Electronic Trip Circuit Breaker Adjustable settings
(I
n
= Max. current rating)
I
r
= Adjustable current setting (0.5 – 1.0 x I
n
) for Long Time Pick-up.
t
r
= Adjustable Long Time Pick-up Delay (2 – 20 sec.) factory set at 10 seconds.
I
sd
= Adjustable Short Time Pick-up (2 – 10 x I
r
) factory set at 6 x I
r
.
t
sd
= Short Time Pick-up Delay (0 – 1000 ms) factory set at 0 ms.
Note: Instantaneous Pick-up fixed at 12 x I
n
.
M22-K10
M22-K01
M22-CK10
M22-CK01
Auxiliary Switches
HIA
HIN
HIN
-NA
-CNA
(UL/CSA)
I
th
=
I
e
a
or – oder – ou – ó – oppure –
或者
–
или
Notes on mounting and wiring Auxiliary Switches for UL/CSA labeled models:
– M22-K(10)(01) have screw terminals. M22-CK(10)(01) have clamp terminals.
– Switch modules are snapped into place at the locations shown in the diagrams that follow.
– Switches will function as either „standard“ or „trip/alarm“ contacts depending on their mounting location.
– Location „HIN“ refers to standard operation. Location „HIA“ refers to „trip/alarm“ operation.
– Follow the numbering and wiring scheme provided above depending on the contact location and function. (N.O. or N.C.)
– Permissible contact configuration: 1 HIA and/or 2 HIN.
ICE
I
th
=
I
e
Note:
After mounting of the M22… switch is complete, check off the appropriate box on the auxiliary switch
label provided on the side of the breaker or switch.
1
1
2
F
3 mm
ON
Trip
2
ON
Trip
Z 2
I
sd
t
sd
6
x
I
r
t
r
t
r
= 20 s
t
r
= 2 s
I
r
4.14
4.12
4.13
4.11
a
1.14
1.12
1.13
1.11
a
1.24
1.22
1.23
1.21
a
U
e
(V)
I
e
(A)
600 AC
10 A
250 DC
1 A
Pilot Duty Ratings:
A 600, P 300
Above 300 V AC
Same polarity
U
e
(V)
I
e
(A)
AC-15
115
4
230
4
400
2
500
1
DC-13
24
3
42
1.7
60
1.2
110
0.8
220
0.3