![Eaton Power Xpert 9395C Скачать руководство пользователя страница 30](http://html1.mh-extra.com/html/eaton/power-xpert-9395c/power-xpert-9395c_installation-and-operation-manual_4265554030.webp)
Eaton Power Xpert 9395C UPS Installation and Operation Manual 164000821—Rev 06
13
33..22..33
IInnssttaallllaattiioonn C
Coonnssiiddeerraattiioonnss
The UPS system installation must meet the following guidelines:
•
The system must be installed on a level floor suitable for computer or electronic equipment.
•
The system must be installed in a temperature and humidity controlled indoor area free of conductive
contaminants.
Failure to follow guidelines may void your warranty.
The UPS equipment operating environment must meet the weight requirements shown in
and the size
requirements shown in
through
. Dimensions are in millimeters (inches).
includes the weights of the heaviest cabinet configuration. Actual weights may be less due to the
installed configuration. Weights are in kilograms (pounds).
Table 2. UPS Cabinet Maximum Weights
Model
Section
Maximum Weight
kg (lb)
Shipping
Installed
Eaton 9395C-1000/1000
UPS (Total)
2539.8 (5599)
2401.8 [5295]
Eaton 9395C-1000/1100
ISBM
817.4 (1802)
773.4 (1705)
Eaton 9395C-1100/1100
PM
1722.4 (3797)
1628.4 (3590)
NOTE
describes power ratings
The UPS cabinets use forced air cooling to regulate internal component temperature. Air inlets are in the front
of the cabinet and outlets are in the top. Allow clearance in front of and above each cabinet for proper air
circulation. The clearances required around the UPS cabinet are shown in
Dimensions are in millimeters (inches).
Table 3. UPS Cabinet Clearances
From Top of Cabinet
457.2 mm (18”) minimum clearance for ventilation
From Front of Cabinet
914.4 mm (36”) working space
From Back of Cabinet
None Required
From Right Side of Cabinet
None Required
From Left Side of Cabinet
None Required
The basic environmental requirements for operation of the UPS are:
•
Recommended Operating Range: 20–25ºC (68–77ºF)
•
Maximum Relative Humidity: 95%, non-condensing
Содержание Power Xpert 9395C
Страница 8: ......
Страница 16: ...xvi Eaton Power Xpert 9395C UPS Installation and Operation Manual 164000821 Rev 06 List of Figures...
Страница 121: ...104 Eaton Power Xpert 9395C UPS Installation and Operation Manual 164000821 Rev 06 Understanding UPS Operation...
Страница 163: ...146 Eaton Power Xpert 9395C UPS Installation and Operation Manual 164000821 Rev 06 Communication...
Страница 171: ...154 Eaton Power Xpert 9395C UPS Installation and Operation Manual 164000821 Rev 06 UPS Maintenance...
Страница 175: ...16400082106 164000821 06...