ELECTRICAL INSTALLATION
Eaton 9PXTFMR5, 9PXPPDM2, 9PXTFMR11, and 9PXPPDM1 User's Guide
S
P-164000200 Rev 4
16
9PXPPDM2 Electrical Installation
This section provides terminal block wiring requirements and electrical
installation procedures for the 9PXPPDM2 model.
Requirements
The 9PXPPDM2 model requires a dedicated branch circuit that meets
the following requirements:
S
30A circuit with short circuit and overcurrent protection
S
208/240 Vac
S
Single phase
S
50/60 Hz
S
Breaker must be wall-mounted and readily accessible to the operator
S
Flexible metal conduit (recommended for ease of service and
maintenance)
Figure 7 shows the 9PXPPDM2 block diagram. The 9PXPPDM2 I/O
terminal block is hardwired.
Voltage Selection
To UPS
Output
From UPS
Input
Transformer
AC Input
Transformer
AC Output
120
120
240
L1
L2
G
N
G
G
L1
L2
G
TB (x3)
TB (x4)
30A CB
30A MBP
30A
L6-30P
L6-30R
Figure 7. 9PXPPDM2 Block Diagram
Содержание PowerPass 9PXPPDM1
Страница 10: ...INTRODUCTION Eaton 9PXTFMR5 9PXPPDM2 9PXTFMR11 and 9PXPPDM1 User s Guide S P 164000200 Rev 4 4...
Страница 12: ...SAFETY Eaton 9PXTFMR5 9PXPPDM2 9PXTFMR11 and 9PXPPDM1 User s Guide S P 164000200 Rev 4 6...
Страница 20: ...EQUIPMENT INSTALLATION Eaton 9PXTFMR5 9PXPPDM2 9PXTFMR11 and 9PXPPDM1 User s Guide S P 164000200 Rev 4 14...
Страница 40: ...VOLTAGE SELECTION Eaton 9PXTFMR5 9PXPPDM2 9PXTFMR11 and 9PXPPDM1 User s Guide S P 164000200 Rev 4 34...
Страница 50: ...STARTUP Eaton 9PXTFMR5 9PXPPDM2 9PXTFMR11 and 9PXPPDM1 User s Guide S P 164000200 Rev 4 44...
Страница 54: ...MAINTENANCE BYPASS Eaton 9PXTFMR5 9PXPPDM2 9PXTFMR11 and 9PXPPDM1 User s Guide S P 164000200 Rev 4 48...
Страница 62: ...SERVICE AND SUPPORT Eaton 9PXTFMR5 9PXPPDM2 9PXTFMR11 and 9PXPPDM1 User s Guide S P 164000200 Rev 4 56...