There is one consolidated Modbus points lists and one SNMP MIB that is specific to the unit’s monitoring
configuration, with an analog points section and a digital points section. The names of sensors and sensor
boards are listed on the
Sensors’ Status
screen. These same sensor names are used on the
Sensors’ Status
screen, the Modbus points list, and SNMP MIB.
In the Modbus Points List and SNMP MIB:
•
Points are grouped together by sensor board and each group of sensor points appears in the same order as
on the
Sensors’ Status
screen.
•
The first part of each point name is the name of the sensor or sensor board.
•
42-Pole panelboards have separate sensor strips for the odd side (CTs 1,3,5, etc.) and even side (CTs
2,4,6, etc.), which are addressed in the Points List and MIB as a single contiguous set of points (CTs
1,2,3,4,5,6, etc.). 84-Pole panelboards have four (4) sensor strips.
shows how the Sensors’ Status list corresponds to sections of the Modbus points list.
NOTE
System configurations vary based upon customer request.
Table 2. Sensor Status List vs. Modbus Point List
Sensors’ Status Screen
Modbus Analog Points section
(1
st
point in each section is shown)
Modbus Digital Points section
(1
st
point in each section is shown)
The Digital Points section is found after the
Analog Points section.
(Global Points in your Points
List Prolong are not found
on any sensor board.)
Prolog: Global Points
, such as total number of
alarms outstanding
Prolog: Global Points
, such as System All
Alerts, showing alarms are present
Input Voltage
Input Voltage
A-B (1
st
analog Input Voltage
point)
Input Voltage
A-B High (1
st
digital point)
Input Current
Input Current
A (1
st
Input Current analog point)
Input Current
A High (1
st
Transformer Input
Current digital point)
Transformer
Transformer
Debounce (this is the only analog
Transformer point)
Transformer
Thermal High Temp Status (1st
digital Transformer Output point)
Output Voltage
Output Voltage
A-B (1
st
Output Voltage point)
Output Voltage
A-B High (1
st
digital
Transformer Output Voltage point)
Output Current
Output Current
A (1
st
Output Current analog
point)
Output Current
A High (1
st
Transformer Output
Current digital point)
Subfeed 1 Current
Subfeed 1
Current A (1
st
Subfeed 1 Point)
Subfeed 1
Current A High (1
st
Subfeed 1 digital
point)
Subfeed 2 up to Subfeed 16
Current
Each Subfeed points list is the same as for
others of the same type.
Each Subfeed points list is the same as for
others of the same type.
Panel 1–8 CT1–41 (odd)
Panel 1–8 CT2–42 (even)
Panels 1-8
are not shown.
Each panelboard points list is the same as for
others of the same type.
Panels 1-8
are not shown.
Each panelboard points list is the same as for
others of the same type.
Содержание PDI WaveStar Infinity 2
Страница 1: ...p n P 164001106 Revision 01 Setup and Operation Manual Eaton PDI WaveStar Infinity 2 Monitoring System...
Страница 4: ......
Страница 10: ...x Eaton PDI WaveStar Infinity 2 Monitoring System Setup and Operation Manual P 164001106 Rev 01 List of Tables...
Страница 12: ...2 Eaton PDI WaveStar Infinity 2 Monitoring System Setup and Operation Manual P 164001106 Rev 01 Safety...
Страница 60: ...50 Eaton PDI WaveStar Infinity 2 Monitoring System Setup and Operation Manual P 164001106 Rev 01 Setup...
Страница 76: ...66 Eaton PDI WaveStar Infinity 2 Monitoring System Setup and Operation Manual P 164001106 Rev 01 Maintenance...
Страница 78: ...P 16400110601 P 164001106 01...