Enable

1

9 = DigIN: 8

P2.1.1

Damper Start

0

1 = Interlock Start

P2.2.27

Auto Control

9

0 = DigIN:NormallyOpen

P3.1.8

RO3 Function

3

35 = Damper Control

Code

Parameter Default Application Setting

Code

Parameter

Default

Application Setting

P13.1.2

Application

0

2 = Advanced

P2.2.19

Run Enable

1

9 = DigIN: 8

P2.1.1

Damper Start

0

2 = Interlock Tout

P2.1.2

Damper Time Out

5

Delta normally taken by damper to close the position 

feedback)

P2.2.27

Auto Control

9

0 = DigIN:NormallyOpen

P3.1.8

RO3 Function

3

35 = Damper Control

Code

Parameter

Default

Application Setting

P13.1.2

Application

0

2 = Advanced

P2.2.19

Run Enable

1

9 = DigIN: 8

P2.1.1

Damper Start

0

3 = Interlock Delay

P2.1.2

Damper Time Out

5

User Defined Time in Seconds ( Recommendation: Time + 

Delta  normally taken by damper to close the position 

feedback)

Interlock Delay:

 Drive waits for the RUN ENABLE (Damper open position feedback) because 

drive Damper start has been programmed for interlock delay, like interlock start/Tout. Except in 
this case drive will not start until the 

Damper Delay time

 has lapsed. 

Interlock Tout:

 Drive waits for the RUN ENABLE (Damper open position feedback) because 

drive Damper start has been programmed for interlock Tout, like interlock start. Except in this 
case if the end switch is not made by the time 

Damper Time Out 

times out, the drive will fault 

with message “Start-up Prevent”. 

P2.2.27

Auto Control

9

0 = DigIN:NormallyOpen

P3.1.8

RO3 Function

3

35 = Damper Control

2) Normal electronic Bypass:   Electronic Bypass mode  for the drive is when the VFD’s

microprocessor (MCU) is used for initiating the close command to the bypass contactor
using the Bypass relay of the drive. Since the  drive  MCU is active, the damper control
interlock is still available through drive controls due to the parameter settings discussed
above. Based on the scheme in Figure: 2 there are 

two

 ways to initiate electronic Bypass

  Below are the recommended drive parameter settings for Damper control. 

These damper control 

parameters are to be set in addition to standard drive commissioning parameters for the 
application. 

2

EATON 

www.eaton.com 

Interlock Start:

 Drive waits for the RUN ENABLE (Damper open position feedback) because 

drive Damper start has been programmed for interlock start. If damper start is left at default setting 
NORMAL, the damper will have to be closed before the issuing

  drive start CMD. 

Отзывы: