background image

 

www.powerware.com/ibm 

  +44 (0) 845 177 3410 

 

15

P14 Technical Specifications* 

 

Electrical Input 

 

Nominal Voltage 

230 Vac (user selectable to 220 Vac) 

Online Voltage Range 

±20% for nominal voltage at full load 

Nominal Input Frequency 

45–65 Hz, 50/60 Hz; auto-sensing 

Input Protection 

Reset-able circuit breaker 

Connection IEC-320-C14 

 

 

Electrical Output 

 

Power Levels 

950W/1400 VA 

Online Regulation 

-10%, +6% of nominal voltage 

On Battery Voltage Regulation 

±5% of nominal voltage; -10% after low battery warning 

On Battery Frequency Regulation 

±0.1 Hz of nominal frequency 

Voltage Wave Shape 

Sine wave (during normal and battery operation) 

Connections (6) 

IEC-320-C13 

 

 

Indicators and Controls 

 

Front Panel LEDs 

Power on, on battery, overload, and battery fault 

Front Panel Buttons 

On/off and alarm silence/self-test 

Communication Port 

DB-9 female (UPS ships with communication cable); USB Interface Adapter is 
optional 

 

 

Battery 

 

Battery Type 

Sealed, maintenance-free lead-acid; starved electrolyte 

Battery Description 

(3) 12V, 9 Ah 

Battery Recharge 

<3 hours to 90% capacity 

Battery Runtime 

See Battery Runtimes table 

Start-On-Battery 

Startup with UPS batteries in absence of utility power 

 

 

General 

 

Topology Line-interactive 

Diagnostics 0.68 

Dimensions and Weight 

See Model Guide 

Network Transient Protector 

In and out RJ-11 jack for telephone/modem protection or RJ-45 for 10BaseT network 
cable; UL497A tested 

 

 

Environmental and Safety 

 

Operating Temperature 

0°C to 40°C (32°F to 104°F) UL tested at 25°C (77°F) 

Transit/Storage Temp. 

-15°C to 55°C (5°F to 131°F) 

Heat Dissipation 

189 BTU/hr, maximum 

Audible Noise 

<45 dBA typical 

Relative Humidity 

5% to 95% noncondensing 

Safety Markings 

UL, cUL, and CSA 

Safety Conformance 

UL 1778, CAN/CSA C22.2, No. 107.1 

EMC Markings 

FCC Class B; 230V models also CE (EN50091-2) and C-Tick 

Surge Suppression 

ANSI C62.41 Category A (formerly IEEE 587) 

Immunity 

IEC 801-2, -3, -4 

* Due to continuing product improvement programs, specifications subject to change without notice.

Содержание Powerware 9910-E30

Страница 1: ...Power Protection Handbook for IBM System i and System p Applications Powerware 9910 UPS International July 2008 ...

Страница 2: ...ry Runtime Do You Need 12 Powerware 9910 UPS Models Attributes at a Glance 13 Powerware 9910 P14 14 Powerware 9910 P16 17 Powerware 9910 E30 20 Powerware 9910 E33 23 Powerware 9910 E64 26 Powerware 9910 E65 30 Powerware 9910 E83 33 Powerware Software and Connectivity 37 Note Due to continuing product improvement programs all specifications are subject to change without notice For the latest inform...

Страница 3: ... i rack applications p5 Rack UPS Chart Configure the appropriate Powerware 9910 UPS for your POWER AIX and Linux and System p rack applications How to determine what parts are included with your 9910 UPS What to know what components are included with your 9910 UPS kit Find out the various components and options available for the 9910 UPS models How much battery runtime do you need Calculate how mu...

Страница 4: ...www powerware com ibm 44 0 845 177 3410 3 9 Power Problems and Their UPS Solutions ...

Страница 5: ...Note Online UPSs provide protection from all 9 power problems listed on page 5 Line Interactive UPS Technology Line interactive UPSs offer basic power protection at mid range prices In addition to protection against power failures power sags and power surges line interactive UPSs protect against brownouts and electrical line noise This design offers low grade voltage regulation by boosting the uti...

Страница 6: ...he batteries need to be replaced 11 How can you be sure UPS batteries are in good condition in order to insure they have maximum holdover in the event of a power failure What preventive maintenance procedures should be done and how often should they be done The batteries used in the UPS and associated battery modules and cabinets are sealed lead acid batteries often referred to as maintenance free...

Страница 7: ... is not equipped with enough output receptacles you may need to add a PowerPass Distribution Module or choose another UPS 4 Adding batteries to the UPS provides additional battery runtime only not added capacity If a customer adds equipment to the configuration a higher rated UPS may be needed With larger UPS models particularly above 3 kVA and for 3 phase UPS solutions it is extremely important t...

Страница 8: ...iant IBM Part Number Pre RoHS IBM Part Number UPS P14 UPS 950W 1400 VA 230 Vac 39J4810 39J2533 P16 UPS 1050W 1500 VA 230 Vac 39J4812 04N6374 E30 UPS 2100W 3000 VA 208 240 Vac 42R8069 38P9297 E33 UPS 2700W 3000 VA 208 240 Vac 42R8065 21P7219 E64 UPS 4200W 6000 VA 208 240 Vac 42R8073 38P9298 E65 UPS 4500W5000 VA 208 240 Vac 42R8077 39J2534 E83 UPS 8000W 10000 VA 220 240 Vac 44V3923 EBM 6605 Extended...

Страница 9: ...tic interference EMI and other voltage or frequency disturbances Electromagnetic Interference EMI Electrical interference that can cause equipment to work improperly EMI can be separated into conducted EMI interference conducted through cables out of the UPS and radiated EMI interference conducted through the air Ground A conducting connection whether intentional or accidental by which an electric...

Страница 10: ...l channels in case of failure Relay Communication Communication between a UPS and a computer through the opening and closing of solid state relays which are pre defined to indicate UPS status RS 232 The standard for serial interfaces serial refers to the eight bits of each character successively sent down one wire used by most computers modems and printers a 25 pin physical interface Sine Wave A w...

Страница 11: ...Kilovolt ampere LAN Local Area Network MBB Make Before Break bypass switch MTBF Mean Time Before Failure MTTR Mean Time To Repair NEMA National Electrical Manufacturers Association NEC National Electrical Code PBX Private Branch Exchange PDM Power Distribution Module PPDM PowerPass Distribution Module PoE Power Over Ethernet PUE Power Usage Efficiency REPO Remote Emergency Power off RFI Radio Freq...

Страница 12: ...0 Tower 750W z z 9111 520 Rack 750W z z 9113 550 Tower 1 100W z z 9113 550 Rack 1 100W z z z1 z 7047 185 Tower 450W z z 7037 A50 Tower 450W z z p5 9110 51A Rack 625W z z p5 9115 505 Rack 500W z z p5 9111 285 Tower 750W z z p5 9116 561 Rack 1300W z z z z p5 9123 710 Rack 700W z z p5 9124 720 Tower 1592W z z1 p5 9124 720 Rack 1592W z z p5 9131 52A Tower 750W z z p5 9131 52A Rack 750W z z p5 9133 55A...

Страница 13: ... before power continuity is fully restored By doubling the system application time you allow for two consecutive power outages to occur while providing an adequate reserve of battery runtime to initiate a safe system shutdown during the second power outage In the example it takes the application 3 minutes to shut down Doubling the shutdown time results in 6 minutes Safety margin Allows for natural...

Страница 14: ...rm Factor z z z z1 Rackmount Form Factor z z z z z Rack Height U 2 2 5 3 6 ABM Technology z z z z z z z Hot Swappable Batteries z z z z z z z Hot Swappable Electronics Module z z Maintenance Service Bypass z1 z Load Segments z z z z z z Extended Battery Modules z z z z z z EBM Feature Code 6605 6644 6643 6645 6645 6646 EBM IBM p n 39J4813 42R8071 42R8067 42R8075 42R8075 44V3921 X Slot Communicatio...

Страница 15: ...0 System I i5 and serial connectivity enhances communication capability Tested and approved by IBM to assure out of box usability Includes premium IBM warranty P14 Model Guide Model Number IBM Number Power Out Watts VA Input Connection Output Connections Dimensions HxWxD in mm Unit Weight lb kg 230 Vac1 50 60 Hz auto sensing 9910 P14 39J4810 950 1400 IEC 320 C14 6 IEC 320 C13 7 6 x 5 9 x 15 4 193 ...

Страница 16: ...er is optional Battery Battery Type Sealed maintenance free lead acid starved electrolyte Battery Description 3 12V 9 Ah Battery Recharge 3 hours to 90 capacity Battery Runtime See Battery Runtimes table Start On Battery Startup with UPS batteries in absence of utility power General Topology Line interactive Diagnostics 0 68 Dimensions and Weight See Model Guide Network Transient Protector In and ...

Страница 17: ...s for IBM Applications Manual Powerware Software Suite CD Service and Support Manual for IBM Applications P14 Applications Matrix Various options are available depending on application For System i or System p applications consult chart below to select appropriate feature codes to order with the P14 UPS IBM Server Watts Vac Expected Battery Runtime in Minutes i5 System i 9406 520 9405 520 600 200 ...

Страница 18: ...nnection Output Connections Dimensions HxWxD in mm Unit Weight lb kg 230 Vac 50 60 Hz auto sensing 9910 P16 39J4812 1050 1500 IEC 320 C141 6 IEC 320 C13 3 5 x 17 x 19 4 89 x 432 x 493 50 23 Extended Battery Module EBM 9910 6605 39J4813 3 5 x 17 x 19 4 89 x 432 x 493 65 29 5 1 P16 includes 3 IEC 320 C13 to IEC 320 C14 interconnecting cords P16 Battery Runtimes Chart in Minutes Load UPS Internal Bat...

Страница 19: ...UPS internal batteries and external batteries modules Recharge Time 2 hours from complete discharge to 80 capacity at nominal line conditions Start On Battery Allows start of UPS without utility input General Topology True online double conversion Diagnostics Full system self test on power up UPS Bypass Automatic on overload or UPS failure Dimensions and Weight See Model Guide Environmental and Sa...

Страница 20: ...tart Guide AS 400 Interface Cable 6 ft 1 8m 3 IEC 320 C13 to IEC 320 C14 Equipment Power Cords 2 Pedestals Black P16 Options Various options are available depending on application For POWER IBM i i5 OS System i applications consult chart below to select appropriate feature codes to order with the P16 UPS Description IBM Feature Code IBM Part Number POWER IBM i i5 OS i5 System i Tower Worldwide Ext...

Страница 21: ...atts VA Input Connection Output Connections Dimensions HxWxD in mm Unit Weight lb kg 208 240 Vac 50 60 Hz auto sensing 9910 E30 42R8069 2100 3000 Varies1 4 IEC 320 C13 1 IEC 320 C19 3 5 x 17 x 19 4 89 x 432 x 493 34 15 9910 E30 FC 6570 42R8069 42R4 320 2100 3000 Varies 4 6 20R 2 5 20R 2 L6 15R 7 x 17 x 19 4 178 x 432 x 493 68 31 Extended Battery Module 9910 6644 42R8071 3 5 x 17 x 19 4 89 x 432 x ...

Страница 22: ... UPS Description IBM Feature Code IBM Part Number POWER IBM i System i Tower IEC POWER IBM i System i Tower NEMA POWER AIX Linux System p Tower IEC POWER AIX Linux System p Tower NEMA POWER AIX Linux System p Rack WW POWER IBM i System i Rack WW ConnectUPS X Web SNMP Card 29341 39J4824 No No Yes2 Yes2 Yes No X Slot Relay Serial Card Kit 29391 42R4332 Yes Yes No No No Yes Extended Battery Module EB...

Страница 23: ...art Battery Replacement Hot swappable UPS internal batteries and external batteries modules Recharge Time 2 hours from complete discharge to 80 capacity at nominal line conditions Start On Battery Allows start of UPS without utility input General Topology True online double conversion Diagnostics Full system self test on power up UPS Bypass Automatic on overload or UPS failure Dimensions and Weigh...

Страница 24: ... E33 Model Guide Model Number IBM Number Power Out Watts VA Input Connection Output Connections Dimensions HxWxD in mm Unit Weight lb kg 208 240 Vac 50 60 Hz auto sensing 9910 E331 42R8065 2700 3000 varies2 9 IEC 320 C13 1 IEC 320 C19 3 5 2U x 17 5 x 24 5 89 x 440 x 610 89 40 4 Extended Battery Module EBM 9910 6643 42R8067 3 5 2U x 17 5 x 24 5 89 x 440 x 610 100 45 5 1 E33 includes 4 IEC 320 C13 t...

Страница 25: ...4 ms typical Dimensions and Weight See Model Guide Communications User Interface Front control panel Audible Alarms For UPS alarm conditions including On Battery Low Battery Overload UPS fault Network Transient Protector UL497A in out jacks RJ 45 REPO Port Meets NEC code 645 11 intent and UL requirements X Slot Interface RS 232 Single Port Serial Card standard other options available Cable 6 ft co...

Страница 26: ...are available depending on application For System i or System p applications consult chart below to select appropriate feature codes to order with the E33 UPS Description IBM Feature Code IBM Part Number POWER AIX Linux System p Rack Worldwide POWER IBM i System i Rack Worldwide ConnectUPS X Web SNMP Card 29341 39J4824 Yes No X Slot Relay Serial Card Kit 29391 42R4332 No Yes Extended Battery Modul...

Страница 27: ...nsions HxWxD in mm Unit Weight lb kg 3 208 240 Vac 50 60 Hz auto sensing 9910 E64 1 42R8073 4200 6000 L6 30AR 1 L6 30R 8 75 5U x 17 x 24 9 219 x 432 x 633 206 93 6 Extended Battery Module EBM 9910 6645 42R8076 5 25 2U x 17 x 24 75 133 x 432 x 628 169 76 8 1 Base configuration of the E64 consists of E64 Accessory Kit IBM p n 42R8074 and two UPS internal battery trays IBM p n 42R4316 2 Input power c...

Страница 28: ...0 6000 VA UPS User s Guide Powerware 9125 9910 E64 Installation Guide for IBM Applications Powerware Software Suite CD Serial Cable RJ 45 to DB 9 6 ft 1 8m Serial Cable DB 9 to DB 9 6 ft 1 8m Battery Retaining Bracket 2 Battery Retaining Bracket Screws M4 x 10 mm 4 Pedestals 4 Pedestal Mounting Screws M4 x 10 mm E64 Line Cord Options Feature Code Description 1424 L6 30R to IEC 309 P N G 32 Amp 142...

Страница 29: ...M Battery Type 9 Ah sealed maintenance free lead acid Battery Type Sealed maintenance free lead acid Battery Runtime See Battery Runtime Chart Battery Replacement Hot swappable UPS internal batteries and external batteries modules Recharge Time 2 hours from complete discharge Start On Battery Allows start of UPS without utility input General Topology True online double conversion Diagnostics Full ...

Страница 30: ...5889 or 7109 PDU to UPS power cord 14 feet of 4 feet respectively 2972 or 2973 25R2555 or 42R4331 No No No No Yes Yes UPS Input Power Cord Varies Varies Yes Yes Yes Yes Yes Yes Options ConnectUPS X Web SNMP Card 2934 1 39J4824 No No Yes Yes Yes 2 No X Slot Relay Serial Card Kit 2939 1 42R4332 Yes Yes No No No Yes Extended Battery Module EBM up to 4 EBMs 6645 42R8075 Yes Yes Yes Yes Yes Yes EBM Acc...

Страница 31: ...tions Dimensions HxWxD in mm Unit Weight lb kg 3 208 240 Vac 50 60 Hz auto sensing 9910 E651 42R8077 4500 5000 L6 30P 1 L6 30R 4 IEC 320 C13 4 IEC 320 C19 5 25 x 17 5 x 26 133 5 x 444 x 660 161 67 Extended Battery Module EBM 9910 6645 42R8075 5 25 x 17 5 x 24 75 133 5 x 444 x 620 169 76 1 Base configuration for the E65 consists of the E65 Accessory Kit IBM p n 42R8078 and two UPS Internal Battery ...

Страница 32: ...peration 100 102 indefinite 103 112 2 minutes and 112 12 line cycles Dimensions and Weight See Model Guide Communications User Interface Front control panel Audible Alarms For various UPS alarm conditions including On Battery Low Battery Overload and UPS Fault REPO Port Meets NEC code 645 11 intent and UL requirements Communication Ports Native USB and serial port X Slot Interface Empty other X Sl...

Страница 33: ...r with the E65 UPS Description IBM Feature Code IBM Part Number POWER AIX Linux System p Rack Worldwide POWER IBM i System i Rack Worldwide Rack Mounting Bracket Kit 42R4322 Yes Yes ConnectUPS X Web SNMP Card 2934 1 39J4824 Yes No X Slot Relay Serial Card Kit 2939 1 42R4332 No Yes 7188 9188 5889 or 7109 PDU to UPS power cord 14 feet or 4 feet respectively 2972 or 2973 25R2555 or 42R4331 Yes Yes UP...

Страница 34: ...nnections Dimensions HxWxD in mm Unit Weight lb kg 3 220 240 Vac 50 60 Hz auto sensing 9910 E831 44V3923 8000 10000 IEC309 P N G 63A 1 IEC309 P N G 63A 4 IEC 320 C19 10 5 x 17 2 x 30 266 x 437 x 762 254 115 Extended Battery Module EBM 9910 6646 44V3921 5 25 x 17 2 x 23 9 133 5 x 437 x 607 179 81 1 Base configuration for the E83 consists of the E82 E83 Accessory Kit IBM p n 44V3919 and four UPS Int...

Страница 35: ...onnector Plug 10A 2 pin E83 Options Various options are available depending on application For System i or System p applications consult chart below to select appropriate feature codes to order with the E83 UPS Description IBM Feature Code IBM Part Number POWER AIX Linux System p Rack Worldwide POWER IBM i System i Rack Worldwide ConnectUPS X Web SNMP Card 2934 1 39J4824 Yes No X Slot Relay Serial...

Страница 36: ...ad Output Receptacles 4 IEC 320 C19 16A 1 IEC309 P N G 63A 363C6W Battery Battery Type Sealed maintenance free valve regulated lead acid Monitoring Advanced monitoring for earlier failure detection and warning Configuration 32 12V 5 Ah Battery Runtime See Battery Runtime Chart Battery Replacement Hot swappable UPS internal batteries and external batteries modules Charging in minutes to 80 usable c...

Страница 37: ...00 4 5 Surge Energy Rating High energy 6500A peak Audible Noise 55 dBA at 5 feet with battery fully charged without horn Altitude 3000m 10 000 ft without derating Leakage Current 3 5 mA Surge Suppression ANSI C62 41 Category B3 Safety Certifications UL 1778 CSA C22 2 No 107 3 EN and IEC 62040 2 NOM 019 SCFI 1993 Agency Markings cULus cUL NOM CE EMC Compliance FCC Part 15 EN 50091 2 ICES 003 Seismi...

Страница 38: ...k battery gather inventory information and control Powerware UPSs network wide from a single console within IBM Director Connectivity options offer maximum flexibility Connectivity options are available to suit nearly any communication requirement The Powerware are equipped with an RS 232 serial communication port some with built in USB port to interface with power management software You can cust...

Страница 39: ...erware com ibm Eaton Powerware ABM LanSafe ConnectUPS and X Slot are trade names trademarks and or service marks of Eaton Corporation or its sub sidiaries and affiliates All other trade marks are property of their respective owners 2008 Eaton Corporation All Rights Reserved Printed in USA 9910INT July 2008 ...

Отзывы: