background image

COOPER POWER

SERIES

          

NOVA® 15i, NOVA 27i, and NOVA 38i; Three-phase 
microprocessor-controlled; installation and operation 
instructions (S280-43-1)

Instructional Literature  

IL0104001E

 

Effective January 2017

Ratings and specifications 

Check recloser ratings prior to installation. . . 

Dimensions 

NOVA i mechanism interface

Control-powered interface . . . . . . . . . . . . . . . 

Installation procedure 

Moving the recloser . . . . . . . . . . . . . . . . . . . 

Lifting the recloser . . . . . . . . . . . . . . . . . . . . 

Remove recloser from service . . . . . . . . . . . 

Grounding the nova i recloser . . . . . . . . . . 

Operation 

Electrical operation . . . . . . . . . . . . . . . . . . . . 

Open/close contact position indicator . . . . . 

Hotstick operation (manual open, electrical 
close) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 

Internal voltage sensing option 

Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . 

Form 6/FXD control settings . . . . . . . . . . . . . 

Accessories 

Auxiliary switch . . . . . . . . . . . . . . . . . . . . . . . 

Terminals . . . . . . . . . . . . . . . . . . . . . . . . . . . . 

Pole-mounting hanger . . . . . . . . . . . . . . . . . . 

Arrester-mounting brackets . . . . . . . . . . . . . . 

Substation-mounting frame . . . . . . . . . . . . . . 

Service information 

Service requirements . . . . . . . . . . . . . . . . . . 

Frequency of inspection. . . . . . . . . . . . . . . . . 

Testing operation . . . . . . . . . . . . . . . . . . . . . . 

High-potential withstand testing . . . . . . . . . . 

Inspection of nova i module . . . . . . . . . . . . . 

Troubleshooting 

Unit will not close . . . . . . . . . . . . . . . . . . . . . 

Unit will not open electrically . . . . . . . . . . . . 

Figure 1.

NOVA

®

 i Three-phase, microprocessor-controlled recloser. 

(shown with four-hole, flat-pad terminal accessory.)

Safety information

Hazard statement definitions  . . . . . . . . . . . . . 

Safety instructions   . . . . . . . . . . . . . . . . . . . . . 

Product information 

Introduction   . . . . . . . . . . . . . . . . . . . . . . . . . . 

Read this manual first   . . . . . . . . . . . . . . . . . 

Additional information   . . . . . . . . . . . . . . . . . . 

Acceptance and initial inspection   . . . . . . . . . 

Handling and storage  . . . . . . . . . . . . . . . . . . . 

Standards  . . . . . . . . . . . . . . . . . . . . . . . . . . . . 

Description of operation   . . . . . . . . . . . . . . . . 

Contents

2

2

3

3

3

3

3

3

3

3

6

7

7

9

9

12

12

12

13

15

16

16

16

17

18

19

19

19

20

21

21

21

Содержание NOVA 15i

Страница 1: ...Installation Form 6 FXD control settings Accessories Auxiliary switch Terminals Pole mounting hanger Arrester mounting brackets Substation mounting frame Service information Service requirements Freq...

Страница 2: ...s situation which if not avoided could result in death or serious injury CAUTION Indicates a potentially hazardous situation which if not avoided may result in minor or moderate injury CAUTION Indicat...

Страница 3: ...oser and inspect it thoroughly for damage incurred during shipment If damage is discovered file a claim with the carrier immediately Handling and storage Be careful during handling and storage of the...

Страница 4: ...100 9 4 kV 50 kV 45 kV 125 kV 100 16 4 kV 60 kV 50 kV 170 kV 100 23 0 kV 70 kV 60 kV Table 2 Current ratings A Description 15 kV 27 kV 38 kV Rated continuous current Short circuit current Symmetrical...

Страница 5: ...Terminal to terminal 1180 79 Lower terminal to ground earth 671 45 NOVA 27i Terminal to terminal 1473 55 Lower terminal to ground earth 951 35 NOVA 38i Terminal to terminal 1763 46 Lower terminal to g...

Страница 6: ...1E Effective January 2017 Figure 3 NOVA 15i recloser dimensions with 3 integrated voltage sensor option in load side Note All dimensions are mm Dimensions shown are approximate Terminal connectors Ter...

Страница 7: ...converter board also houses voltage monitoring and conditioning circuits that protect the battery from failure and provide trip close operations without ac power In the absence of ac power to the ele...

Страница 8: ...ices when making hitches and lifting the equipment Lift the unit smoothly and do not allow the unit to shift This equipment is not intended to protect human life Follow all locally approved procedures...

Страница 9: ...ded on both sides Hazardous voltage Solidly ground all equipment Failure to comply can result in death severe personal injury and equipment damage WARNING Equipment Damage Do not adjust or rotate bush...

Страница 10: ...of a grounding mat may be required depending upon the local safety regulations defining the permissible step and touch potential levels Consult local regulations for proper grounding procedures In pol...

Страница 11: ...the equipment It is recommended to use a minimum of 50 sq mm copper wire for the pole ground connection to the recloser 2 Any ground wire of the equipment is not allowed to be connected to the neutra...

Страница 12: ...quipment It is recommended to use a minimum of 50 sq mm copper wire for the pole ground connection to the recloser IMPORTANT All external inputs to the control must be routed within 203 mm of their co...

Страница 13: ...his equipment is not intended to protect human life Follow all locally approved procedures and safety practices when installing or operating this equipment Failure to comply can result in death severe...

Страница 14: ...tor located on the mechanism housing Provide a good electrical ground connection to the control cabinet ground Note Painted surfaces of the mechanism housing may prevent a ground connection to the rec...

Страница 15: ...voltage sensor Energize recloser and confirm the voltage outputs in the control When the recloser is energized the output of the voltage sensor in 6 V based upon the Form 6 FXD control s input impeda...

Страница 16: ...for a Wye connection Also the Phantom Phase feature must be disabled Refer to Service Information S280 70 4 for more information on programming the Form 6 FXD control Figure 16 Form 6 FXD control syst...

Страница 17: ...tion to copper wires to optimize the electrical connection Anti oxide coatings for temporary protection of wire brushed aluminum cable connections to flat pad terminals must be maintained at intervals...

Страница 18: ...ing brackets The arrester mounting bracket accessory see Figure 18 can be bolted to the recloser frame and pole mounting hanger for the addition of inboard and outboard arresters The arresters are not...

Страница 19: ...vailable for substation mounting applications Figure 19 Dimensions of NOVA i recloser with substation mounting frame accessory Terminal options A Eyebolt 1 0 500 mcm 89 Cable range 630 A maximum Eyebo...

Страница 20: ...gs settings and interface options on the recloser nameplate see Figure 6 are correct for the planned testing 2 Test electrical open and close operation Close and open the recloser contacts using the m...

Страница 21: ...0 seconds TEST 2 1 Close the recloser contacts 2 Ground the recloser 3 Ground Phase A terminal 2 and Phase C terminal 6 4 Apply proper test voltage to Phase B terminal 3 5 The recloser should withstan...