4 Commissioning
4.2 Parameter Sets
30
DX-NET-SWD...
08/14 MN04012009Z-EN
www.eaton.com
4.2 Parameter Sets
The following parameter settings listed below are required for operation with
SmartWire-DT.
•
For DA1 variable frequency drives: P1-12
•
For DC1 variable frequency drives and DE1 variable speed starters: P12
Other parameters do not have to be set.
Valule P-12
description
0
Control signal terminals
…
…
9
SmartWire-DT actuation with setpoint value via SmartWire-DT
10
SmartWire-DT actuation with local setpoint value
11
Local actuation with setpoint value via SmartWire-DT
12
Actuation via SmartWire-DT - depending on the settings with the loss in
communication, automatic change to the local actuation
13
Actuation and setpoint value via SmartWire-DT with enable via terminal
→
Further information about parameter P-12