![Eaton Powerware 9155 Скачать руководство пользователя страница 23](http://html1.mh-extra.com/html/eaton/powerware-9155/powerware-9155_manual_3698416023.webp)
User’s Guide P-164000628
P-164000628—Rev 05
15
C
Chhaapptteerr 44 O
Oppeerraattiioonn
44..11
N
Noo B
Brreeaakk TTrraannssffeerr ffrroom
m U
UP
PS
S M
Mooddee ttoo S
Seerrvviiccee M
Mooddee
It is critical that the following steps are followed to ensure correct and safe operation.
Do not attempt to push the red interlock button or attempt to move the bypass switch handle if the UPS is
operating on battery power.
Refer to the UPS user guide or call the Eaton service help desk for specific BPM to UPS signal functionality.
To turn the BPM to SERVICE:
1.
Press and hold the red button and turn the switch to LINE (see
NOTE
Pressing the red button sends the UPS into Internal Bypass mode. This allows the UPS
output to synchronize with utility for safe, uninterrupted transfer.
The UPS is now in LINE mode. The critical load is fed directly from utility and the UPS remains energized
from utility power. The UPS may be left in this mode while trying to troubleshoot, gather alarms from the
UPS, or perform other preventative maintenance activities.
Figure 15. From UPS to LINE
2.
Turn the switch from LINE to SERVICE (see
). The critical load is fed directly from utility and the
UPS is now completely disconnected from AC power. Ensure that the UPS is off and the terminals are
completely de-energized before performing any maintenance on the UPS.
Содержание Powerware 9155
Страница 4: ...iv User s Guide P 164000628 P 164000628 Rev 05 Table of Contents...
Страница 6: ...vi User s Guide P 164000628 P 164000628 Rev 05 List of Figures...
Страница 8: ...viii User s Guide P 164000628 P 164000628 Rev 05 List of Tables...
Страница 18: ...10 User s Guide P 164000628 P 164000628 Rev 05 Signal Wire Routing...
Страница 26: ...18 User s Guide P 164000628 P 164000628 Rev 05 No Break Transfer from Service Bypass to UPS Mode...
Страница 28: ...P 16400062805 P 164000628 05...