Eaton PDI WaveStar Infinity 2 Monitoring System Setup and Operation Manual P-164001106—Rev 01
77..22
IInnlliinnee C
Caalliibbrraattiioonn
If
Inline Calibration
is checked on the
GENERAL
screen, you can calibrate any analog measurement directly
from a measurement screen without going to the
CALIBRATE
screen.
Table 5. Inline Calibration Procedure
Calibration Step
Screen or Illustration
1.
Display
HOME
screen.
2.
Log in (as an administrator).
3.
Touch or click an analog measurement field
on the
HOME
screen, such as
V
,
VI
,
I,
or
Panels
.
(
Output Voltage
is used in this example.)
4.
Touch or click the measurement field you
wish to calibrate.
(When using a mouse, when you mouse over
the measurement field it will change color.)
4
5.
A small screen pops up over the
measurement screen that lets you enter any
calibrated measurement in the selection.
Enter calibrated
measurement.
6.
Enter value for the circuit you are calibrating,
then select outside the box (so that the box
“loses focus”). The box will turn green if
calibration is successful, but red if not
successful.
7.
Close pop-up when you are done.
Содержание PDI WaveStar Infinity 2
Страница 1: ...p n P 164001106 Revision 01 Setup and Operation Manual Eaton PDI WaveStar Infinity 2 Monitoring System...
Страница 4: ......
Страница 10: ...x Eaton PDI WaveStar Infinity 2 Monitoring System Setup and Operation Manual P 164001106 Rev 01 List of Tables...
Страница 12: ...2 Eaton PDI WaveStar Infinity 2 Monitoring System Setup and Operation Manual P 164001106 Rev 01 Safety...
Страница 60: ...50 Eaton PDI WaveStar Infinity 2 Monitoring System Setup and Operation Manual P 164001106 Rev 01 Setup...
Страница 76: ...66 Eaton PDI WaveStar Infinity 2 Monitoring System Setup and Operation Manual P 164001106 Rev 01 Maintenance...
Страница 78: ...P 16400110601 P 164001106 01...