Front and Rear View 

 

 

Battery cover 

 

AC power switch (push to 
switch on and off). 

 

Alarm mute switch (push to 
switch off the alarm sounds). 

 

Indicator lights: 
 

 

AC on – green 

 

 

Battery mode – yellow 

 

 

Fault - red 

 

Connection cover 

 

DC output and alarm 
connector: 
 Pin 1:  +12V dc output 
 Pin 2:  0V dc output 
 Pin 3:  Alarm signal return 
 Pin 4:  On battery 
 Pin 5:  Replace battery 
 Pin 6:  Battery missing 
 Pin 7:  Low battery 

 

AC power connector 

 

Wall mount screw key-holes 

 Warnings

 

 

If MPS12-30 is hotter than usual, or the battery is hot or 
swollen, disconnect from AC socket/outlet, 

switch off AC 

power switch (

), and c

ontact your MPS12-30 supplier. 

 

Risk of explosion if incorrect battery type is used. 

 

Risk of internal damage if battery connections are reversed. 

 

Recycle old batteries according to local regulations. Or 
contact your MPS12-30 supplier for advice.

 

What is supplied with the MPS12-30 

 

Installation and Operation Guide 

 

AC power cord

 

What you will need to install the MPS12-30 

 

12V dc output/alarm cables (supplied with the terminal 
equipment or see Specifications). 

 

Small, flat blade screwdriver for output and alarm 
connectors. 

 

Optional: screwdriver and screws for wall mounting.

 

 

 

How to connect the MPS12-30 

1.

 

Unpack and check the MPS12-30. 

If any item is damaged or missing contact the product supplier. Do 

not use the MPS12-30 if it is damaged.

 

2.

 

Remove the rear cover (

). 

3.

 

Connect the dc output wires to pin 1 (+) and pin 2 (-) (

).  

The alarm connections are optional. Refer to instructions with the 

terminal equipment.

 

4.

 

Connect the AC power cord to the MPS12-30 (

). 

5.

 

Replace the rear cover.

 

How to mount the MPS12-30 

1.

 

Select a suitable location for  the MPS12-30: 

 

Close to an AC power socket/outlet. The AC power cord is 
the main AC disconnect device so ensure the socket/outlet 
is easily accessible. 

 

Close to the terminal equipment. Check the length of the 12V dc 
output/alarm cable. 

 

Protected from excessive moisture and temperature. See 
Specifications (on next page) for the recommended temperature 
range. 

2.

 

Either: 

 

Mount the MPS12-30 on its back on a flat, firm surface, or 

 

Mount it on a wall with two screws (see below). If needed, 
use wall anchors or plugs to suit the type of wall and the 
weight of the MPS12-30. 

 

 

Minimum wall space 

required: 

A = 130mm, B = 420mm 
 

Screw spacing: 

C = 80mm 
 

Place the screws at least: 

 

25mm from any side 
obstruction (D). 

 

70mm 

below

 any 

obstruction (E). 

 

350mm 

above

 any 

obstruction (F).

 

 

 

 

How to turn on the MPS12-30 

1.

 

Plug the MPS12-30 into the wall socket and switch on the 
socket. MPS12-30 will beep briefly. 

2.

 

Push in the AC power switch (

). The MPS12-30 will beep for 

two seconds. 

3.

 

The AC On light (green 

) will flash for five minutes (the 

MPS12-30 is performing a battery self-test).  

4.

 

Check the Alarm mute switch (

) is out. 

If the Alarm mute switch is pressed in, then the alarm will not sound 
to alert you to a problem (the lights will still operate). 

5.

 

Check the connected equipment is operating correctly. 

6.

 

After five minutes, check the 

AC On

 light (green 

) has 

stopped flashing and no other lights are on. 

If any other lights are on, or if the MPS12-30 beeps see below.

 

 

What the lights and alarm sounds mean 

Light and Alarm 

Sound*

 

Meaning and what to do

 

No lights on 

AC power is not connected. 

Action required:

 Check MPS12-30 is plugged 

into wall socket and socket is switched on. Press 
AC power switch (

). 

Green light on 

 

AC power is connected. Normal operation. 

Action required:

 None. 

Green light flashing

 

Battery self test. Lasts for 5 minutes at turn-on 
and every 21 days.  Normal operation. 

Action required:

 None. 

Yellow light on 

 

and beeps every 5 

seconds*

 

The MPS12-30 is operating on battery power** 
because the AC power is off.  

Action required:

 

Check MPS12-30 is plugged 

into wall socket and socket is switched on. 

Alarm will stop when AC power is restored. 

Yellow light 

flashing 

 

and beeps every

 

second* 

The battery power is low. The MPS will shortly 
shut down and the connected equipment will 
turn off. 

Action required:

 

Check MPS12-30 is plugged 

into wall socket/outlet and socket is switched 
on. 

Alarm will stop when AC power is restored. 

Red light flashing 

 

and beeps every

 2 

seconds* 

The battery has failed its self-test. 

Action required:

 Replace the battery (see next 

page).  

Red light on 

 

and beep is 

c

ontinuous* 

Internal fault. 

Action required: 

Disconnect from the AC 

socket/outlet. Switch off AC power switch (

). 

Contact your MPS12-30 supplier for the repair 
or replacement procedure. 

* No sound if the Alarm Mute switch (

) is pressed in. 

** Typically battery will last for five hours, depending on battery age and 

the connected equipment. 

 

Содержание MPS12-30

Страница 1: ...rmation pplies to damages or profits loss of product chaser s employees or nty representation or on products No such d without further notice does not convey any without limitation its d in any form b...

Страница 2: ...ternal damage if battery connections are reversed Recycle old batteries according to local regulations Or contact your MPS12 30 supplier for advice What is supplied with the MPS12 30 Installation and...

Страница 3: ...dc output alarm cable Protected from excessive moisture and temperature See Specifications on next page for the recommended temperature range 2 Either Mount the MPS12 30 on its back on a flat firm su...

Страница 4: ...gged into wall socket and socket is switched on Press AC power switch Green light on AC power is connected Normal operation Action required None Green light flashing Battery self test Lasts for 5 minu...

Страница 5: ...30 supplier for advice Specifications AC Supply Output Voltage Output Power Battery Type Backup time 1A discharge Recharge Time Discharge Preventio Rated Charging Vo Charge Current Output Terminals Al...

Страница 6: ...is document The foregoing disclaimer applies to damages or personal injury property damage loss of operation loss of profits loss of product or loss of time whether incurred by the purchaser the purch...

Страница 7: ...7 W 14 5 H 3 2 D Weight 3 5kg 7 7 lb Eaton Corporation disclaims any liability for direct indirect incidental special or consequential damages arising out of the application or use of any information...

Страница 8: ...d the weight of the MPS12 30 Minimum wall space required A 130mm B 420mm Screw spacing C 80mm Place the screws at least 25mm from any side obstruction D 70mm below any obstruction E 350mm above any ob...

Отзывы: