VERSION 2 WALL-MOUNTED BYPASS SWITCH
Eaton 9355 UPS (10/15 kVA) User's Guide
S
164201594 Rev D
www.eaton.com/powerquality
50
16.
Hardwire the load to the bypass cabinet (see Figure 35).
17.
Route the maintenance bypass wires through the conduit to the
UPS terminal block (see Figure 33 on page 48).
Connect the black and the red wires from the terminal block on the
Tie Cabinet to TB2 on the UPS.
NOTE
The maintenance bypass contacts are normally-open. To ensure proper bypass
operation, DO NOT use the blue wire (it is normally-closed).
18.
Replace the UPS wiring access cover and conduit landing plate.
Содержание Powerware 9355
Страница 1: ...Powerware Series Eaton 9355 UPS 10 15 kVA User s Guide...
Страница 2: ......
Страница 3: ...Powerware Series Eaton 9355 UPS 10 15 kVA User s Guide...
Страница 12: ...INTRODUCTION Eaton 9355 UPS 10 15 kVA User s Guide S 164201594 Rev D www eaton com powerquality 4...
Страница 16: ...SAFETY WARNINGS Eaton 9355 UPS 10 15 kVA User s Guide S 164201594 Rev D www eaton com powerquality 8...
Страница 36: ...UPS INSTALLATION Eaton 9355 UPS 10 15 kVA User s Guide S 164201594 Rev D www eaton com powerquality 28...
Страница 66: ...STABILIZING THE CABINET Eaton 9355 UPS 10 15 kVA User s Guide S 164201594 Rev D www eaton com powerquality 58...
Страница 88: ...COMMUNICATION Eaton 9355 UPS 10 15 kVA User s Guide S 164201594 Rev D www eaton com powerquality 80...
Страница 112: ...SPECIFICATIONS Eaton 9355 UPS 10 15 kVA User s Guide S 164201594 Rev D www eaton com powerquality 104...
Страница 116: ...TROUBLESHOOTING Eaton 9355 UPS 10 15 kVA User s Guide S 164201594 Rev D www eaton com powerquality 108...
Страница 119: ......
Страница 120: ...164201594D 164201594 D...