Figure 42. Panelboard Screens (Part 2)
LOAD/MIN/MAX
screen:
Current (A)
Breaker Rating (A)
Load (%Current/Rating)
Min (A) since reset
Max (A) since reset
THD-F (%)
Crest Factor (CF)
POWER DEMAND
screen:
Current (A)
Demand (A)
Max Demand (A)
Demand (KW)
Max Demand (KW)
KWH (KW)
Crest Factor (CF)
Unlike major circuits or subfeeds, panelboard circuits have (3) alarm types:
•
Alarm: current exceeded alarm level (color code=red)
•
Warning: current exceeded warning level (color code=orange)
•
Zero: current fell to ≤ 0.5A after first measuring ≥ 3A (color code=orange)