Eaton PDI WaveStar TFA Static Transfer Switch Installation and Operation Manual P-164001113—Rev 01
77..55..33
R
Reem
moottee S
Soouurrccee S
Seelleecctt O
Oppttiioonn
Two external two dry contacts can be used to control the remote selection of the preferred source. Dry contact
closures are generally used when two UPSs supply power to the system. If the preferred UPS goes to bypass
mode, the "good" UPS becomes preferred:
•
Signal 1 (Remote Select S1) dry contact closure will make Source 1 preferred.
•
Signal 2 (Remote Select S2) dry contact closure will make Source 2 preferred.
•
If both dry contacts closures are open, the preferred source control is returned to the system operator
control panel.
Any remote-control signal or closure puts the unit into a "Retransfer=Yes" mode to ensure system redundancy.
Normally the closures are controlled by auxiliary contacts in the UPS bypass circuit breakers. If both dry
contacts close, the first input to the TFA STS is recognized.
77..55..44
M
Muullttii--S
Sw
wiittcchh LLiinnkk O
Oppttiioonn ((N
N++11 U
UP
PS
S))
In an N+1 UPS Configuration, there are multiple STS units, each with a preferred source fed by a separate UPS.
The alternate source on all STSs is provided by a single backup UPS.
All STS units in an N+1 UPS configuration must have Enhanced Contractor Boards and the Multi-Switch Link
Option installed, providing coordination among the STSs.
Because the backup UPS can only provide power through the STS to a single downstream load, when an STS
transfers its load to the backup UPS, the STS must signal the other STS units that it is using the UPS. The other
STS units are locked out and cannot transfer to the backup source.
An "Inhibit Transfer" alarm is signaled on each STS. The STSs are prevented from transferring until the Preferred
Source on the STS using the backup UPS returns to normal and the STS retransfers the load back to the
Preferred Source.
Содержание PDI WaveStar TFA STS 250-600A
Страница 4: ......
Страница 16: ...2 Eaton PDI WaveStar TFA Static Transfer Switch Installation and Operation Manual P 164001113 Rev 01 Safety ...
Страница 120: ...106 Eaton PDI WaveStar TFA Static Transfer Switch Installation and Operation Manual P 164001113 Rev 01 Web Pages ...
Страница 124: ...110 Eaton PDI WaveStar TFA Static Transfer Switch Installation and Operation Manual P 164001113 Rev 01 Troubleshooting ...
Страница 149: ...Eaton PDI WaveStar TFA Static Transfer Switch Installation and Operation Manual P 164001113 Rev 01 135 Resources ...
Страница 150: ...P 16400111301 P 164001113 01 ...