Eaton PMINT Скачать руководство пользователя страница 5

5

04/10 AWB1230-1621

Effective April 2010

PMINT—PROFIBUS DP translator

module—installation and use

 

EATON CORPORATION

 www.moeller.net/en/support 

Remote enable switch (SW1-1)

The PMINT provides a REMOTE ENABLE switch (see 

Figure 2

that will enable/disable access by a PROFIBUS master to control  

the opening/closing of the circuit breaker by communications . Refer 

to 

Table 5

 .

Table 5.  Remote Enable Switch

SW1-1

SW1-2

SW1-3

Remote disable

Open

X

X

Remote enable

Close

X

X

Reserved switches (SW1-2 and SW1-3)

Switches SW1-2 and SW1-3 on the PMINT are reserved for  

future use .

Section 6: PROFIBUS DP GSD file

The current GSD file for the PMINT is listed in Appendix A .  

PROFIBUS DP-V0 cyclic data transfers are supported .

Section 7: PROFIBUS DP-V0 profiles

The PMINT supports the PROFIBUS DP profile for low voltage 

switchgear devices (LVSG): Circuit Breaker Device Classification . 

This classification provides cyclic data exchange structures for 

one command (outputs from the PROFIBUS master to the PMINT 

slave device) format (Format 0) and four monitoring (inputs from 

the PMINT slave device to the PROFIBUS master) formats (Format 

0–Format 3) . The PMINT also supports an added monitoring format 

(Format 4), similar to Format 3, except the active energy value is 

provided with a higher resolution . 

Cyclic data exchange command structure format

Command structure Format 0 for cyclic data exchange from the 

PROFIBUS master supported by the PMINT is described in 

Table 6

 .

The bits are defined as bit 0 is bit 0 of byte 0; bit 8 is bit 0 of byte 1 .

Cyclic data exchange monitoring structure formats

Monitoring structure Formats 0–4 for cyclic data exchange returned 

from the PMINT to the PROFIBUS master are described in 

Table 7

 

through 

Table 11

, respectively .

The state information bytes are required in all monitoring formats . 

The bits are defined as bit 0 is bit 0 of state byte 0; bit 8 is bit 0 

of state byte 1 . The definitions are deciphered from the Primary/

Secondary/Cause-Of-Status information reported from the Trip Unit 

(see 

Table 13

Table 14

, and 

Table 15

, respectively) .

The multi-byte measurement values of Formats 1–4 are transmitted 

most significant byte first, as required by the PROFIBUS protocol .

Table 6.  Cyclic Data Exchange Command Format 0

Byte

Bit(s) Description

Implementation

0

1–0

Circuit breaker:

00 = no change

01 = switch OFF

10 = switch ON

11 = no change

Open breaker (if remote enabled, see Section 5)

Close breaker (if remote enabled, see Section 5)

2

Clear last trip

“Reset Trip” issued to trip unit

3

Output 0

Not implemented

4

Output 1

Not implemented

5

Output 2

Not implemented

6

Output 3

Not implemented

7

Output 4

Not implemented

1

9–8

Test mode:

00 = no test

01 = w/o release

10 = with release

11 = with warning

No trip phase current self-test at 3.0 per unit 

issued to Digitrip 1150 trip unit only

Not implemented

Not implemented

10

Delete history 

memory

Not implemented

11

Reset min./max. 

memory

“Reset all min./max. values” issued to trip unit

12

Reset temperature 

min./max. memory

Not implemented

13

Output 5

Not implemented

14

Reset maintenance 

information

“Reset trip unit health buffer” issued to trip unit

15

Clock synchronization

Not implemented

Содержание PMINT

Страница 1: ...ircuit breaker position switch connector TB2 4 PROFIBUS DP RS 485 connector 4 Section 5 Switches and indicator LEDs 4 PROFIBUS SYSFAULT LED red 4 PROFIBUS BUSFAULT LED red 4 INCOM connection Tx LED gr...

Страница 2: ...le 4 PROFIBUS DP LED States 4 Table 5 Remote Enable Switch 5 Table 6 CFG Data Formats 5 Table 7 Cyclic Data Exchange Command Format 0 5 Table 8 Cyclic Data Exchange Monitoring Format 0 6 Table 9 Cycli...

Страница 3: ...cover all of the details or variations of the equipment for its storage delivery installation checkout safe operation or maintenance When mounting the PMINT verify that a C Shape 32 mm or Standard 35...

Страница 4: ...he RxD TxD data lines is critically important Refer to Table 3 Table 3 PROFIBUS DP RS 485 Connector Pin Outs Pin No Input Output Signal 1 Shield a 2 M24 ground for 24V output a 3 RxD TxD P B dataline...

Страница 5: ...ed as bit 0 is bit 0 of byte 0 bit 8 is bit 0 of byte 1 Cyclic data exchange monitoring structure formats Monitoring structure Formats 0 4 for cyclic data exchange returned from the PMINT to the PROFI...

Страница 6: ...unit not yet established 15 Load rejection 1 Primary status alarm cause 26 Table 8 Cyclic Data Exchange Monitoring Format 1 Byte s Data Type Description Resolution 0 Unsigned8 State 0 byte 0 of monito...

Страница 7: ...r when the PMINT returns a high priority cyclic data exchange Table 12 DP V0 Unit Diagnostics Definitions Byte Bit s Value Description 7 08H Header device related diagnostics length 8 bytes 8 7 0 81H...

Страница 8: ..._supp 1 187 5_supp 1 500_supp 1 1 5M_supp 1 3M_supp 1 6M_supp 1 12M_supp 1 MaxTsdr_9 6 60 Bit Time MaxTsdr_19 2 60 Bit Time MaxTsdr_31 25 60 Bit Time MaxTsdr_45 45 60 Bit Time MaxTsdr_93 75 60 Bit Tim...

Страница 9: ...it_Diag_Bit 0034 Data Object 10 invalid Unit_Diag_Bit 0035 Data Object 11 invalid Unit_Diag_Bit 0036 Data Object 12 invalid Unit_Diag_Bit 0037 Data Object 13 invalid Unit_Diag_Bit 0038 Data Object 14...

Страница 10: ...isted in Table 14 The definition of the cause of status word pertaining to the primary status is listed in Table 15 Table 13 Primary Status Code Definitions Code Definition Code Definition 0 Unknown 1...

Страница 11: ...5 Making current release 36 Operation time exceeded 76 Fixed instantaneous phase overcurrent 3 37 Coil supervision 77 Set points error 38 Programmable logic 78 Overtemperature 39 Diagnostic warning 1...

Страница 12: ...installation and use Eaton Industries GmbH Electrical Sector 2010 by Eaton Industries GmbH nderungen vorbehalten Subject to alterations 04 10 AWB1230 1621 Z8896 Moon Doku Heng Printed in USA 04 10 04...

Страница 13: ...ung TB1 4 INCOM Schalterposition Steckverbinder Positionsschalter TB2 4 PROFIBUS DP RS 485 Stecker 4 Abschnitt 5 Schalter und Anzeigen 4 PROFIBUS SYSFAULT LED rot 4 PROFIBUS BUSFAULT LED rot 4 Leuchte...

Страница 14: ...abelle 4 Leuchte PROFIBUS DP 4 Tabelle 5 Schalter Fernaktivierung 5 Tabelle 6 Formate der Konfigurationsdaten 5 Tabelle 7 Befehl Zyklischer Datenaustausch Format 0 5 Tabelle 8 Kontrolle Zyklischer Dat...

Страница 15: ...altung auftreten k nnen oder alle Details und Variationen der beschriebenen Betriebsmittel ab Das PMINT Modul kann auf einer C Schiene 32 mm oder einer Standard DIN Hutschiene 35 7 5 mm montiert werde...

Страница 16: ...Klemme Nr Ein Ausgangssignal 1 INCOM Datennetz 2 INCOM Datennetz 3 INCOM Schirm 4 Positionsschalter 1 Leistungsschalter 5 Positionsschalter 2 Leistungsschalter 6 Positionsschalter GND Masse Leistungss...

Страница 17: ...giewert wird aber mit einer h heren Aufl sung geliefert Befehlsstruktur Format 0 f r den zyklischen Datenaustausch Die von dem PMINT Modul unterst tzte Befehlsstruktur Format 0 f r den zyklischen Date...

Страница 18: ...tion zu Ausl seeinheit noch nicht aufgebaut 15 Lastabwurf 1 Zustand prim r Alarm Ursache 26 Tabelle 8 Kontrolle Zyklischer Datenaustausch Format 1 Byte Datentyp Beschreibung Aufl sung 0 vorzeichenlos8...

Страница 19: ...m PROFIBUS Master vermittelt wenn das PMINT Modul einen zyklischen Datenaustausch mit hoher Priorit t zur ck meldet Tabelle 12 Diagnosebits der DP V0 Einheit Byte Bit s Wert Beschreibung 7 08H Header...

Страница 20: ...upp 1 187 5_supp 1 500_supp 1 1 5M_supp 1 3M_supp 1 6M_supp 1 12M_supp 1 MaxTsdr_9 6 60 Bit Time MaxTsdr_19 2 60 Bit Time MaxTsdr_31 25 60 Bit Time MaxTsdr_45 45 60 Bit Time MaxTsdr_93 75 60 Bit Time...

Страница 21: ...Unit_Diag_Bit 0034 Data Object 10 invalid Unit_Diag_Bit 0035 Data Object 11 invalid Unit_Diag_Bit 0036 Data Object 12 invalid Unit_Diag_Bit 0037 Data Object 13 invalid Unit_Diag_Bit 0038 Data Object 1...

Страница 22: ...ng des Worts das die Ursache f r den prim ren Status beschreibt ist in Tabelle 15 aufgef hrt Tabelle 13 Statuscodes prim rseitig Code Definition Code Definition 0 Unbekannt 19 Alarm Phase A 1 ffnen 20...

Страница 23: ...schaltstromausl ser 36 Betriebszeit berschritten 76 fest unverz gert bei berstrom in Phase 3 37 berwachung Spule 77 Sollwertfehler 38 Programmierbare Logik 78 bertemperatur 39 Diagnosewarnung 1 79 Zub...

Страница 24: ...lation und Verwendung Eaton Industries GmbH Electrical Sector 2010 by Eaton Industries GmbH nderungen vorbehalten Subject to alterations 04 10 AWB1230 1621 Z8896 Moon Doku Heng Printed in USA 04 10 04...

Отзывы: