Operation
Eaton 9355 UPS (20/30kVA) Installation and Operation Manual 164201626—Rev F
www.eaton.com/powerquality
73
10. Select the TURN UPS ON option. Press and hold the
button for three seconds, until the UPS stops
beeping.
The UPS precharges for a few minutes and then the
indicator illuminates. The UPS is now powering
the load.
If the
indicator is flashing, check the UPS status from the front panel to view the active alarms.
Correct the alarms and restart if necessary.
11. Replace the UPS front door.
Starting the UPS on Battery
Note:
Before using this feature, the UPS must have been powered by utility power at least once.
To start the UPS on battery:
1.
Remove the UPS front door (see page 10).
2.
Verify that the maintenance bypass switch is in the UPS position (see Figure 55 on page 80).
3.
Push the red start-on-battery button on the UPS (see Figure 54).
Figure 54. Start-on-Battery Button
4.
Wait for the front panel LCD to illuminate.
5.
Press any button on the front panel display to activate the menu options.
6.
Within three minutes, press the
button on the front panel display and then press the
button to
select the TURN UPS ON/OFF menu.