108
Eaton PDI WaveStar TFA Static Transfer Switch Installation and Operation Manual P-164001113—Rev 01
2.
Login on the
Home
page as Administrator or other higher-level authorization.
3.
Touch the
Reset
button on the
Alarms
page to clear alarms. (Alarms will remain listed in the Event Log.)
4.
Check that SAS board alarms clear and do not reappear.
5.
If SAS board alarms reappear, contact your customer service representative.
1155..55
C
Coom
mppoonneenntt FFaaiilluurree
The TFA STS has substantial component redundancy and a single component failure will normally not impact
operation. Nevertheless, if alarms indicate component failure, contact your customer service representative.
1155..66
C
Coom
mm
moonn FFeeeeddeerr ffoorr bbootthh S
Soouurrcceess
If both power sources are temporarily fed from a common upstream feeder, the unit should be put in bypass
until two independent source feeders are available.
Содержание PDI WaveStar TFA STS 250-600A
Страница 4: ......
Страница 16: ...2 Eaton PDI WaveStar TFA Static Transfer Switch Installation and Operation Manual P 164001113 Rev 01 Safety ...
Страница 120: ...106 Eaton PDI WaveStar TFA Static Transfer Switch Installation and Operation Manual P 164001113 Rev 01 Web Pages ...
Страница 124: ...110 Eaton PDI WaveStar TFA Static Transfer Switch Installation and Operation Manual P 164001113 Rev 01 Troubleshooting ...
Страница 149: ...Eaton PDI WaveStar TFA Static Transfer Switch Installation and Operation Manual P 164001113 Rev 01 135 Resources ...
Страница 150: ...P 16400111301 P 164001113 01 ...