Eaton PDI WaveStar BCMS Hub Installation and Operation Manual P-164001108—Rev 01
23
•
A: Administrator
•
S: Service
The Eaton class is hardcoded and cannot be assigned by the administrator.
44..22
S
Seettttiinnggss S
Sccrreeeenn
The Settings screen has panels for Modbus RTU, Ethernet, manual Time setting, and the Home page banner
heading.
Touch the
Setup
tab to display the
Settings
screen.
Figure 16. Settings Screen
44..22..11
M
MooddB
Buuss S
Seettttiinnggss
The downstream link from the BCMS Hub to its monitored devices is always Modbus RTU at 9600 bps.
Modbus RTU parameters for upstream link from the BCMS Hub to the BMS or other Modbus client device is
specified in the
Modbus Settings
panel:
•
Address
The Modbus address of the BCMS Hub as addressed from the upstream Modbus client device
can be changed by touching the Address button and entering a value from 1 to 246. Default address is 1.
•
Baud rate upstream from the BCMS Hub can be 9600 or 19200 bps.
•
Modbus RTU upstream parity can be even (e), odd (o) or none (n).
•
Offset
determines whether the BCMS Hub Modbus address is added to downstream device addresses
when displayed on the
Home
page device list.
Содержание PDI WaveStar BCMS
Страница 1: ...p n P 164001108 Revision 01 Installation and Operation Manual Eaton PDI WaveStar BCMS Hub...
Страница 4: ......
Страница 8: ...viii Eaton PDI WaveStar BCMS Hub Installation and Operation Manual P 164001108 Rev 01 List of Figures...
Страница 10: ...2 Eaton PDI WaveStar BCMS Hub Installation and Operation Manual P 164001108 Rev 01 Safety...
Страница 28: ...20 Eaton PDI WaveStar BCMS Hub Installation and Operation Manual P 164001108 Rev 01 Installation...
Страница 38: ...30 Eaton PDI WaveStar BCMS Hub Installation and Operation Manual P 164001108 Rev 01 System Setup...
Страница 52: ...44 Eaton PDI WaveStar BCMS Hub Installation and Operation Manual P 164001108 Rev 01 Glossary...
Страница 54: ...P 16400110801 P 164001108 01...