Eaton

®

Power Xpert

®

9395P-900 Installation and Operation Manual 164000501—Rev 12

66..22..66

B

Baatttteerryy M

Mooddee

The UPS automatically transfers to Battery mode if a utility power outage occurs, or if the utility power does not
conform to specified parameters. In Battery mode, the battery provides emergency DC power that the inverter
converts to AC power.

Figure 71

shows the path of electrical power through the UPS system when operating in Battery mode.

During a utility power failure, the rectifier no longer has an AC utility source from which to supply the DC output
current required to support the inverter. The input contactor K1 opens and the battery instantaneously supplies
energy to the battery converter. The converter either bucks or boosts the voltage so that the inverter can
support the customer's load without interruption. If bypass is common with the rectifier input, the backfeed
protection contactor K5 also opens. The opening of contactors K1 and K5 prevent system voltages from
bleeding backwards through the static switch and rectifier snubber components and re-entering the input
source.

If the input power fails to return or is not within the acceptance windows required for normal operation, the
battery continues discharging until a DC voltage level is reached where the inverter output can no longer
support the connected loads. When this event occurs, the UPS issues another set of audible and visual alarms
indicating SHUTDOWN IMMINENT. Unless the rectifier has a valid AC input soon, the output can be supported
for only two minutes before the output of the system shuts down. If the bypass source is available, the UPS
transfers to bypass instead of shutting down.

If at any time during the battery discharge the input power becomes available again, contactors K1 and K5 close
and the rectifier begins to supply DC current to the converter and inverter. At this point, the unit returns to
Online mode. Depending on the total load and the duration of the battery discharge, battery current limit alarms
may be seen for a short time due to the current required to recharge the battery.

Figure 71. Path of Current Through the UPS in Battery Mode

K1

K3

K5

K1

K3

K2

Main Power Flow

Trickle Current

Energized 

De-Energized

Contactors

Breakers

Bypass Input

Rectifier

Input

Input

Breaker

(CB1)

Battery

Breaker

Output

Closed

Open

 

Rectifier

Inverter

Static

Switch

Battery

Converter

Battery

NOTE  

On a UPS configured as an IOM, the bypass input, static switch, bypass breaker (CB4), and K5 are not present.

NOTE  

On a UPS configured with a Continuous Static Switch (CSS), bypass breaker (CB4) is not present.

Understanding UPS Operation

Содержание Power Xpert 9395 High Performance

Страница 1: ...0501 Revision 12 900 kW 900 kVA Installation and Operation Manual For use with Two UPM 450 600 kVA Three UPM 675 900 kVA and Plus 1 675 900 kVA UPS Models Eaton Power Xpert 9395 High Performance 9395P...

Страница 2: ...INSTRUCTIONS This manual contains important instructions that you should follow during installation and maintenance of the UPS Please read all instructions before operating the equipment and save this...

Страница 3: ...m a host of threats including power outages surges lighting strikes and enable you to monitor and control your power infrastructure We trust that your Eaton 9395 Uninterruptible Power Supply system wi...

Страница 4: ...e license to use the Firmware in conjunction with the operation of the product to which the Firmware pertains or other products as described by Eaton in the Documentation Licensee does not acquire any...

Страница 5: ...CT IS AT LICENSEE S SOLE RISK 5 0 GENERAL PROVISIONS 5 1 Update Policy Eaton may from time to time but has no obligation to create Updates of the Firmware or components thereof 5 2 Limitation on Liabi...

Страница 6: ...nctions Programs Pages Programs aspx or to any national of any such country wherever located who intends to transmit or transport the Firmware back to such country ii to any end user who Licensee know...

Страница 7: ...nfidential aspects of the Firmware shall not be disclosed to third parties without the prior written consent of Eaton Accordingly Eaton will be entitled to preliminary and permanent injunctive and oth...

Страница 8: ......

Страница 9: ...System 7 1 3 6 Input Output Module Configuration 7 1 3 7 Continuous Static Switch 7 1 3 8 Inherent Redundancy 8 1 3 9 Energy Saver and High Alert Modes 8 1 3 10 Variable Module Management System and H...

Страница 10: ...attery Interface Connections 95 4 9 3 X Slot Connections 96 4 10 Installing a REPO Switch 97 4 11 Installing Options Accessories and Distributed Bypass Control Wiring 101 4 12 Initial Startup 101 4 13...

Страница 11: ...mation Pop Up 165 7 3 7 Meters Summary Screen 165 7 3 8 Input Bypass and Output Meters Screens 166 7 3 9 Battery Meters Screen 171 7 3 10 System Events Main Screen 172 7 3 11 User Log 172 7 3 12 Batte...

Страница 12: ...ode 197 7 5 7 Start Variable Module Management System High Alert Mode 197 7 5 8 Starting the Distributed Bypass System in Bypass Mode 197 7 5 9 Starting the UPS UPMs 198 7 5 10 Starting a Single UPM 1...

Страница 13: ...aintenance 218 9 2 1 DAILY Maintenance 218 9 2 2 MONTHLY Maintenance 218 9 2 3 PERIODIC Maintenance 221 9 2 4 ANNUAL Maintenance 221 9 2 5 BATTERY Maintenance 221 9 3 Installing Batteries 222 9 4 Recy...

Страница 14: ...xiv Eaton Power Xpert 9395P 900 Installation and Operation Manual 164000501 Rev 12 Table of Contents...

Страница 15: ...Center of Gravity FI UPM and 2X UPMs 32 Figure 19 UPS Center of Gravity 3X UPMs 33 Figure 20 UPS Center of Gravity 2X UPMs 34 Figure 21 Remote EPO Switch Dimensions 35 Figure 22 UPS Cabinet as Shipped...

Страница 16: ...l Chain Wiring with MOBs 111 Figure 60 Remote Monitor Panel II and Remote Monitor Panel II Terminal Locations 113 Figure 61 Remote Monitor Panel II Relay Interface Module II or Supervisory Contact Mod...

Страница 17: ...0 Configurations 151 Figure 89 Typical Distributed Bypass System 2 1 and 3 0 Configurations 152 Figure 90 Typical Distributed Bypass System 3 1 and 4 0 Configurations 153 Figure 91 UPS Controls and In...

Страница 18: ...179 Figure 126 Disable ESS Screen 180 Figure 127 High Alert Timer Screen 180 Figure 128 Statistics Basic Screen 181 Figure 129 Statistics Data Detail Screen 181 Figure 130 ESS Comparison Screen 182 F...

Страница 19: ...e Battery 42 Table 14 400V Input Output Ratings and External Wiring Requirements for the Three Four UPM Models Common Battery 43 Table 15 400V Input Output Ratings and External Wiring Requirements for...

Страница 20: ...ble 36 RMP II RIM II or SCM II Wiring Terminations 114 Table 37 J1 through J4 Interface Connectors 116 Table 38 Oneline Configurations 130 Table 39 Status Indicators 158 Table 40 Security Levels and F...

Страница 21: ...ularities that are inherent in commercial utility power Working with a building s electrical system the UPS system supplies clean consistent power that sensitive electronic equipment requires for reli...

Страница 22: ...S The Power Xpert 9395P 900 Two UPM UPS 450 600 kVA contains two sections see Figure 1 an ISBM or an IOM section rated for a maximum of 900 kVA to provide future upgradability a UPM section containin...

Страница 23: ...to provide future upgradability a UPM section containing two UPMs each UPM rated for a maximum of 300 kVA for a total maximum of 600 kVA an FI UPM section to provide N 1 redundancy for the system if t...

Страница 24: ...hree UPM UPS model 675 900 kVA contains two sections see Figure 3 an ISBM or an IOM section rated for a maximum of 1200 kVA to provide future upgradability a UPM section containing three UPMs Each UPM...

Страница 25: ...of 300 kVA for a total maximum of 900 kVA an FI UPM section which provides N 1 redundancy for the system see paragraph 1 3 2 Field Installed UPM Figure 4 Eaton Xpert 9395P 900 Three UPM Plus 1 FI UPM...

Страница 26: ...information X Slot Communication Bays Four communication bays are standard equipment One to four optional X Slot connectivity cards can be installed in the UPS module at any time X Slot cards are quic...

Страница 27: ...st tr riib bu ut te ed d B By yp pa as ss s S Sy ys st te em m There are two types of redundancy UPS based based on the number of UPSs and UPM based based on the number of UPMs NOTE All UPSs in the di...

Страница 28: ...to double conversion mode or if in double conversion mode remains in double conversion mode for a default time period of one hour High Alert mode allows the user to place the unit in double conversio...

Страница 29: ...spatch of technicians PredictPulse requires a Power Xpert Gateway Card PXGX connectivity card in an X Slot communication bay and an Environmental Monitoring Probe EMP for battery temperature humidity...

Страница 30: ...TO OPERATOR S MANUAL Refer to your operator s manual for additional information such as important operating and maintenance instructions This symbol indicates that you should not discard the UPS or t...

Страница 31: ...optional features procedures for using with the UPS and information about maintenance Refer to the Eaton 9395P Field Installed UPM Mechanical Installation Manual P 164000503 for the following addition...

Страница 32: ...12 Eaton Power Xpert 9395P 900 Installation and Operation Manual 164000501 Rev 12 Introduction...

Страница 33: ...carry live voltage even when the UPS is disconnected from an AC source To reduce the risk of fire or electric shock install this UPS in a temperature and humidity controlled indoor environment free of...

Страница 34: ...onnement du produit Lors de la v rification du fonctionnement de l UPS ne pas enlever la mise la terre si des charges y sont raccord es Ne pas ouvrir ni ab mer les batteries L lectrolyte qu elles cont...

Страница 35: ...r les portes de l onduleur ferm es et les panneaux avant en place pour garantir une circulation ad quate de l air de refroidissement et pour prot ger le personnel des tensions dangereuses dans l unit...

Страница 36: ...ompl tement les fourches dans les passages de fourche de la base NE PAS ins rer partiellement les fourches dans les passages pour d placer l armoire Il est possible d ins rer partiellement les fourche...

Страница 37: ...nd Chapter 4 UPS System Installation to create a logical plan for installing the system 3 3 2 2 P Pr re ep pa ar riin ng g t th he e S Siit te e For the UPS system to operate at peak efficiency the in...

Страница 38: ...sues One is the creation of microclimates which are persistent variations of temperature and or RH within a single room for example one side of the room is always cooler than the other side no matter...

Страница 39: ...9395P 900 900 Eaton 9395P 900 900 Eaton 9395P 900 825 Eaton 9395P 900 750 Eaton 9395P 900 675 ISBM CSS 808 1782 764 1684 3XUPM 496 1094 475 1047 FI UPM 496 1094 764 1684 Eaton 9395P 900 600 Eaton 9395...

Страница 40: ...e same room as the UPS the battery cabinet environmental requirements supercede the UPS requirements Operating temperatures above the recommended range will result in decreased battery life and perfor...

Страница 41: ...2 18 2 Eaton 9395P 900 550 CSS 550 kVA 550 kVA 480 480 72 2 18 2 Eaton 9395P 900 500 CSS 500 kVA 500 kVA 480 480 63 8 16 1 Eaton 9395P 900 450 CSS 450 kVA 450 kVA 480 480 54 1 13 6 NOTE CSS Continuou...

Страница 42: ...41 7 7 Eaton 9395P 900 450 CSS 450 kVA 450 kVA 400 400 63 3 15 9 NOTE CSS Continuous Static Switch IOM Input Output Module Table 7 380V Air Conditioning and Ventilation Requirements During Full Load O...

Страница 43: ...n Power Xpert 9395P 900 Installation and Operation Manual 164000501 Rev 12 23 Figure 5 UPS Cabinet Dimensions Three UPM Front View Dimensions are in millimeters inches UPS Installation Plan and Unpack...

Страница 44: ...Xpert 9395P 900 Installation and Operation Manual 164000501 Rev 12 Figure 6 UPS Cabinet Dimensions Two UPM Front View Dimensions are in millimeters inches 1880 74 0 3036 9 119 5 UPS Installation Plan...

Страница 45: ...pert 9395P 900 Installation and Operation Manual 164000501 Rev 12 25 Figure 7 UPS Cabinet Dimensions Right Side View Dimensions are in millimeters inches 892 35 40 1 6 830 32 7 UPS Installation Plan a...

Страница 46: ...ev 12 Figure 8 ISBM Section Dimensions Front View Dimensions are in millimeters inches 1880 74 0 1705 67 1 For 4 wire systems only Figure 9 ISBM Section Dimensions Top View Front Dimensions are in mil...

Страница 47: ...l 164000501 Rev 12 27 Figure 10 ISBM Section Dimensions Bottom View Front Dimensions are in millimeters inches Figure 11 UPM Section Dimensions Three UPM Front View Dimensions are in millimeters inche...

Страница 48: ...al 164000501 Rev 12 Figure 12 UPM Section Dimensions Three UPM Top View Front Dimensions are in millimeters inches Figure 13 UPM Section Dimensions Two UPM Front View Dimensions are in millimeters inc...

Страница 49: ...Installation and Operation Manual 164000501 Rev 12 29 Figure 14 UPM Section Dimensions Two UPM Top View Front Dimensions are in millimeters inches 1015 43 40 0 34 44 1 4 37 14 1 5 758 83 29 9 UPS Inst...

Страница 50: ...501 Rev 12 Figure 15 UPM Section Dimensions FI UPM Front View Dimensions are in millimeters inches 1880 74 0 735 9 29 0 Figure 16 UPM Section Dimensions FI UPM Top View Front Dimensions are in millime...

Страница 51: ...ty FI UPM and 3X UPMs 1880 74 0 DIMENSIONS MM IN CENTER OF GRAVITY THREE UPMS 361 14 3 362 14 3 357 14 1 900 35 4 918 36 1 850 33 5 362 14 3 918 36 1 900 1 kVA UPS FI UPM ISBM IOM 3XUPM A B A B Side V...

Страница 52: ...ity FI UPM and 2X UPMs DIMENSIONS MM IN CENTER OF GRAVITY THREE UPMS 361 14 3 362 14 3 357 14 1 900 35 4 918 36 1 850 33 5 362 14 3 918 36 1 900 1 kVA UPS FI UPM ISBM IOM 2XUPM A B 759 29 9 2119 83 4...

Страница 53: ...3 Figure 19 UPS Center of Gravity 3X UPMs DIMENSIONS MM IN CENTER OF GRAVITY THREE UPMS 360 14 3 357 14 1 896 35 3 850 33 5 362 14 3 918 36 1 900 kVA UPS ISBM 3XUPM A B 2172 85 5 983 38 7 1029 40 5 Si...

Страница 54: ...12 Figure 20 UPS Center of Gravity 2X UPMs DIMENSIONS MM IN CENTER OF GRAVITY TWO UPMS 360 14 3 357 14 1 896 35 3 850 33 5 362 14 3 918 36 1 900 1 kVA UPS ISBM 2XUPM A B 759 29 9 1850 72 8 A ISBM 2XUP...

Страница 55: ...fication is for copper wire with a 75 C rating Material and labor for external wiring requirements are to be provided by designated personnel If installing a maintenance bypass a minimum of two separa...

Страница 56: ...ted in Table 24 Select overcurrent protection input battery and output breakers according to the UPS nameplate rated for either 80 or 100 Follow all applicable NEC and local codes For three or four UP...

Страница 57: ...ions Battery Conductor Sizing Eaton strongly recommends using the specified DC conductor size and quantity shown above for optimum system performance and battery run time Battery Cable Routing Require...

Страница 58: ...each 500 3 500 3 500 3 500 3 500 3 AC Output to Critical Load Full Load Current 3 Phases 1 Ground D Amps 812 902 992 1083 1083 Minimum Conductor Size Number per Pole AWG or kcmil each 500 3 500 3 500...

Страница 59: ...attery Conductor Sizing Eaton strongly recommends using the specified DC conductor size and quantity shown above for optimum system performance and battery run time Battery Cable Routing Requirements...

Страница 60: ...500 3 500 3 500 3 500 3 500 3 AC Output to Critical Load Full Load Current 3 Phases 1 Ground D Amps 541 601 662 722 722 Minimum Conductor Size Number per Pole AWG or kcmil each 500 4 500 4 500 4 500 4...

Страница 61: ...rs A C and D map to Figure 82 NOTE Bypass wiring data is not applicable to IOM configurations Battery Conductor Sizing Eaton strongly recommends using the specified DC conductor size and quantity show...

Страница 62: ...1 Positive 1 Negative AWG or kcmil each 500 3 500 3 500 3 500 3 500 3 500 3 500 3 AC Output to Critical Load Five Wire Full Load Current 3 Phases 1 Neutral 1 Ground D Total Amps 626 696 765 835 939 10...

Страница 63: ...rs A C and D map to Figure 82 NOTE Bypass wiring data is not applicable to IOM configurations Battery Conductor Sizing Eaton strongly recommends using the specified DC conductor size and quantity show...

Страница 64: ...1 Positive 1 Negative AWG or kcmil each 500 3 500 3 500 3 500 3 500 3 500 3 500 3 AC Output to Critical Load Five Wire Full Load Current 3 Phases 1 Neutral 1 Ground D Total Amps 650 722 794 866 974 10...

Страница 65: ...tters A C and D map to Figure 82 NOTE Bypass wiring data is not applicable to IOM configurations Battery Conductor Sizing Eaton strongly recommends using the specified DC conductor size and quantity s...

Страница 66: ...00 4 500 4 500 5 500 6 500 6 500 6 NOTE Callout letters A B C and D map to Figure 72 NOTE If a 4 pole Automatic Transfer Switch ATS is used to connect the UPS to a generator or alternative input sourc...

Страница 67: ...UPM 2 E3A UPM 3 E3A UPM 4 Four UPM Model Phase C 4 stud mounting 14 2 10 4 M8 AC Output from UPM Section E9A UPM 1 E9A UPM 2 E9A UPM 3 E9A UPM 4 Phase A 4 stud mounting 14 2 10 4 M8 E10A UPM 1 E10A U...

Страница 68: ...Phase A 6 2 bolt mounting 76 56 M12 E2 Phase B 6 2 bolt mounting 76 56 M12 E3 Phase C 6 2 bolt mounting 76 56 M12 AC Input to Bypass E6 Phase A 6 2 bolt mounting 76 56 M12 E7 Phase B 6 2 bolt mountin...

Страница 69: ...ery Input Output and Ground 180500037 120 Nut M12 86 Rectifier Input Bypass Input Battery Input Output and Ground 180200001 07 NOTE Bypass terminations are not applicable to IOM configurations Table 2...

Страница 70: ...put to Bypass and Output A B C Ground 4 3 4 DC Common Battery Battery Positive Negative Ground 5 3 5 3 All models DC Separate Battery per UPM Battery Positive Negative Ground 7 4 1 NOTE 1 Because of t...

Страница 71: ...9395P 900 550 Eaton 9395P 900 500 415 Vac AC Input to UPS Rectifier A B C Ground 5 3 5 AC Input to Bypass and Output A B C Ground 4 3 4 DC Common Battery Battery Positive Negative Ground 6 3 6 Eaton...

Страница 72: ...Battery Battery Positive Negative Ground 8 3 5 4 Eaton 9395P 900 675 400 Vac 380 Vac AC Input to UPS Rectifier A B C Ground 6 3 6 AC Input to Bypass and Output A B C Ground 6 3 6 DC Common Battery Bat...

Страница 73: ...cable to IOM configurations Battery Conductor Routing Refer to the notes at the bottom of Table 8 to Table 17 Input Output Ratings and External Wiring Requirements External overcurrent protection and...

Страница 74: ...of fire connect only to a circuit provided with maximum input circuit breaker current ratings from Table 26 in accordance with the NEC ANSI NFPA 70 ATTENTION Pour r duire le risque d incendie ne branc...

Страница 75: ...ure upgradability to a fully rated 900 kW UPS with the addition of the FI UPM Eaton recommends using the breaker size specified for a 1100 kW UPS There is no manual DC disconnect device within the UPS...

Страница 76: ...5P 900 900 Eaton 9395P 900 600 800A Eaton 9395P 900 900 Eaton 9395P 900 825 Eaton 9395P 900 750 Eaton 9395P 900 675 Eaton 9395P 900 600 Eaton 9395P 900 550 Eaton 9395P 900 500 Eaton 9395P 900 450 700A...

Страница 77: ...attery Aux and 48 Vdc Shunt Trip signal wiring from the UPS must be connected to the DC source disconnect device Battery Aux and 48 Vdc Shunt Trip wiring should be a minimum of 18 AWG The REPO feature...

Страница 78: ...tor The output of this UPS will not directly support phase to neutral loads MOBs with dual auxiliary contacts are to be provided by the customer Table 27 lists the recommended rating for the MOBs The...

Страница 79: ...n position horizontale avant de les ins rer dans les passages de fourche NE PAS orienter les pointes de fourche vers le haut Ins rer compl tement les fourches dans les passages de fourche de la base N...

Страница 80: ...elles pourraient se renverser 3 Set the pallet on a firm level surface allowing a minimum clearance of 3m 10 ft on each side for removing the cabinet from the pallet NOTE The ISBM and UPM sections are...

Страница 81: ...Eaton Power Xpert 9395P 900 Installation and Operation Manual 164000501 Rev 12 61 Figure 22 UPS Cabinet as Shipped on Pallet ISBM Section For 4 wiring systems only UPS Installation Plan and Unpacking...

Страница 82: ...62 Eaton Power Xpert 9395P 900 Installation and Operation Manual 164000501 Rev 12 Figure 23 UPS Cabinet as Shipped on Pallet UPM Section UPS Installation Plan and Unpacking...

Страница 83: ...the conduit landing plates to add conduit landing holes as required Plate material is 16 gauge steel 1 5 mm 0 06 thick If perforated floor tiles are required for ventilation place them in front of the...

Страница 84: ...a section de l onduleur lorsque l armoire est soulev e ou d plac e Soulever ou d placer la section de l onduleur en n utilisant que les passages de fourche l avant ou l arri re V rifier que les fourch...

Страница 85: ...at the beginning of this procedure 2 Remove the three bolts securing the left side shipping bracket to the cabinet and three bolts securing the bracket to the pallet see Figure 24 or Figure 26 Remove...

Страница 86: ...g a forklift see the caution statement at the beginning of this procedure raise the UPS cabinet section until the cabinet bottom clears the pallet by approximately 3 mm 1 8 5 Pull the pallet from unde...

Страница 87: ...Operation Manual 164000501 Rev 12 67 Figure 26 Removing the UPM Section Left Side Shipping Bracket Shipping Bracket Bolts Shipping Bracket Bolts Pallet Left Side Shipping Bracket UPM Removable Front...

Страница 88: ...ted space to slide the sections together from the sides NOTE 2 For the following steps verify that the forklift or pallet jack is rated to handle the weight of the section see Table 2 for cabinet weig...

Страница 89: ...ft Side Panel Wireway Panel UPM Section 5 Remove the screws securing the left top panel and remove the panel see Figure 28 Retain the hardware for later use 6 Remove the screws securing the left middl...

Страница 90: ...nt of the cabinet bases are flush with each other see Figure 29 8 Reinstall the corner channel see Figure 28 and secure using the retained hardware 9 Reinstall the left middle panel see Figure 28 and...

Страница 91: ...View Base Bracket UPM Section Base ISBM Section Base Bracket from Kit Screw from Kit Screw from Kit 4 4 4 4 E Elle ec ct tr riic ca alllly y C Co on nn ne ec ct tiin ng g t th he e S Se ec ct tiio on...

Страница 92: ...Preparation for wiring and termination requirements NOTE AC output intercabinet power wiring harnesses are supplied attached to the interior left side panel of the UPM section see Figure 28 10 Locate...

Страница 93: ...ee B in Figure 35 20 In the UPM section see B in Figure 35 locate the coiled RJ 45 CAN cable Remove the wire ties securing the cable to the interior left side panel of the UPM section Route this cable...

Страница 94: ...74 Eaton Power Xpert 9395P 900 Installation and Operation Manual 164000501 Rev 12 Figure 31 ISBM Section Intercabinet Power Terminal Locations AC Input to ON OFF UPS System Installation...

Страница 95: ...n a UPS without CB1 UPM input wiring terminations are in the same positions on the bus bars installed in the place of CB1 NOTE On a UPS configured as an IOM UPM input wiring terminations are the same...

Страница 96: ...UPMs Cable 1G3 Black UPM 1 1E5A Cable 1G3 Black DC Input to UPM Cable 1G3 Red UPM 1 1E4A Cable 1G3 Red Cable 2G3 Black UPM 2 2E5A Cable 2G3 Black Cable 3G3 Black UPM 3 3E5A Cable 3G3 Black Cable 2G3 R...

Страница 97: ...le 3G4 3G5 Orange UPM 1 Cable 1G4 1G5 Brown UPM 2 Cable 2G4 2G5 Brown UPM 3 Cable 3G4 3G5 Brown UPM 1 Cable 1G4 1G5 Yellow UPM 2 Cable 2G4 2G5 Yellow UPM 3 Cable 3G4 3G5 Yellow UPM 1 Cable 1G4 1G5 Gra...

Страница 98: ...nterface Harness Locations Wiring Access Location of J50 J51 J61 and J70 Coiled Harnesses Location of RJ 45 Coiled CAN Cable UPM Wireway Location of P61 Harness Location of P50 P51 and P70 Harnesses U...

Страница 99: ...on Power Xpert 9395P 900 Installation and Operation Manual 164000501 Rev 12 79 Figure 36 Pl1 Interface Board Location Pl1 Interface Board Front ISBM Section Right Side Inside View UPS System Installat...

Страница 100: ...alled proceed to paragraph 4 7 Distributed Bypass Tie Cabinet Installation if installing a distributed bypass tie cabinet otherwise proceed to paragraph 4 8 Installing UPS External and Battery Power W...

Страница 101: ...up to remove them from the panel hanger brackets at the top of the cabinet 2 Remove the screws securing the top and bottom internal safety shield panels and remove the panels to gain access to the inp...

Страница 102: ...bris Shields ISBM Section Front Ventilation Grill Debris Shields Remove shields before operating system Three UPM Section Front Two UPM Section Front Ventilation Grill Debris Shields Remove shields be...

Страница 103: ...tion 5 Using hardware from the external wiring terminal hardware kit see Table 21 connect phase A B and C rectifier input power wiring from the utility source to the rectifier input terminals in the I...

Страница 104: ...ph 3 2 4 UPS System Power Wiring Preparation for wiring and termination requirements 10 Proceed to paragraph 4 8 2 Battery Power Wiring 11 Using hardware from the external wiring terminal hardware kit...

Страница 105: ...C E3 Phase B E2 AC Input to UPS Bypass Front Ground Terminals NOTE AC Input to Bypass terminals are not applicable to an IOM configuration Section A A 4 4 8 8 2 2 B Ba at tt te er ry y P Po ow we er...

Страница 106: ...ng the UPS for a common battery proceed to Step 3 if wiring for a separate battery proceed to Step 5 3 Using hardware from the external wiring terminal hardware kit see connect the positive negative a...

Страница 107: ...ert 9395P 900 Installation and Operation Manual 164000501 Rev 12 87 Figure 42 UPS Power Terminal Detail BB Common Battery DC Input from Battery E4 E5 DC Input from Battery Front Section B B UPS System...

Страница 108: ...DC Input from Battery UPM 1 DC Input from Battery E4 UPM 2 DC Input from Battery E4 UPM 3 UPM 4 FI UPM UPM 4 FI UPM 4 4 9 9 I In ns st ta alllliin ng g I In nt te er rf fa ac ce e C Co on nn ne ec ct...

Страница 109: ...mmunication bay To gain access to terminal block TB1 TB2 and the left interface entry conduit landing plates remove the screws securing the top internal safety shield panel and remove the panel Retain...

Страница 110: ...90 Eaton Power Xpert 9395P 900 Installation and Operation Manual 164000501 Rev 12 Figure 44 ISBM Section Interface Terminal Locations UPS System Installation...

Страница 111: ...al TB2 Name Description 1 Pull Chain Output Backup control for parallel operation 2 Pull Chain Common 3 Alarm Relay NC Output General purpose normally closed NC relay contact 4 Alarm Relay Common 5 Al...

Страница 112: ...ogrammable UPS alarm activated by a remote dry contact closure Default function set for maintenance bypass 10 Building Alarm 5 Return NOTE Return indicates connection to electronics circuit ground Com...

Страница 113: ...0 Vac and 28 Vdc NOTE Alarm relay normally open and normally closed return terminals are separated on the terminal board but are electrically in common NOTE Do not directly connect relay contacts to t...

Страница 114: ...mum connected between the alarm input and common terminal as shown Building alarm inputs can be programmed for use with either normally open or normally closed contacts All control wiring and relay an...

Страница 115: ...4 through Figure 49 NOTE When installing shunt trip and battery aux interface wiring to the UPS interface terminals conduit must be installed between the UPS and battery system 6 Remove the left inter...

Страница 116: ...Vdc Battery Aux Battery Aux Return 48 Vdc Battery Shunt Trip NOTE Battery aux and DC shunt trip wiring should be a minimum of 18 AWG 48 Vdc Battery Shunt Trip TB1 UPS 5 6 7 8 ST ST ST ST 4 4 9 9 3 3 X...

Страница 117: ...ure 44 and Figure 50 for X Slot communication bay locations 6 Close the door and secure the latch 7 Refer to the manual supplied with the X Slot card for operator instructions Figure 50 X Slot Communi...

Страница 118: ...wiring must be in accordance with NEC Article 725 Class 2 requirements To Install a REPO switch 1 Verify the UPS system is turned off and all power sources are removed See Chapter 7 UPS Operating Inst...

Страница 119: ...ening Torque 3 NO TB1 3 Twisted Wires 2 14 22 AWG 0 75 4 0 mm2 7 lb in 0 8 Nm 4 NO TB1 4 Figure 52 Normally Open REPO Switch Wiring 3 NO 1 NC UPS TB1 2 Return 4 Return REPO Switch NO Twisted Wires NOT...

Страница 120: ...be a latching type switch not tied to any other circuits NOTE REPO normally open and normally closed return terminals are separated on the terminal board but are electrically in common UPS TB1 2 Retur...

Страница 121: ...s other than verifying software and operating setup parameters Service personnel may request a copy of the completed Installation Checklist to verify all applicable equipment installations have been c...

Страница 122: ...o A remote battery disconnect control is mounted in its installed location and its wiring is terminated inside the UPS and battery cabinet OPTIONAL o Accessories are mounted in installed locations and...

Страница 123: ...ed to the UPS cabinets and to the tie cabinet or distribution panel o All power cables are properly sized and terminated o A ground conductor is properly installed o Controller Area Network CAN wiring...

Страница 124: ..._____________________ _________________________________________________________________________ _________________________________________________________________________ ______________________________...

Страница 125: ...or 5A maximum Power wiring should be a minimum of 22 AWG and a maximum of 14 AWG The wire should be rated for 1A minimum Use only 75 C copper wire 120 Vac for the RMP II RIM II or SCM II should be pro...

Страница 126: ...erify the UPS system is turned off and all power sources are removed See Chapter 7 UPS Operating Instructionsfor shutdown instructions 2 Unfasten the front door latch and swing the door open see Figur...

Страница 127: ...Bridge Card Interface Connections J3 Terminal Name Description 1 Alarm Programmable UPS alarm Activated by a remote dry contact closure 2 Alarm Return 3 Alarm Relay NC Normally closed contact opens w...

Страница 128: ...ware for later use 4 Remove the interface entry conduit landing plates to drill or punch holes see Figure 39 5 Reinstall the interface entry plates and install the conduit 6 To locate the appropriate...

Страница 129: ...ring without MOBs UPS 1 CAN Bridge Card J3 UPS 2 CAN Bridge Card J3 UPS 3 CAN Bridge Card J3 If Installed UPS 4 CAN Bridge Card J3 If Installed NOTE External CAN connections between UPSs require shiel...

Страница 130: ...10 1 2 3 4 5 7 8 6 9 10 1 2 3 4 5 7 8 6 9 10 UPS 1 Twisted Pair Twisted Pair Twisted Pair Twisted Pair Twisted Pair Twisted Pair UPS 2 UPS 3 If Installed Twisted Pair UPS 4 If Installed TB1 TB1 1 B T...

Страница 131: ...ted pair wire NOTE Use twisted pair wiring between the UPS and MOB AUX contacts NOTE Always m contact operation prior to wiring 2 S P U 1 S P U 2 B T 2 B 2 B T TB2 1 B T 1 B T UPS 3 If Installed UPS 4...

Страница 132: ...ull Chain Common UPS 4 CAN Bridge Card J3 1 Alarm MOB 4 Aux 1 NC MOB Open Alarm UPS 4 CAN Bridge Card J3 2 Alarm Return MOB 4 Aux 1 Com UPS 4 TB2 1 Pull Chain MOB 4 Aux 2 NO Pull Chain MOB 1 Aux 2 Com...

Страница 133: ...e 60 Figure 61 and Table 36 for the RMP II terminal location and wiring information NOTE 120 Vac for the RMP II should be supplied from the critical bus by facility planners or the customer 8 Install...

Страница 134: ...a inverter or bypass If the indicators on the RMP II show the appropriate status then it is operating correctly If the communication link between the UPS and the RMP II is not present the RMP II perfo...

Страница 135: ...on 7 Install wiring between the UPS and RIM II See Figure 56 and Table 32 for the Hot Sync CAN Bridge Card terminal location and wiring information and Figure 60 Figure 61 and Table 36for the RIM II t...

Страница 136: ...l S Su up pe er rv viis so or ry y C Co on nt ta ac ct t M Mo od du ulle e I II I To install SCM II wiring 1 Verify the UPS system is turned off and all power sources are removed See Chapter 7 UPS Ope...

Страница 137: ...and Table 36 for the terminal location and wiring information Figure 63 Supervisory Contact Module II Terminal Location Ground Terminal Terminal TB1 Signal Connections from the UPS Terminal TB3 120 V...

Страница 138: ...n Imminent NOTE Supervisory contacts are rated at 2 0A at 28 Vdc or 120 Vac and 0 15A at 115 Vdc NOTE Supervisory contacts require an external power supply Internal 24 Vdc is not capable of supplying...

Страница 139: ...emote Monitor Panel II Dimensions Flush Mount using 10 Pan Head Screws Mount with vent holes facing up Surface Mount using 10 Pan Head Screws for Hanging Mount with vent holes facing up Dimensions are...

Страница 140: ...lay Interface Module II Dimensions Knockouts Provided on Five Surfaces Surface Mount using 10 Pan Head Screws for Hanging Mount with vent holes facing up Flush Mount using 10 Pan Head Screws Mount wit...

Страница 141: ...rvisory Contact Module II Dimensions Surface Mount using 10 Pan Head Screws for Hanging Mount with vent holes facing up Flush Mount using 10 Pan Head Screws Mount with vent holes facing up Dimensions...

Страница 142: ...122 Eaton Power Xpert 9395P 900 Installation and Operation Manual 164000501 Rev 12 Installing Options and Accessories...

Страница 143: ...r a specified period of time or until the utility power returns For extended power outages the UPS allows you to either transfer to an alternative power system such as a generator or shut down your cr...

Страница 144: ...agement System VMMS mode the UPS operates as a traditional double conversion UPS but selectively shifts the load to fewer UPMs to increase the efficiency of the UPS In Bypass mode the critical load is...

Страница 145: ...y returns to Online mode when the overload condition is cleared and system operation is restored within specified limits If the UPS suffers an internal failure it switches automatically to Bypass mode...

Страница 146: ...is 80 of the UPM full power rating If the limit is exceeded additional UPMs take on the increased load The VMMS redundancy setting sets the number of redundant UPMs that the customer requires Both the...

Страница 147: ...d protection contactor is normally always closed ready to support the static switch unless the bypass input source becomes unavailable Figure 70 Path of Current Through the UPS in Bypass Mode K1 K3 K5...

Страница 148: ...peration the battery continues discharging until a DC voltage level is reached where the inverter output can no longer support the connected loads When this event occurs the UPS issues another set of...

Страница 149: ...Eaton Power Xpert 9395P 900 Installation and Operation Manual 164000501 Rev 12 129 Understanding UPS Operation...

Страница 150: ...mon Rectifier Feed Common Battery Dual Feed Configuration Continuous Static Switch Figure 75 Eaton 9395P 900 900 Eaton 9395P 900 900 Eaton 9395P 900 825 Eaton 9395P 900 750 Eaton 9395P 900 675 Single...

Страница 151: ...Separate Battery IOM Configuration Figure 82 Eaton 9395P 900 900 Eaton 9395P 900 900 Eaton 9395P 900 825 Eaton 9395P 900 750 Eaton 9395P 900 675 Single Reverse Transfer UPS Four UPM Common Rectifier...

Страница 152: ...se Service Connector Battery Converter Inverter Output Contactor K3 Fuse Rectifier Input Contactor K1 Battery Contactor K2 Fuse Fuse Fuse UPM 2 Battery Breaker E4 E5 Battery Converter Inverter Output...

Страница 153: ...ut Contactor K1 Battery Contactor K2 Fuse Fuse Fuse UPM 3 Battery Breaker E4 E5 Battery Breaker E4 E5 Battery Converter Inverter Output Contactor K3 Fuse Rectifier Input Contactor K1 Battery Contactor...

Страница 154: ...Interface Board Battery Aux Remote EPO Building Alarms Alarm Relays Fuse Service Connector Battery Converter Inverter Output Contactor K3 Fuse Rectifier Input Contactor K1 Battery Contactor K2 Fuse Fu...

Страница 155: ...y Converter Inverter Output Contactor K3 Fuse Rectifier Input Contactor K1 Battery Contactor K2 Fuse Fuse Fuse UPM 2 Battery Breaker E4 E5 Battery Converter Inverter Output Contactor K3 Fuse Rectifier...

Страница 156: ...3 or 4 Wire A B C Rotation Interface Board Battery Aux Remote EPO Building Alarms Alarm Relays Fuse Service Connector Battery Converter Inverter Output Contactor K3 Fuse Rectifier Input Contactor K1 B...

Страница 157: ...rface Board Battery Aux Remote EPO Building Alarms Alarm Relays Fuse Service Connector Battery Converter Inverter Output Contactor K3 Fuse Rectifier Input Contactor K1 Battery Contactor K2 Fuse Fuse F...

Страница 158: ...ilding Alarms Alarm Relays Fuse Service Connector Battery Converter Inverter Output Contactor K3 Fuse Rectifier Input Contactor K1 Battery Contactor K2 Fuse Fuse Fuse UPM 1 Battery Breaker E4 E5 Batte...

Страница 159: ...ery Converter Inverter Output Contactor K3 Fuse Rectifier Input Contactor K1 Battery Contactor K2 Fuse Fuse Fuse UPM 2 Battery Breaker E4 E5 Battery Converter Inverter Output Contactor K3 Fuse Rectifi...

Страница 160: ...ice Connector Battery Converter Inverter Output Contactor K3 Fuse Rectifier Input Contactor K1 Battery Contactor K2 Fuse Fuse Fuse UPM 2 Battery Breaker BATTERY SYSTEM E4 E5 Battery Converter Inverter...

Страница 161: ...e Rectifier Input Contactor K1 Battery Contactor K2 Fuse Fuse Fuse UPM 2 Battery Breaker E4 E5 Battery Converter Inverter Output Contactor K3 Fuse Rectifier Input Contactor K1 Battery Contactor K2 Fus...

Страница 162: ...tifier Input Contactor K1 Battery Contactor K2 Fuse Fuse Fuse UPM 2 Battery Breaker E4 E5 Battery Converter Inverter Output Contactor K3 Fuse Rectifier Input Contactor K1 Battery Contactor K2 Fuse Fus...

Страница 163: ...y Breaker E4 E5 Battery Converter Inverter Output Contactor K3 Fuse Rectifier Input Contactor K1 Battery Contactor K2 Fuse Fuse Fuse UPM 1 Bypass Breaker CB4 Battery Converter Inverter Output Contacto...

Страница 164: ...s If a bypass input breaker BIB is installed in the maintenance bypass and a single feed UPS is being installed a single feed to the maintenance bypass is acceptable for supplying both the UPS and the...

Страница 165: ...2 0 if both UPMs in a system are required to support the load A parallel capacity system can also be redundant 2 1 as long as there is always one or more UPMs online than required to support the load...

Страница 166: ...or distribution panel for parallel systems up to four modules The applied load is shared equally among the available UPMs in the system Figure 85 shows the path of electrical power through the paralle...

Страница 167: ...the load If the load can be supported the system does not switch to bypass Figure 86 shows the path of electrical power through the parallel system when operating in Bypass mode In a distributed bypa...

Страница 168: ...to bypass 6 6 4 4 4 4 B Ba at tt te er ry y M Mo od de e D Diis st tr riib bu ut te ed d B By yp pa as ss s The UPSs transfer to Battery mode automatically if a utility power outage occurs or if the u...

Страница 169: ...the battery discharge the input power becomes available again the rectifier begins to supply DC current to the inverter At this point the UPS returns to Online mode If at any time during the battery d...

Страница 170: ...ype Figure 88 Eaton 9395P 900 900 Eaton 9395P 900 900 Eaton 9395P 900 825 Eaton 9395P 900 750 Eaton 9395P 900 675 Eaton 9395P 900 600 Eaton 9395P 900 600 Eaton 9395P 900 550 Eaton 9395P 900 500 Eaton...

Страница 171: ...Battery Breaker Battery Converter Inverter K3 Fuse Rectifier K1 K2 Fuse Fuse Fuse E6 E7 E8 E12 K5 Static Switch Fuse E1 E2 E3 CB1 optional UPS 2 A B E4 E5 BATTERY SYSTEM Not supplied with the UPS C E9...

Страница 172: ...Switch Fuse E1 E2 E3 CB1 optional UPS 2 A B E4 E5 BATTERY SYSTEM Not supplied with the UPS C E9 E10 E11 E12 D Battery Breaker Battery Converter Inverter K3 Fuse Rectifier K1 K2 Fuse Fuse Fuse E6 E7 E...

Страница 173: ...E12 D Battery Breaker Battery Converter Inverter K3 Fuse Rectifier K1 K2 Fuse Fuse Fuse E6 E7 E8 E12 K5 Static Switch Fuse E1 E2 E3 CB1 optional UPS 3 A B E4 E5 BATTERY SYSTEM Not supplied with the UP...

Страница 174: ...154 Eaton Power Xpert 9395P 900 Installation and Operation Manual 164000501 Rev 12 Understanding UPS Operation...

Страница 175: ...s section of the manual and have thorough knowledge of UPS operation before attempting to operate any of the controls NOTE 3 The UPS displays two minutes of battery runtime at the initial startup Afte...

Страница 176: ...d to control the AC input to the UPS rectifier 7 7 2 2 C Co ollo or r T To ou uc ch hs sc cr re ee en n C Co on nt tr ro oll P Pa an ne ell This section describes how the various screens are used to c...

Страница 177: ...93 UPS Color Touchscreen Control Panel Typical 1 2 Symbols enlarged to show detail The color touchscreen control panel consists of A color liquid crystal touch screen display 1 A horizontal row of LED...

Страница 178: ...tor is not illuminated when the system is in Bypass mode Red Lit Steady The UPS has an active alarm and requires immediate attention The screen shows the highest priority active alarms All alarms are...

Страница 179: ...ystem model and time allows the operator select a different language from an imbedded list The top line of the display blinks while scrolling when the system needs attention Some notices and alarms ma...

Страница 180: ...uest Screen A B C ENTER BUTTON Number indicates security level 0 4 Table 40 Security Levels and Functions Level Name Passcode Description 0 USER NONE USER 1 CONTROL 1111 USER CONTROL 2 CONFIGURATION 0...

Страница 181: ...ontrol screens POWER MAPS Allows operator to observe system power flow LOGS Allows access to system information logs STATISTICS Allows access to see system specific operation values SETTINGS Allows ac...

Страница 182: ...S Sc cr re ee en n O On nlliin ne e M Mo od de e Figure 97 shows the Main Menu and Power Maps screen The Power Maps screen displays immediately after entering the access code The Power Maps screen sh...

Страница 183: ...gure 98 Output kVA Screen from Home Screen Touching the AVERAGE EFFICIENCY button displays the system efficiency screen shown in Figure 99 Figure 99 Average Efficiency Screen from Home Screen Touching...

Страница 184: ...igure 101 shows the Bypass screen The Bypass screen displays only when the system is in Bypass mode The Bypass screen shows a real time graphical representation of the operating status Touching any of...

Страница 185: ...rs Summary screen This screen allows selection of the various metering readout functions of Input Output and overall System status The three left items in the OVERVIEW section of the screen are not ac...

Страница 186: ...pass and Output screens allow selection of the source UPS Metering mode Line to Line Line to Neutral and UPS details See Figure 104 Figure 104 Meters Selection Buttons Typical Line to Neutral Opens se...

Страница 187: ...Eaton Power Xpert 9395P 900 Installation and Operation Manual 164000501 Rev 12 167 Figure 105 Input Meters Screen UPS Operating Instructions...

Страница 188: ...6 allows the operator to choose the individual source for system readings Figure 106 Select Source Screen Input Meters Detail Screen The Show Details button Figure 107 shows the Input Meters detail sc...

Страница 189: ...he Metering Method Option screen The operator can select line to line or line to neutral monitoring values See Figure 108 Figure 108 Online Mode Metering Method Option Screen Bypass Meters Screen The...

Страница 190: ...reen The Show Details button on the Bypass Mode Metering Method Option Screen allows the operator to select the metering method for either line to line or line to neutral monitoring values See Figure...

Страница 191: ...he Output Meters Screen shown in Figure 111 displays values pertaining to the system output Figure 111 Output Meters Screen 7 7 3 3 9 9 B Ba at tt te er ry y M Me et te er rs s S Sc cr re ee en n Figu...

Страница 192: ...taking place The horn cycles at a half second rate System Event Indicators The status indicators on the UPS control panel work with the event horn to let the operator know when the UPS is operating in...

Страница 193: ...Manual 164000501 Rev 12 173 Figure 114 User Log Screen 1 2 Selecting an event opens the Event Detail screen shown in Figure 115 This screen details the specifics of the event for the user to see Figur...

Страница 194: ...12 7 7 3 3 1 12 2 B Ba at tt te er ry y L Lo og g Figure 116 shows the Battery Log access screen Figure 116 Battery Log Screen Figure 117 shows the Battery Log Detail screen Figure 117 Battery Log De...

Страница 195: ...OLS pushbutton on the main menu bar to display the System Status screen Online operation transfer to bypass UPM start up and shutdown and LOAD OFF commands are controlled through this screen In additi...

Страница 196: ...Go to Load Off System Controls Home Module Controls Controls EAA UPS STATUS STATUS BYPASS Available Online Online POWER XPERT 9395P Figure 121 shows the Module Controls screen This screen allows cont...

Страница 197: ...evious screen Figure 121 the user can observe full details of an individual module It also allows the user to move through various modules and modes while within this screen The color of the UPM butto...

Страница 198: ...stalled firmware version etc Touching the CLEAN SCREEN button disables the screen for 30 seconds to allow the user to safely clean the screen without affecting operation Figure 123 Settings Screen 7 7...

Страница 199: ...wn in Figure 125 allows the operator to activate the various energy saving and power efficiency modes of the system The various Energy Advantage Architecture operations are described in the UPS Instal...

Страница 200: ...allation and Operation Manual 164000501 Rev 12 Figure 126 Disable ESS Screen The screen shown in Figure 127 asks the operator if they want to start the High Alert mode timer Figure 127 High Alert Time...

Страница 201: ...ure 128 allows the operator to query the system for various operational statistics such as shown in Figure 129 Figure 128 Statistics Basic Screen Figure 129 Statistics Data Detail Screen 7 7 3 3 1 18...

Страница 202: ...Mo od du ulle e M Ma ap p S Sc cr re ee en n The screen shown in Figure 131 allows the operator to control the individual UPMs Figure 131 UPS Module Map Screen 7 7 3 3 2 20 0 S Sy ys st te em m O Ov...

Страница 203: ...security level sign in If a sign in request screen appears see Figure 95 for details NOTE A Field Installed UPM FI UPM is always designated as UPM 4 7 7 4 4 1 1 S St ta ar rt tiin ng g t th he e U UP...

Страница 204: ...the screen The UPM status indicates Active Charger ON on the UPM Module Control Detail screen see Figure 121 To activate or enable disable any of the UPS operational modes follow the online screen pro...

Страница 205: ...r rg gy y S Sa av ve er r S Sy ys st te em m H Hiig gh h A Alle er rt t M Mo od de e NOTE 1 The High Alert mode commands are displayed only if enabled at the factory or by an Eaton Customer Service En...

Страница 206: ...g ge em me en nt t S Sy ys st te em m M Mo od de e To disable Variable Module Management System mode NOTE 1 The Variable Module Management System mode commands are displayed only if enabled at the fac...

Страница 207: ...hock If the inverter output of the UPS is not available and the critical load needs to be energized In Bypass mode the critical load is not protected from commercial power interruptions and abnormalit...

Страница 208: ...ive indicating logic power 8 Make sure you are logged in for user access see Figure 95 9 Verify no alarms are active 10 Press the Controls button on the Home screen see Figure 96 The System Status scr...

Страница 209: ...dicating logic power 9 Make sure you are logged in for user access see Figure 95 10 Press the Controls button on the Home screen see Figure 96 The System Status screen is displayed see Figure 119 11 O...

Страница 210: ...r f fr ro om m B By yp pa as ss s t to o O On nlliin ne e M Mo od de e To transfer the critical load to Online mode 1 If not already closed close the battery breaker 2 Make sure you are logged in for...

Страница 211: ...8 Verify the following UPM x IS SHUTTING DOWN message appears The UPM POWER STATUS shows Shutdown on the Module Control Detail screen see Figure 122 The UPM status bar shows in a black color Shutdown...

Страница 212: ...al load is lost when the Load Off is selected in the following step You should use this feature only when you want to de energize the critical load 3 Press the Load Off button The Shut Down confirmati...

Страница 213: ...ass backfeed contactors open the battery breaker or disconnect is tripped and the power module is turned off immediately without asking for verification Do not attempt to restart the system after the...

Страница 214: ...ib bu ut te ed d B By yp pa as ss s S Sy ys st te em m iin n O On nlliin ne e M Mo od de e To start the distributed bypass system If required to close a circuit breaker inside a UPS use appropriate pe...

Страница 215: ...ve er r S Sy ys st te em m M Mo od de e To enable Energy Saver System mode NOTE 1 The Energy Saver System mode commands are displayed only if enabled at the factory or by an Eaton Customer Service En...

Страница 216: ...AA screen is displayed see Figure 125 4 On the EAA screen select Start High Alert Timer the Start high alert timer confirmation screen appears see Figure 127 5 Select Yes on the confirmation screen Th...

Страница 217: ...indicator is illuminated The UPS status indicates Online 7 7 5 5 7 7 S St ta ar rt t V Va ar riia ab blle e M Mo od du ulle e M Ma an na ag ge em me en nt t S Sy ys st te em m H Hiig gh h A Alle er rt...

Страница 218: ...icating logic power 11 Make sure you are logged in for user access see Figure 95 12 On any UPS press the Controls button on the Home screen see Figure 96 The System Status screen is displayed see Figu...

Страница 219: ...dule Controls Detail screen for the UPM appears see Figure 122 14 Press the Start UPM button in the Power Status section 15 Select Yes on the confirmation screen Verify the following A message that th...

Страница 220: ...ation screen Verify the following message is displayed UPM 1 IS STARTING The UPM 1 rectifier and inverter turn on UPM Power Status line shows idle The UPM status bar shows in a gray color Idle 16 Repe...

Страница 221: ...as ss s M Mo od de e a an nd d S Sh hu ut t D Do ow wn n U UP PM Ms s To transfer the critical load to Bypass mode and shut down all UPMs 1 Transfer the critical load to bypass by performing the proc...

Страница 222: ...graph 5 1 Installing an Optional Hot Sync CAN Bridge Card To shut down a single UPS 1 Open the MOB for the UPS being shut down 2 Make sure you are logged in for user access see Figure 95 3 On the UPS...

Страница 223: ...ser access see Figure 95 3 On the UPS to shut down press the Controls button on the Home screen see Figure 96 The System Status screen is displayed see Figure 119 4 On the System Status screen select...

Страница 224: ...e equipment Injury to personnel may occur from electrical shock 1 Close the MOB for the UPS being restarted 2 Close UPS input and bypass feeder circuit breakers for the UPS being restarted 3 Unfasten...

Страница 225: ...n paragraph 7 4 17 Using the UPS Load Off Button UPS and Critical Load Shutdown The input output battery and bypass backfeed contactors open and the power module is turned off Power is present inside...

Страница 226: ...lowing step You should use this feature only when you want to de energize the critical load 3 Press the Load Off button The Shut Down confirmation screen is displayed providing a choice to proceed or...

Страница 227: ...the REPO pushbutton switch 1 Firmly push the red pushbutton until it locks into place The switch latches into the activated state see Figure 133 The input output and bypass backfeed contactors open th...

Страница 228: ...n Power Xpert 9395P 900 Installation and Operation Manual 164000501 Rev 12 Figure 134 REPO Operation Activated Pushbutton locked into place Deactivated Unlock pushbutton to release UPS Operating Instr...

Страница 229: ...network drop Modbus Card provides direct integration of UPS information meters and status to a Building Management System BMS using the Modbus RTU protocol Relay Interface Card AS 400 has isolated dry...

Страница 230: ...eway UPS card PredictPulse uses standard Eaton connectivity hardware requiring no special software devices only need to be connected to a network Ability to give an unlimited number of coworkers acces...

Страница 231: ...ironments The software s mass configuration capabilities make installation and maintenance easy which minimizes the effort required and benefits the bottom line Eaton s cost effective Intelligent Powe...

Страница 232: ...RMP II can be installed to monitor the operation of the UPS system from virtually any location within the facility up to 150m 500 ft from the UPS The RMP II contains backlit status indicators and a lo...

Страница 233: ...supplying the critical load Usually this means that the UPS is not energized The load is not protected in Bypass mode and a horn sounds after 30 seconds UPS ALARM The UPS system is issuing an alarm Co...

Страница 234: ...connectors labeled J1 through J4 Figure 137 Relay Interface Module II The RIM II can provide the status and alarm signals shown in Table 43 Table 43 Customer Interface Connectors Status J1 through J4...

Страница 235: ...flush mounted or surface mounted on a desktop or secured to a wall Figure 138 shows the SCM II Figure 138 Supervisory Contact Module II The SCM II provides signals for the indications shown in Table...

Страница 236: ...216 Eaton Power Xpert 9395P 900 Installation and Operation Manual 164000501 Rev 12 Communication...

Страница 237: ...e any assumptions about the electrical state of any cabinet in the UPS system AVERTISSEMENT L installation et l entretien ne doivent tre effectu s que par du personnel qualifi PR SENCE DE TENSIONS MOR...

Страница 238: ...nsiderations and Chapter 10 Product Specifications 4 Ensure the UPS is in Online mode Online status indicator is illuminated If an alarm lamp is illuminated or the Online status indicator is not illum...

Страница 239: ...am filters over the screw heads on the cabinet mounted studs and remove the filters from the cabinet e Push the washed or new foam filters over the screw heads on the cabinet mounted studs until seate...

Страница 240: ...cement filter To remove the filter a Remove one top screw and two bottom screws securing the FI UPM front panel refer to the Eaton Power Xpert 9395P UPS Field Installed UPM Mechanical Installation Man...

Страница 241: ...ents wiring and connections exhibit evidence of overheating Particular attention should be given to bolted connections Maintenance procedures should specify that the bolted connections be retorqued to...

Страница 242: ...r fire Observe proper precautions ATTENTION Une batterie peut pr senter un risque de choc lectrique de brulure ou d incendie Suivre les pr cautions qui s imposent Pour le remplacement utiliser le m me...

Страница 243: ...50 60 Hz Eaton 9395P 900 550 two or three UPM 550 kVA 500 kW 50 60 Hz Eaton 9395P 900 500 two or three UPM 500 kVA 500 kW 50 60 Hz Eaton 9395P 900 450 two or three UPM 450 kVA 450 kW 50 60 Hz 1 10 0 2...

Страница 244: ...15 or Figure 16 for 415V three UPM models See Figure 17 or Figure 18 for 400V three UPM models See Figure 19 or Figure 20 for 380V three UPM models Output Voltage Balance 2 5 for 100 maximum load imb...

Страница 245: ...0 m 3000 ft at 40 C without derating Storage Temperature 25 to 60 C excluding batteries prolonged storage above 40 C causes rapid battery self discharge Relative Humidity Operating and Storage 5 to 95...

Страница 246: ...16400050112 164000501 12...

Отзывы: