background image

Technical Spec i fi ca tions

© 2005 Eaton Corporation 
All Rights Reserved 
Printed in Australia  

5/06 Rev 1

HEAD OFFICE  
Eaton Power Quality Pty Ltd
10 Kent Road 
Mascot  NSW  2020 
Phone: +61 2 9693 9366 
Fax: +61 2 8338 1159

www.powerware.com.au

Sales 1300 UPS UPS 
Service 1300 303 059

SALES OFFICES 
Queensland 
Phone: +61 7 3891 1211 
Fax: +61 7 3891 2492

Victoria 
Phone: + 61 3 9706 5662 
Fax: + 61 3 9794 9150

South Australia  
Phone: +61 8 8347 3622 
Fax: +61 8 8445 6328

Western Australia 
Phone: +61 8 9240 5655 
Fax: + 61 8 9240 5644

Wellington New Zealand 
Phone: + 64 4 477 4717 
Fax: +64 4 477 3691

Powerware and ABM are trade names, 
trademarks and/or service marks of 
Eaton Power Quality Corporation 
or its subsidiaries and affiliates. All 
other trademarks are property of their 
respective owners.

* Up to 4 EBMs can be connected. EBM runtimes include internal batteries. This guide provides typical application information. Battery run times are approximate and 
may vary with equipment, configuration, battery age, temperature, etc.

Battery Runtimes (in minutes full load/half load)* 

Model 

Standard Internal 

Batteries

1 EBM 

2 EBMs 

3 EBMs 

4 EBMs

1000VA 

5/16 

48/110 

100/220 

170/6h 

4h/8h

1500VA 

6/17 

33/79 

63/146 

92/174 

120/201

2000VA 

6/15 

30/70 

60/190 

90/215 

120/240

2200VA 

5/14 

26/60 

55/170 

81/198 

106/224

POWERWARE 5125

Rating 

1000VA 

1500VA 

2000VA 

2200VA

Part Number 

51251000A 

51251500A 

51252000A 

51252200A

Capacity (VA/Watts) 

1000/700 

1500/1050 

2000/1400 

2200/1600

Dimensions WxDxH (mm) 

162x401x250 

162x467x250 

205x493x250 

205x493x250

Weight (kg) 

16 

23 

31 

31

Input Connection 

IEC320/10A 

IEC320/10A 

IEC320/10A 

IEC320/16A

Output Connection 

4 x AUST. 10A 

4 x AUST. 10A 

6 x AUST. 10A 

6 x AUST.10A

Typical runtime (Full load) 

5 min 

6 min 

6 min 

5 min

Operational 

Nominal input voltage (Vac) 

220/230/240 Vac

Input voltage range 

166-276 VAC (+15/-30% of nominal)

Operating frequency 

50/60 Hz auto sensing

Input power factor 

Same as load

Nominal output voltage 

220/230/240 VAC

Output voltage regulation 

-10%/+6% of selected nominal voltage

Overload capacity 

110% 3 min; 150% 10 cycles

Efficiency 

95%

User interface 

LED Information 

LED display

Standard communication ports 

RS232

Optional 

SNMP/WEB card, USB card, relay cards

Environmental 

Operating temperature 

0oC - +40oC

Storage temperature 

-15oC - +55oC

Altitude 

< 3000 m

Audible noise at 1 metre 

< 45dB normal mode 
< 50dB battery mode

Certification 

Markings 

CE/GS/UL/C-Tick

Safety 

EN 50091-1-1 & UL 1778

EMC 

EN 50091-2, EN6100-3-2