Eaton PDI WaveStar TFA Static Transfer Switch Installation and Operation Manual P-164001113—Rev 01
•
The automatic retransfer to the Preferred Source can be disabled by an authorized user with administrator,
service, or Eaton level privileges, by setting
Retransfer = No
.
•
If
Retransfer = No
, there is no affinity to the Preferred Source, except at startup. The logic will transfer the
load from the failing source to the "good" source and will remain on that source even after the Preferred
Source returns to acceptable limits. The only effect of specifying a Preferred Source is to specify the
source used at STS startup.
•
Retransfer = No
also allows the operator to verify the power source prior to reapplying the critical load.
After verifying power reliability on the Preferred Source, the operator can force a manual transfer back.
99..11..33
M
Maannuuaall TTrraannssffeerrss
Manual transfers can be made in three ways:
1.
In Normal Mode, from Home screen, switching the Preferred Source to the other source will manually
transfer the load to the other source if:
a.
Preferred Source = Current Source, and
b.
the new Preferred Source is within acceptable voltage limits and phase tolerances. The selected
transfer algorithm, VSS or POG, is used.
2.
In Normal Mode, toggling the SOURCE SELECTOR momentary toggle switch on the ROI panel is an
alternative way to set the Preferred Source. Transfer behavior is the same as in (1.) above.
3.
In Redundant Mode, from the ROI panel, toggling the SOURCE SELECTOR momentary toggle switch
directly transfers the load to the other source, if not already on that source and the other source is within
specification. The SAS logic board controls the transfer, not the Monitor logic.
99..11..44
S
Sppeecciiaall TTrraannssffeerr S
Siittuuaattiioonnss
To keep power flowing to the output load, STS logic responds to several special circumstances:
•
Excessive transfers.
If transfers between sources become excessive, the logic dynamically adjusts
certain transfer parameters to minimize thrashing between sources until one or the other power source
stabilizes.
•
Excessive load current.
If the load current exceeds an adjustable preset level, automatic transfers are
disabled until load current falls below that level, even if the voltage on the selected source exceeds the
transfer limits.
•
Shorted power switching element.
Shorted SCRs cannot be opened and the load must remain on or be
transferred to the side with the shorted SCR to avoid cross-currents. Hence,
–
If there is a shorted SCR on the non-conducting side, the load is transferred to the non-conducting
side and retransfer is inhibited. The input switch or circuit breaker on the previously conducting side is
opened. An alarm is sounded and recorded with a date-and-time stamp in the Event Log.
–
If there is a shorted SCR on the conducting side, transfer is inhibited and the input switch or circuit
breaker on the non-conducting side is opened. An alarm is sounded and recorded with a time/date
stamp in the event log.
Example A:
1.
Source 1 is the Preferred Source and is supporting the load.
2.
Source 1 experiences an outage.
3.
The load is transferred to Source 2.
4.
The current inrush reduces voltage to Source 2 for (2) cycles.
5.
This causes the internal voltage monitors to detect an outage on both sources.
Содержание PDI WaveStar TFA STS 250-600A
Страница 4: ......
Страница 16: ...2 Eaton PDI WaveStar TFA Static Transfer Switch Installation and Operation Manual P 164001113 Rev 01 Safety ...
Страница 120: ...106 Eaton PDI WaveStar TFA Static Transfer Switch Installation and Operation Manual P 164001113 Rev 01 Web Pages ...
Страница 124: ...110 Eaton PDI WaveStar TFA Static Transfer Switch Installation and Operation Manual P 164001113 Rev 01 Troubleshooting ...
Страница 149: ...Eaton PDI WaveStar TFA Static Transfer Switch Installation and Operation Manual P 164001113 Rev 01 135 Resources ...
Страница 150: ...P 16400111301 P 164001113 01 ...