8
Eaton PDI WaveStar Color Monitor Setup and Operation Manual P-164001109—Rev 01
33..22..11
M
Mooddbbuuss R
RTTU
U P
Poorrttss
The Color Monitor has four (4) paralleled Modbus ports:
•
J1 and J3 are header/plug connections for connecting to most devices.
–
J1 is the upstream port.
–
J3 is the downstream port.
•
J2 and J4 accept standard RJ12 phone cable plugs for connection to an M4G PDU board.
–
J2 is the upstream port.
–
J4 is the downstream port.
The Modbus RTU interface is isolated, and pin designations are given in
:
Table 1. Pin-Out for Modbus Headers
Pin
J1, J3
J2 (for RJ12 plugs)
J4 (for RJ12 plugs)
1
Ground
Not used
Not used
2
RX-
RX-
TX-
3
RX+
TX-
RX-
4
TX-
RX+
TX+
5
TX+
TX+
RX+
6
NA
Ground
Ground
33..22..22
M
Mooddbbuuss R
RTTU
U 22--W
Wiirree vvss.. 44--W
Wiirree C
Coonnffiigguurraattiioonn
Eaton devices have two (2) jumpers near their Modbus ports for configuring 2-wire vs. 4-wire Modbus RTU
(see
). The Monitor’s 2-wire configuration jumpers are W1 and W2 (upstream) and W3 and W4
(downstream). Upstream and downstream chains can be differently configured.
For 2-wire configuration:
•
At least one device in a device chain must have both jumpers jumped on its Modbus connection. If any
device in the chain has jumpers installed for 2-wire, all of the device chain is 2-wire. To avoid confusion
when troubleshooting, all of the devices in the chain should be jumped in the same way.
•
TX+ or RX+ on the Monitor (either one, because the on-board 2-wire jumpers short them together) wires
to TX+ or RX+ on downstream devices.
•
TX- or RX- on the Monitor wires to TX- or RX- on downstream devices.
•
The + and - signal wires should comprise of a (twisted) wire pair residing in the same shield.
For 4-wire configuration:
•
All of these jumpers must be removed from every device in the chain.
•
TX+ on the Monitor’s PCB or on the customer Building Management System (BMS) wires to RX+ on a
device PCB (see
).
•
TX- from the Monitor or BMS wires to RX- on device PCB (see
•
A second pair of wires connects the other pair of TX+ / RX+ and TX- / RX-.
•
The TX+ and TX- going to the RX+ and RX- should be in the same shield. Do not run the +'s in one shield
and the -'s in another. Doing so may lead to sporadic communication.
Содержание PDI WaveStar
Страница 1: ...p n P 164001109 Revision 01 Setup and Operation Manual Eaton PDI WaveStar Color Monitor...
Страница 4: ......
Страница 8: ...viii Eaton PDI WaveStar Color Monitor Setup and Operation Manual P 164001109 Rev 01 List of Figures...
Страница 10: ...x Eaton PDI WaveStar Color Monitor Setup and Operation Manual P 164001109 Rev 01 List of Tables...
Страница 12: ...2 Eaton PDI WaveStar Color Monitor Setup and Operation Manual P 164001109 Rev 01 Safety...
Страница 30: ...20 Eaton PDI WaveStar Color Monitor Setup and Operation Manual P 164001109 Rev 01 Setup Monitor and Network...
Страница 60: ...50 Eaton PDI WaveStar Color Monitor Setup and Operation Manual P 164001109 Rev 01 Web Pages...
Страница 62: ...52 Eaton PDI WaveStar Color Monitor Setup and Operation Manual P 164001109 Rev 01 Glossary...
Страница 64: ...54 Eaton PDI WaveStar Color Monitor Setup and Operation Manual P 164001109 Rev 01 Bibliography...
Страница 68: ...P 16400110901 P 164001109 01...