Exchange of Modules
25
06/09 AWB2723-1613en
Exchange of Modules
After replacement of the modules and connection of the
voltage the configuration button must be pressed. The new
module is assigned an address by this means.
Device status
The individual SmartWire-Darwin slaves indicate their device
status with the help of the LED diagnostics.
Table 1:
Diagnostic messages of the SmartWire-Darwin status
LED
h
Caution!
Replacement of the SmartWire-Darwin input/output
modules is not permitted until the entire SmartWire-
Darwin system has been switched off.
h
Caution!
The order of the SmartWire-Darwin units must not be
altered.
Designation
Colour
State
Message
SWD
Green
continuous light
Device is operating fault-free.
Flashing (1 Hz)
• addressing process in progress
– after gateway power On
– after actuation of the
configuration button on the
gateway
• slave not in current configuration
• invalid type
Flashing (3 Hz)
Device reports a diagnostics (see
section “Programming”, sub-point
“Diagnostics”)