INM 5500 Rev 11
75
10 .4 .2 Trip calibration
Switches and multiturn potentiometers for setting the trip points are located on top of the unit
(see figure 10.7). For each of channels A and B:
i
Set trip switch to H (high) or L (low) as required (see table 10.4
for
relay
operation).
ii Set input current to the required value for trip-point.
iii Adjust SET A/SET B until LED A/B is on: then slowly adjust until
LED
goes
out.
iv Relays are energised in normal operation and de-energised when
tripped. A lit LED shows the safe condition (not tripped).
Table 10 .4
Trip
switch
A or B
Operation
PWR
LED
A or
B
LED
Relay contacts
11 - 12
8 - 9
10 - 11
7 - 8
H (high)
Input > trip setting
•
open
closed
H (high)
Input < trip setting
closed
open
L (low)
Input > trip setting
closed
open
L (low)
Input < trip setting
•
open
closed
-
-
•
•
open
closed
Terminal
Function
1
Current input
2
Transmitter ve
3
Common
7
Trip B (NC)
8
Trip B (COM)
9
Trip B (NO)
10
Trip A (NC)
11
Trip A (COM
12
Trip A (NO)
13
Supply –ve
14
ve
Figure 10 .7:
Top label