ELECTRICAL INSTALLATION
Eaton 9PXTFMR5, 9PXPPDM2, 9PXTFMR11, and 9PXPPDM1 User's Guide
S
P-164000200 Rev 4
17
Procedure
To wire the I/O terminal block for the 9PXPPDM2:
1.
Switch off utility power at the distribution point where the
9PXPPDM2 model will be connected. Be absolutely sure there is no
power.
2.
Verify that the output circuit breaker is in the OFF position (see
“Rear Panels” on page 52).
3.
On the front cover, unsnap and remove the square center cover.
4.
Verify that the bypass switch is in the UPS (normal) position:
S
If the bypass switch is set to UPS, replace the square center
cover and go to Step 5.
S
If the bypass switch is set on Bypass, turn the bypass switch to
the UPS (normal) position (see Figure 8). Replace the square
center cover and go to Step 5.
208V
2
4
0
V
NORMAL
BYPASS
Figure 8. Resetting the Switch to UPS (Normal)
5.
Use a Phillips-head screwdriver to remove the screw to detach the
terminal block cover. Retain the cover and screw (see Figure 9).
Содержание PowerPass 9PXPPDM1
Страница 10: ...INTRODUCTION Eaton 9PXTFMR5 9PXPPDM2 9PXTFMR11 and 9PXPPDM1 User s Guide S P 164000200 Rev 4 4...
Страница 12: ...SAFETY Eaton 9PXTFMR5 9PXPPDM2 9PXTFMR11 and 9PXPPDM1 User s Guide S P 164000200 Rev 4 6...
Страница 20: ...EQUIPMENT INSTALLATION Eaton 9PXTFMR5 9PXPPDM2 9PXTFMR11 and 9PXPPDM1 User s Guide S P 164000200 Rev 4 14...
Страница 40: ...VOLTAGE SELECTION Eaton 9PXTFMR5 9PXPPDM2 9PXTFMR11 and 9PXPPDM1 User s Guide S P 164000200 Rev 4 34...
Страница 50: ...STARTUP Eaton 9PXTFMR5 9PXPPDM2 9PXTFMR11 and 9PXPPDM1 User s Guide S P 164000200 Rev 4 44...
Страница 54: ...MAINTENANCE BYPASS Eaton 9PXTFMR5 9PXPPDM2 9PXTFMR11 and 9PXPPDM1 User s Guide S P 164000200 Rev 4 48...
Страница 62: ...SERVICE AND SUPPORT Eaton 9PXTFMR5 9PXPPDM2 9PXTFMR11 and 9PXPPDM1 User s Guide S P 164000200 Rev 4 56...