9x55 8–15 kVA Battery Upgrade (8–15 kVA)
—Rev 1
13
12. Slide the new battery trays into the unit. The positive (+) terminal of each tray should face the front of the
unit and be on the right side of the tray (highlighted in yellow in
Figure 14
). When sliding it into position, lift
the rear of each battery tray onto the shelf to get it started.
Figure 14. Insert New Battery Trays
13. Locate the remaining cabinet wiring that was previously disconnected from the old trays. Use a wire cutter
(preferably the scissor action type as opposed to diagonal cutters) to cut/remove the existing female
Faston® terminal on the cabinet harness (spade terminal off the ends of the red and black wires). It is
preferred to perform this step by doing one string/shelf at a time.
Battery Upgrade Procedure