5 Technical data
5.2 Specific rated data
DB1 variable frequency drive
11/20 MN040031EN
Eaton.com
93
5.2.2 DB1-1M… device series
Size
Symbol
Unit
4D3
Rated current
I
e
A
4.3
Overload current for 60 s every 600 s
I
L
A
6.5
Overload current for 3.75 s every 600 s
I
L
A
7.5
Apparent power at rated operation 230 V
S
kVA
0.99
Apparent power at rated operation 240 V
S
kVA
1
Assigned motor output
at 230 V, 50 Hz
P
kW
0.75
at (220 - 240) V, 60 Hz
P
HP
1
Mains side (primary side):
Number of phases
single-phase or two-phase
Rated voltage
U
LN
V
110 (-20 %) - 230 (+10 %)
48 - 62 Hz, 88 - 253 ±0 %
Input current (phase current)
I
LN
A
110 V: 10.92 230 V: 5.1
Switching frequency (pulse frequency)
Default setting
f
PWM
kHz
8
Adjustable range
f
PWM
kHz
4 - 32
Maximum leakage current
(touch current) to ground (PE) at U
LN
: 240 V,
without motor
I
Touch
mA
ITouch
< 3.5
Power loss (% n
N
/ % M
N
)
90 / 100 @ 4 kHz
P
V
W
n/s
90 / 100 @ 8 kHz
P
V
W
n/s
90 / 100 @ 12 kHz
P
V
W
n/s
90 / 100 @ 16 kHz
P
V
W
n/s
90 / 100 @ 24 kHz
P
V
W
n/s
90 / 100 @ 32 kHz
P
V
W
n/s
90 / 50 @ 8 kHz
P
V
W
n/s
50 / 100 @ 8 kHz
P
V
W
n/s
50 / 50 @ 8 kHz
P
V
W
n/s
50 / 25 @ 8 kHz
P
V
W
n/s
0 / 100 @ 8 kHz
P
V
W
n/s
0 / 50 @ 8 kHz
P
V
W
n/s
0 / 25 @ 8 kHz
P
V
W
n/s
in no-load state, (device not enabled)
P
V
W
6.5
Frame size
–
–
FS1C
Note: n/ s = not specified