UPS Installation Plan and Unpacking
Eaton
®
Power Xpert
®
9395P-900 UPS Installation and Operation Manual P-164000501—Rev 09
www.eaton.com/powerquality
3-31
NOTE 1
V
Because of the future upgradability to a fully rated 480V 900 kVA UPS with the addition of the FI-UPM, these conduit sizes are specified
for a 900 kVA UPS.
NOTE 2
V
Bypass conduit data is not applicable to IOM configurations.
Battery Conductor Routing
Table 3-22. 480V Power Cable Conduit Requirements
UPS Model
Voltage
Terminal
Number of
Wires in
Conduit
Minimum Conduit
Trade Size
Number of
Conduits
Eaton 9395P-900/900*
Eaton 9395P-900/900
Eaton 9395P-900/825
480 Vac
AC Input to UPS Rectifier
(A, B, C, Ground)
4
3
5
AC Input to Bypass and Output
(A, B, C, Ground)
4
3
4
DC
(Common
Battery)
Battery
(Positive, Negative, Ground)
5
3.5
5
Eaton 9395P-900/750
Eaton 9395P-900/675
480 Vac
AC Input to UPS Rectifier
(A, B, C, Ground)
4
3
4
AC Input to Bypass and Output
(A, B, C, Ground)
4
3
3
DC
(Common
Battery)
Battery
(Positive, Negative, Ground)
5
3.5
4
Eaton 9395P-900/600*
Eaton 9395P-900/600
Eaton 9395P-900/550
Eaton 9395P-900/500
Eaton 9395P-900/450
See Note 1
480 Vac
AC Input to UPS Rectifier
(A, B, C, Ground)
4
3
5
AC Input to Bypass and Output
(A, B, C, Ground)
4
3
4
DC
(Common
Battery)
Battery
(Positive, Negative, Ground)
5
3.5
5
All models
DC
(Separate
Battery -
per UPM)
Battery
(Positive, Negative, Ground)
7
4
1