Safety guidelines to read  before installing the product 

1 The product must be used indoors only. 

Use 

Installation 

1 Do not place the product near liquid or In an excesslvel1• damp environment. 

1 Do not place the product directly in the sun or near a heat sour

c

e. 

1 Do not let liquid or foreign objects enter the product. 

1 Ground the product using a 2P + ground socket. 

1 When installing th8 product, ensure that the sum of the leakage currents of the product and the devices lt 

supplies does not exceed 3.5 mA. 

1 The AC-power Input must be connected to an  approprlate e

l

ectrica

network protectlon or tap-off clrcult 

(fuse or circuit-breaker). 

Warning; for safety reasons, only the 16A/16A lead should be used to connect the 

HotSwap MBP (Maintenance Bypass) module to a UPS with a power rating greater than 

2kVA. 

The 

HotSwap MBP 

module makes it possible to Service or even replace the UPS without aflecting the 

connected loads 

(Ho!Swap 

functlon). 

Refer to the UPS installalion and user manual. 

HotSwap  MBP module operation 

The 

HotSwap MBP 

module has a rotary switch with two positions: 

1 Normal - the load is supplled by the UPS, 

1 Bypass• 

the load is supplied directly by the AC-power source. 

UPS start-up with the HotSwap MBP module 

1  - Check that the UPS is correctly connected to the 

HotSwap MBP 

module. 

2 - Set swltch to the Normal position. 

3 - Start the UPS by presSlng the ON/OFF button on the UPS contml panel: 

1 The load is supplied by the UPS. 

Green LED "UPS ON -OK to switch" on the 

HotSwap MBP 

module goes ON. 

HotSwap MBP module test 

1  - Set swijch to the Bypass posilion and check that the load is still supplied. 

2 - Set swltch back to lhe Nomial position. 

Maintenance on a UPS equipped with the HotSwap 

MBP 

module 

The 

HotSwap MBP 

module makes it posslble to service or even replace the UPS without aflectlng the 

connecled loads 

(HotSwap 

funclion). 

Maintenance: 

1 - Set switch to the Bypass position. The red LED on the 

HotSwap MBP 

module goes ON, indicating that 

the load  is supplied directly with AC power. 

2 - Stop the UPS: green LED "UPS ON - OK to switch" goes OFF, the UPS can now be disronnected and 

replaced. 

Return to normal operation: 

1  - Check that lhe UPS is correctly connected to the HotSwap 

MBP 

module. 

2 - Start the UPS: green LED "UPS ON -OK to switch' on the HotSwap MBPmodulegoesON (otherwise, 

there is a connectlon error between the HotSWap MBP module and the UPS). 

3 - Sat swijch to tha Normalposition. The red LED on the HotSwap MBP module goes OFF. 