Castell key lock accessory 

  

  

EATON 

www.eaton.com

Instruction Leaflet

 IL01301050E

Effective January 2019

Figure 5.  Soeps 4 and 5.

Soep 7: 

Identify the mounting location for the key lock assembly. 

Two threaded mounting holes are provided in the mounting tab to 

accommodate the two mounting screws (E) and two fiber retaining 

washers (F), which serve as spring washers when tightened. Make 

sure the key (B) is removed before mounting the assembly. Position 

the key lock assembly and tighten the two mounting screws. Make 

sure the mounting bracket’s sheet metal tab is positioned under the 

plastic of the pushbutton plate. Use a small flat screwdriver to get the 

metal tab under the plastic.

Figure 6. 

Side 

plate

Sheet metal 

tab

Pushbutton 

plate plastic

Mounting 

holes

Mounting 

screws

Soep 7. NF frame.

Figure 6a. Soep 7. RF frame.

Bracket mounting 

screws (E)

Mounting screws (G)

Lever assembly (J)

Grooves 

seated against 

mounting plate

(K)

Mounting holes

Mounting 
screws (E)

Side plate

Pushbutton 
face plate

Sheet metal 
tab

Soep 8 (NF frame Nnly):

 If this is a fixed circuit breaker, skip this step 

and proceed to Step 9. If this is a drawout circuit breaker, put back 

and re-tighten the three captive secondary mounting bracket screws 

previously removed in Step 3 of this section. Start with the center 

screw.

Noe:

N

If any connectors were accidentally loosened, ensure they are pushed 

back into place.

Soep 9:

 With the key lock assembly now installed, place the front 

cover previously removed in Step 2 on an appropriate work surface 

front side up. Put a rigid support under the round knockout window. 

Using a small punch and a hammer, carefully punch out the round 

window in the upper center portion of the front cover. If necessary, 

use a small file to remove any burrs from the window. Make certain 

that all pieces and/or particles are cleaned up and removed before 

proceeding.

Soep 10:

 Replace the front cover, and secure it in place with the 

mounting screws previously removed in Step 1. Remove the adhesive 

backing from the external protective ring (A), and press it onto the 

front cover over the key lock.

Installed 

lock 

assembly

Front 

cover

Drilled 

hole

External 

protective 

ring (A)

Figure 7. Soep 10.

Soep 11:

 Perform a functional test:

1.  With the key in the cylinder, press the red “Push To Open” button 

down and rotate the key counterclockwise. The key must be 

pushed in to turn. Remove the key. Charge the breaker. 

2.  Push the green “Push to Close” button. The breaker should not 

close.

3.  Insert the key and rotate 90° clockwise. Press the green button to 

close. The breaker should close.