Effective April 2010

2A11998H01

04/10 AWB1230-1621

PMINT—PROFIBUS DP translator

module—installation and use

Contents

Description 

Page

List of figures   .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 2
List of tables  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 2
Section 1: General description   .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 3
Section 2: Features  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 3
Section 3: Installation   .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 3

INCOM connection   .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 3
PROFIBUS DP RS-485 network  .  .  .  .  .  .  .  .  .  .  .  .  . 3

Section 4: PMINT connections  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 4

Power connector (TB1)   .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 4
INCOM/circuit breaker position  

switch connector (TB2)  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 4
PROFIBUS DP RS-485 connector  .  .  .  .  .  .  .  .  .  .  . 4

Section 5: Switches and indicator LEDs  .  .  .  .  .  .  .  . 4

PROFIBUS SYSFAULT LED (red)  .  .  .  .  .  .  .  .  .  .  .  . 4
PROFIBUS BUSFAULT LED (red)  .  .  .  .  .  .  .  .  .  .  .  . 4
INCOM connection Tx LED (green)  .  .  .  .  .  .  .  .  .  . 4
Status LED (green)  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 4
Remote enable switch (SW1-1)  .  .  .  .  .  .  .  .  .  .  .  .  . 5

Section 6: PROFIBUS DP GSD file  .  .  .  .  .  .  .  .  .  .  .  . 5
Section 7: PROFIBUS DP-V0 profiles  .  .  .  .  .  .  .  .  .  . 5

Cyclic data exchange command  

structure format  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 5
Cyclic data exchange monitoring  

structure formats  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 5

Section 8: PROFIBUS DP-V0 diagnostics  .  .  .  .  .  .  . 7
Appendix A   .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 8

PROFIBUS DP-V0 GSD Profile Document  .  .  .  .  . 8

Appendix B   .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 10

Primary/Secondary/Cause   .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . 10

Содержание PMINT

Страница 1: ...ircuit breaker position switch connector TB2 4 PROFIBUS DP RS 485 connector 4 Section 5 Switches and indicator LEDs 4 PROFIBUS SYSFAULT LED red 4 PROFIBUS BUSFAULT LED red 4 INCOM connection Tx LED gr...

Страница 2: ...le 4 PROFIBUS DP LED States 4 Table 5 Remote Enable Switch 5 Table 6 CFG Data Formats 5 Table 7 Cyclic Data Exchange Command Format 0 5 Table 8 Cyclic Data Exchange Monitoring Format 0 6 Table 9 Cycli...

Страница 3: ...cover all of the details or variations of the equipment for its storage delivery installation checkout safe operation or maintenance When mounting the PMINT verify that a C Shape 32 mm or Standard 35...

Страница 4: ...he RxD TxD data lines is critically important Refer to Table 3 Table 3 PROFIBUS DP RS 485 Connector Pin Outs Pin No Input Output Signal 1 Shield a 2 M24 ground for 24V output a 3 RxD TxD P B dataline...

Страница 5: ...ed as bit 0 is bit 0 of byte 0 bit 8 is bit 0 of byte 1 Cyclic data exchange monitoring structure formats Monitoring structure Formats 0 4 for cyclic data exchange returned from the PMINT to the PROFI...

Страница 6: ...unit not yet established 15 Load rejection 1 Primary status alarm cause 26 Table 8 Cyclic Data Exchange Monitoring Format 1 Byte s Data Type Description Resolution 0 Unsigned8 State 0 byte 0 of monito...

Страница 7: ...r when the PMINT returns a high priority cyclic data exchange Table 12 DP V0 Unit Diagnostics Definitions Byte Bit s Value Description 7 08H Header device related diagnostics length 8 bytes 8 7 0 81H...

Страница 8: ..._supp 1 187 5_supp 1 500_supp 1 1 5M_supp 1 3M_supp 1 6M_supp 1 12M_supp 1 MaxTsdr_9 6 60 Bit Time MaxTsdr_19 2 60 Bit Time MaxTsdr_31 25 60 Bit Time MaxTsdr_45 45 60 Bit Time MaxTsdr_93 75 60 Bit Tim...

Страница 9: ...it_Diag_Bit 0034 Data Object 10 invalid Unit_Diag_Bit 0035 Data Object 11 invalid Unit_Diag_Bit 0036 Data Object 12 invalid Unit_Diag_Bit 0037 Data Object 13 invalid Unit_Diag_Bit 0038 Data Object 14...

Страница 10: ...isted in Table 14 The definition of the cause of status word pertaining to the primary status is listed in Table 15 Table 13 Primary Status Code Definitions Code Definition Code Definition 0 Unknown 1...

Страница 11: ...5 Making current release 36 Operation time exceeded 76 Fixed instantaneous phase overcurrent 3 37 Coil supervision 77 Set points error 38 Programmable logic 78 Overtemperature 39 Diagnostic warning 1...

Страница 12: ...installation and use Eaton Industries GmbH Electrical Sector 2010 by Eaton Industries GmbH nderungen vorbehalten Subject to alterations 04 10 AWB1230 1621 Z8896 Moon Doku Heng Printed in USA 04 10 04...

Страница 13: ...ung TB1 4 INCOM Schalterposition Steckverbinder Positionsschalter TB2 4 PROFIBUS DP RS 485 Stecker 4 Abschnitt 5 Schalter und Anzeigen 4 PROFIBUS SYSFAULT LED rot 4 PROFIBUS BUSFAULT LED rot 4 Leuchte...

Страница 14: ...abelle 4 Leuchte PROFIBUS DP 4 Tabelle 5 Schalter Fernaktivierung 5 Tabelle 6 Formate der Konfigurationsdaten 5 Tabelle 7 Befehl Zyklischer Datenaustausch Format 0 5 Tabelle 8 Kontrolle Zyklischer Dat...

Страница 15: ...altung auftreten k nnen oder alle Details und Variationen der beschriebenen Betriebsmittel ab Das PMINT Modul kann auf einer C Schiene 32 mm oder einer Standard DIN Hutschiene 35 7 5 mm montiert werde...

Страница 16: ...Klemme Nr Ein Ausgangssignal 1 INCOM Datennetz 2 INCOM Datennetz 3 INCOM Schirm 4 Positionsschalter 1 Leistungsschalter 5 Positionsschalter 2 Leistungsschalter 6 Positionsschalter GND Masse Leistungss...

Страница 17: ...giewert wird aber mit einer h heren Aufl sung geliefert Befehlsstruktur Format 0 f r den zyklischen Datenaustausch Die von dem PMINT Modul unterst tzte Befehlsstruktur Format 0 f r den zyklischen Date...

Страница 18: ...tion zu Ausl seeinheit noch nicht aufgebaut 15 Lastabwurf 1 Zustand prim r Alarm Ursache 26 Tabelle 8 Kontrolle Zyklischer Datenaustausch Format 1 Byte Datentyp Beschreibung Aufl sung 0 vorzeichenlos8...

Страница 19: ...m PROFIBUS Master vermittelt wenn das PMINT Modul einen zyklischen Datenaustausch mit hoher Priorit t zur ck meldet Tabelle 12 Diagnosebits der DP V0 Einheit Byte Bit s Wert Beschreibung 7 08H Header...

Страница 20: ...upp 1 187 5_supp 1 500_supp 1 1 5M_supp 1 3M_supp 1 6M_supp 1 12M_supp 1 MaxTsdr_9 6 60 Bit Time MaxTsdr_19 2 60 Bit Time MaxTsdr_31 25 60 Bit Time MaxTsdr_45 45 60 Bit Time MaxTsdr_93 75 60 Bit Time...

Страница 21: ...Unit_Diag_Bit 0034 Data Object 10 invalid Unit_Diag_Bit 0035 Data Object 11 invalid Unit_Diag_Bit 0036 Data Object 12 invalid Unit_Diag_Bit 0037 Data Object 13 invalid Unit_Diag_Bit 0038 Data Object 1...

Страница 22: ...ng des Worts das die Ursache f r den prim ren Status beschreibt ist in Tabelle 15 aufgef hrt Tabelle 13 Statuscodes prim rseitig Code Definition Code Definition 0 Unbekannt 19 Alarm Phase A 1 ffnen 20...

Страница 23: ...schaltstromausl ser 36 Betriebszeit berschritten 76 fest unverz gert bei berstrom in Phase 3 37 berwachung Spule 77 Sollwertfehler 38 Programmierbare Logik 78 bertemperatur 39 Diagnosewarnung 1 79 Zub...

Страница 24: ...lation und Verwendung Eaton Industries GmbH Electrical Sector 2010 by Eaton Industries GmbH nderungen vorbehalten Subject to alterations 04 10 AWB1230 1621 Z8896 Moon Doku Heng Printed in USA 04 10 04...

Отзывы: