manualshive.com logo in svg
background image

 3 

 

Programming 

Parameter 
Name 

Default 
Value 

0 

1 

2 

3 

HHIR-PROG Handset 
Graphics 

Description 

 

 

Button Activation 

 

 

On / Raise 

 

On 

 

 

 

 

Turn lights on. 

Off / Lower 

 

Off 

 

 

 

 

Turn lights off. 

Walk test 

Off 

On 

Off 

 

 

 

When set to On this causes a red LED to 
flash on the sensor when it detects 
movement. Use this feature to check for 
adequate sensitivity levels. 

Time Out 
(Time 
adjustment) 

10 mins 

1, 10 & 
20 
minutes 

5, 15 & 
30 
minutes 

 

 

 

Once the detector is turned on, this value 
sets how long the lights will stay on once 
movement has ceased. 

Lux on level 
(Switch 
level on) 

2, 5 & 7 

4, 6 & 9   

 

 

Lux level setting to prevent the luminaires 
being switched on if the ambient light level 
is sufficient (adjustable between 1  
and 9). The luminaires will always be 
switched on at level 9.  

Lux off level 
(Switch 
level off) 

2, 5 & 7 

4, 6 & 9   

 

 

Lux level setting to switch the luminaires off 
during occupancy if the ambient light level 
goes above the setting (adjustable between 
1 and 9). Level 9 will always keep the lights 
on. This setting can be used for “window 
row switching”.  

Sensitivity 

1, 5 & 9 

3, 6 & 8   

 

 

Sensitivity level for detecting movement. 
1 = low sensitivity 
9 = high sensitivity 

Defaults 

 

 

 

 

 

Returns the unit to the default settings. 

Shift 

 

 

 

 

 

 

Use this button to select the settings in red 
and blue signified by the ‘Shift 1’ and ‘Shift 
2’ LEDs 

Number of Shift key presses 

The functionality of the MPD-C-EXT 12-24V is controlled by a number of parameters which 
can be changed or programmed by any of the following devices: 

 

HHIR-PROG

  Infrared Handset. See below for programmable functions. 

 

HHIR-LCD-PROG

  Infrared Handset (with LCD). See user guide for full 

programming details. 

For most basic programming operations the HHIR-PROG handset can be used and the 
following procedures are based on using this device. 
Point the handset at the Sensor and send the required programming commands to the unit 
as shown below. 
Valid commands will be indicated by a red LED flash. See page 1 for details of other LED 
responses. 

Note: other functions on the HHIR-PROG which are not shown below are not applicable to 
this product.

 

SHIFT 1  SHIFT 2 

SHIFT 1  SHIFT 2 

SHIFT 1  SHIFT 2 

SHIFT 1  SHIFT 2 

Содержание MPD-C-EXT

Страница 1: ... area is occupied lighting is only switched on when the level of natural light is below a preset level Features Microwave Sensor Detects movement within the unit s detection range allowing load control in response to changes in occupancy IR Receiver Receives control and programming commands from an IR infrared handset Light Level Sensor An integral adjustable photocell allows the lights to be kept...

Страница 2: ...t is necessary to screw through the rear of the enclosure ensure that any holes are covered with the caps provided and sealed with silicone sealant where appropriate Note when externally mounted the unit may be triggered by trees animals leaves etc Wiring NC NC NO COM NO Fault finding What if the load does not turn ON Check to see if the live supply to the circuit is good If the supply and wiring ...

Страница 3: ...e lights on This setting can be used for window row switching Sensitivity 9 1 5 9 3 6 8 Sensitivity level for detecting movement 1 low sensitivity 9 high sensitivity Defaults D Returns the unit to the default settings Shift Use this button to select the settings in red and blue signified by the Shift 1 and Shift 2 LEDs Number of Shift key presses The functionality of the MPD C EXT 12 24V is contro...

Страница 4: ...mm the power density is 6 of the ANSI IEEE C95 1 1991 recommended microwave power density At a distance of 5mm from the unit it is 84 of recommended power density Due to our policy of continual product improvement we reserve the right to alter the specification of this product without prior notice Eaton Lighting Systems Usk House Lakeside Llantarnam Park Cwmbran NP44 3HD UK Tel 44 0 1633 838088 Fa...