![Eaton Power Xpert 9395C Скачать руководство пользователя страница 42](http://html1.mh-extra.com/html/eaton/power-xpert-9395c/power-xpert-9395c_installation-and-operation-manual_4265554042.webp)
Eaton Power Xpert 9395C UPS Installation and Operation Manual 164000821—Rev 06
25
Table 10. Recommended Installation Parts and Tools (Not Supplied by Eaton) (Continued)
Part
Size
Quantity
Manufacturer
Part Number
Notes
350 MCM
Thomas & Betts
54872BE
400 MCM
Thomas & Betts
54874BE
500 MCM
Thomas & Betts
54876BE
Manual Hydraulic Crimp Tool
14 Ton
1
Thomas & Betts
TBM14M
Die Set
N/A
1
Thomas & Betts
15506
Conduit sizes were chosen from NEC Table 4, Electrical Metallic Tubing (EMT). See
for conduit
requirements.
Per NEC article 300, 3(B)(1), all three-phase conductors must be run in the same conduit. Neutral and ground
must be run in the same conduit as the phase conductors.
Conduit is sized to accommodate one neutral conductor the same size as the phase conductor and one ground
conductor sized in accordance with NEC Table 250.122.
Conduit sizes listed are for copper wiring only.
Table 11. 480V Power Cable Conduit Recommendations
UPS Model
Voltage
Terminal
Number of
Wires in
Conduit
Minimum
Conduit
Trade Size
Number
of
Conduits
Eaton 9395C-1000/1000
Eaton 9395C-1000/1100
480 Vac
AC Input to UPS Rectifier
(A, B, C, Ground)
4
3
5
AC Input to Bypass and
Output
(A, B, C, Ground)
4
3
5
DC (Common
Battery)
Battery
(Positive, Negative, Ground)
5
3.5
5
Eaton 9395C-1100/1100
480 Vac
AC Input to UPS Rectifier
(A, B, C, Ground)
4
3
6
AC Input to Bypass and
Output
(A, B, C, Ground)
4
3
5
DC (Common
Battery)
Battery
(Positive, Negative, Ground)
7
4
4
Battery Conductor Routing: Refer to the notes at the bottom of
Input/Output Ratings and External
Wiring Requirements.
External overcurrent protection and disconnect are not provided by this product, but are required by codes.
Refer to
for wiring requirements. If an output lockable disconnect is required, it is to be supplied by the
customer.
lists the recommended rating for input circuit breakers with breaker ratings for rectifier input.
Содержание Power Xpert 9395C
Страница 8: ......
Страница 16: ...xvi Eaton Power Xpert 9395C UPS Installation and Operation Manual 164000821 Rev 06 List of Figures...
Страница 121: ...104 Eaton Power Xpert 9395C UPS Installation and Operation Manual 164000821 Rev 06 Understanding UPS Operation...
Страница 163: ...146 Eaton Power Xpert 9395C UPS Installation and Operation Manual 164000821 Rev 06 Communication...
Страница 171: ...154 Eaton Power Xpert 9395C UPS Installation and Operation Manual 164000821 Rev 06 UPS Maintenance...
Страница 175: ...16400082106 164000821 06...