IMPORTANT SAFETY INSTRUCTIONS

Read before installing product. 

Safety of Persons

 The UPS has its own internal power source (the battery). Consequently, the power outlets may be energized even if the UPS is 

 

disconnected from the AC-power source.

Dangerous voltage levels are present within the 

 

UPS. It should be opened exclusively by qualified service personnel.

 The

 

 UPS must be properly earthed. Measurements are required to ensure that the total leakage current of the UPS and the protected 

equipment does not exceed 3.5 mA by checking their characteristics.

 The battery supplied with the 

 

UPS contains small amounts of toxic materials. To avoid accidents, the directives listed below 

must be observed:

- Never burn the battery (risk of explosion).
- Do not attempt to open the battery (the electrolyte is dangerous for the eyes and skin).
- Comply with all applicable regulations for the disposal of the battery.
-  Batteries constitute a danger (electrical shock, burns). The short-circuit current may be very high. Precautions must be taken 

for all handling: remove watches, rings, bracelets and any other metal objects, use tools with insulated handles. 

Product Safety

The UPS connection in

 

structions and operation described in the manual must be followed in the indicated order.

 UPS must be connected to a nearby wall outlet that is easily accessible. The UPS can be disconnected from the AC-power source by 

 

removing the power cord.
 Check that the indications on the rating plate correspond to your AC-power system and to the actual electrical consumption of all the 

 

equipment to be connected to the UPS.
Never install the UPS near liquids or in an excessively damp environment.

 

Never let a foreign body penetrate inside the UPS.

 

Never block the ventilation grates of the UPS.

 

Never expose the UPS to direct sunlight or source of heat.

 

If the UPS must be stored prior to installation, storage must be in a dry place.

 

The admissible storage temperature range is -25ºC to +55

 

ºC. 

Special Precautions

 Once installed an

 

d connected to the AC power source for the first time, the battery will start to charge. Full charging to obtain the 

rated battery backup time requires at least 8 hours.
 Before and after the installation, if the UPS remains de-energized for a long period, the UPS must be energized for a period of 24 

 

hours, at least once every 6 months (for a normal storage temperature less than 25°C). This charges the battery, thus avoiding 

possible irreversible damage.
 During the replacement of the battery module, it is imperative to use the same type and number of element previously mounted 

 

in the UPS, in order to maintain an identical level of performance and safety. In case of doubt, don’t hesitate to contact our after 

sales department (for more information, refer to the web site www.eaton.com).