2

Product information

Introduction

Service Information S280-43-1 provides installation, operation, and 
maintenance instructions for the NOVA i three-phase, micropro-
cessor-controlled recloser. Before installing and operating this 
recloser, carefully read and understand the contents of this 
manual.

Read this manual first

Read and understand the contents of this manual and follow all 
locally approved procedures and safety practices before installing 
or operating this equipment. This recloser is used in conjunction 
with a Cooper Power Systems microprocessor-based recloser 
control. Refer to Service Information S280-70-18 for installation 
information on the Form 6/FXD pole mount control.

Additional information

These instructions cannot cover all details or variations in the 
equipment, procedures, or process described nor provide 
directions for meeting every possible contingency during installa-
tion, operation, or maintenance. For additional information, please 
contact your Cooper Power Systems representative.

Acceptance and initial inspection

Each recloser is completely assembled, tested, and inspected at 
the factory. It is in good condition when accepted by the carrier 
for shipment. Upon receipt, inspect the shipping container for 
signs of damage. Unpack the recloser and inspect it thoroughly for 
damage incurred during shipment. If damage is discovered, file a 
claim with the carrier immediately.

Handling and storage

Be careful during handling and storage of the recloser to minimize 
the possibility of damage. Refer to the Moving the Recloser and 
Lifting the Recloser sections. If the recloser is to be stored for any 
length of time prior to installation, provide a clean, dry storage 
area.

Standards

NOVA i reclosers are designed and tested in
accordance with:

IEC 62271-111 2005

IEEE Standard C37.60-2012™.

QUALITY STANDARDS

ISO 9001:2000 Certified Quality Management System.

Description of operation

The NOVA i recloser is a three-phase, vacuum-interrupting 
recloser designed for electrical distribution systems through 38 
kV. The NOVA i recloser is designed and tested to be compatible 
with Cooper Power Systems’ control-powered Form 6/FXD 
control.

The solid polymer insulation system does not rely on a gaseous, 
liquid, or foam dielectric. The NOVA i recloser is highly resistant to 
ozone, oxygen, moisture, contamination, and ultraviolet light. The
NOVA i recloser has three solid-polymer interrupter modules, 
polymer current transformers, and a low-energy magnetic actuator 
mechanism. It is suitable for operation through a temperature 
range of -40°C to +65°C.

Effective January 2017

NOVA

®

 15i, NOVA 27i, and NOVA 38i; Three-phase

microprocessor-controlled; installation and operation
instructions (S280-43-1)

Instructional Literature 

IL0104001E

Содержание NOVA 15i

Страница 1: ...Installation Form 6 FXD control settings Accessories Auxiliary switch Terminals Pole mounting hanger Arrester mounting brackets Substation mounting frame Service information Service requirements Freq...

Страница 2: ...s situation which if not avoided could result in death or serious injury CAUTION Indicates a potentially hazardous situation which if not avoided may result in minor or moderate injury CAUTION Indicat...

Страница 3: ...oser and inspect it thoroughly for damage incurred during shipment If damage is discovered file a claim with the carrier immediately Handling and storage Be careful during handling and storage of the...

Страница 4: ...100 9 4 kV 50 kV 45 kV 125 kV 100 16 4 kV 60 kV 50 kV 170 kV 100 23 0 kV 70 kV 60 kV Table 2 Current ratings A Description 15 kV 27 kV 38 kV Rated continuous current Short circuit current Symmetrical...

Страница 5: ...Terminal to terminal 1180 79 Lower terminal to ground earth 671 45 NOVA 27i Terminal to terminal 1473 55 Lower terminal to ground earth 951 35 NOVA 38i Terminal to terminal 1763 46 Lower terminal to g...

Страница 6: ...1E Effective January 2017 Figure 3 NOVA 15i recloser dimensions with 3 integrated voltage sensor option in load side Note All dimensions are mm Dimensions shown are approximate Terminal connectors Ter...

Страница 7: ...converter board also houses voltage monitoring and conditioning circuits that protect the battery from failure and provide trip close operations without ac power In the absence of ac power to the ele...

Страница 8: ...ices when making hitches and lifting the equipment Lift the unit smoothly and do not allow the unit to shift This equipment is not intended to protect human life Follow all locally approved procedures...

Страница 9: ...ded on both sides Hazardous voltage Solidly ground all equipment Failure to comply can result in death severe personal injury and equipment damage WARNING Equipment Damage Do not adjust or rotate bush...

Страница 10: ...of a grounding mat may be required depending upon the local safety regulations defining the permissible step and touch potential levels Consult local regulations for proper grounding procedures In pol...

Страница 11: ...the equipment It is recommended to use a minimum of 50 sq mm copper wire for the pole ground connection to the recloser 2 Any ground wire of the equipment is not allowed to be connected to the neutra...

Страница 12: ...quipment It is recommended to use a minimum of 50 sq mm copper wire for the pole ground connection to the recloser IMPORTANT All external inputs to the control must be routed within 203 mm of their co...

Страница 13: ...his equipment is not intended to protect human life Follow all locally approved procedures and safety practices when installing or operating this equipment Failure to comply can result in death severe...

Страница 14: ...tor located on the mechanism housing Provide a good electrical ground connection to the control cabinet ground Note Painted surfaces of the mechanism housing may prevent a ground connection to the rec...

Страница 15: ...voltage sensor Energize recloser and confirm the voltage outputs in the control When the recloser is energized the output of the voltage sensor in 6 V based upon the Form 6 FXD control s input impeda...

Страница 16: ...for a Wye connection Also the Phantom Phase feature must be disabled Refer to Service Information S280 70 4 for more information on programming the Form 6 FXD control Figure 16 Form 6 FXD control syst...

Страница 17: ...tion to copper wires to optimize the electrical connection Anti oxide coatings for temporary protection of wire brushed aluminum cable connections to flat pad terminals must be maintained at intervals...

Страница 18: ...ing brackets The arrester mounting bracket accessory see Figure 18 can be bolted to the recloser frame and pole mounting hanger for the addition of inboard and outboard arresters The arresters are not...

Страница 19: ...vailable for substation mounting applications Figure 19 Dimensions of NOVA i recloser with substation mounting frame accessory Terminal options A Eyebolt 1 0 500 mcm 89 Cable range 630 A maximum Eyebo...

Страница 20: ...gs settings and interface options on the recloser nameplate see Figure 6 are correct for the planned testing 2 Test electrical open and close operation Close and open the recloser contacts using the m...

Страница 21: ...0 seconds TEST 2 1 Close the recloser contacts 2 Ground the recloser 3 Ground Phase A terminal 2 and Phase C terminal 6 4 Apply proper test voltage to Phase B terminal 3 5 The recloser should withstan...

Страница 22: ...k to its original condition 1 Bypass and remove the recloser from service as described in this manual 2 Inspect module for damage to the terminals Remove any damaged terminals and replace 3 Inspect mo...

Страница 23: ...S3 COM N O R1 C Open COM N C 52a MS1 R1 A VTC Pull Up 2 R1 E Close COM N O 52b MS2 R1 B VTC Pull Up 1 H2 H1 R1 U R1 V LEGEND SYMBOL DESCRIPTIO N AB Actuator Circuit Board AS Auxiliary Switch 3 Stage C...

Страница 24: ...ts Reserved Printed in China Publication No IL01004001E November 2017 Eaton is a registered trademark of Eaton Corporation All other trademarks are property of their respective owners NOVA 15i NOVA 27...

Отзывы: