background image

Before You Begin 

 

Menvier40/100 

Page 8 

KEY-K01/KP01/KPZ01 Controls and Displays 

2

3

6

5

5

4

7

1

 

1. LCD display  
2. Programming keys. 
3. Navigation keys. This key has built-in alert 
LEDs. 
4. Setting and unsetting keys. The ABCD 
keys have built-in status LEDs that can show 
the setting status of a part setting system. 
These LEDs can be disabled, see page 18. 
5. Plastic caps covering screws (shown 
closed and open). 
6. Hold Up Alarm (HUA) keys. 
7. Number/text keys. 

Figure 9 KEY-K01/KP01/KPZ01 Controls and 

Displays 

Opening the KEY-K01/KP01/KPZ01 

To open the unit, unclip the caps covering the 
screws on the front. (You may need to gently push 
the bottom edge of the caps in with the end of a 
small screwdriver to start them.) Remove the two 
screws hidden underneath (see Figure 9). Gently 
swing the lower side of the front out from the back 
box by about 10mm and then slide the front 
upwards to disengage the top catches. (Be careful 
not to pull the lower side of the front more than 
about 25mm away from the back while the top 
catches are engaged, or you may break the 
catches.) 

1

2

3

 

Figure 10 Opening the Keypad 

 

1. Central keyhole. 
2. Fixing holes. 
3. Cable entry. 
4. Tamper block 

Figure 11 Keypad Rear Housing 

 

1. Jumpers for addressing and LED function: 
 

1a Addressing (not used) 

 

1b LED functions 

2. Sounder volume control. 
3. Tamper switch. 
4. Sounder.  
5. Connector for control unit data bus. 

Figure 12 KEY-K01 Keypad PCB 

Содержание menvier40

Страница 1: ...Menvier40 Menvier100 Security System Installation Guide Issue 3...

Страница 2: ...by the words Note Caution or WARNING Note Describes conditions that may affect the proper functioning of the equipment but will not damage the equipment Caution Describes actions that will physically...

Страница 3: ...6 Connect Wired Zones 22 Four Wire Closed Circuit Connections 22 Two Wire Closed Circuit Connections 22 Fully Supervised Loop Connections 22 Step 7 Connect Wired Outputs 24 Control Unit Wired Outputs...

Страница 4: ...Menvier40 100 Page iv This page is intentionally blank...

Страница 5: ...and an external prox reader KEY EP A range of wireless peripherals is available for operation with the wireless expanders These include a door contact universal transmitter a passive infra red detect...

Страница 6: ...etting the time and date is a user function If you wish you can also program the system from a PC or laptop connected to the Ethernet port on the control unit PCB The control unit contains a web page...

Страница 7: ...ll affect the signal from a transmitter Please read Eaton s Security Business publication Guidance Notes for Wireless Alarm System Installations obtainable from www coopersecurity co uk for more infor...

Страница 8: ...conducting films These glasses are particularly poor at transmitting radio waves Guided Tour CAUTION All printed circuit boards for the control unit its expanders and keypads have been tested for Ele...

Страница 9: ...Control Unit 1 PSTN Connector for on board communicator 2 Lid tamper connector 3 RS485 terminator 4 Engineering keypad connector 5 USB socket Mini B 6 Heartbeat LED 7 Zone output and Aux power connec...

Страница 10: ...Page 6 1 Bus cable connector 2 Aux power 3 Wired zone connectors 4 Aux power 5 Outputs relay and transistorised 6 12V Siren Bell supply 7 Siren strobe and TR 8 Auxiliary tamper 9 Loudspeaker Figure 4...

Страница 11: ...e B ACE fixed To open the keypad first gently prise off the trim on the front and remove the two screws Next carefully lever the front of the keypad containing the PCB and display away from the keypad...

Страница 12: ...ont You may need to gently push the bottom edge of the caps in with the end of a small screwdriver to start them Remove the two screws hidden underneath see Figure 9 Gently swing the lower side of the...

Страница 13: ...XT READER Z1 Z2 OP 1 6a 6b 3 4 5 6 2 1 Tamper switch 2 Sounder 3 Connector for KEY EP Terminals for zones 4 Sounder volume control 5 Connector for control unit data bus and output terminal 6 Jumpers f...

Страница 14: ...ne connectors 16 Bus address display 17 Aux power 18 Loudspeaker connectors 19 Outputs Figure 15 EXP W10 Wired Expander 1 1 2 3 1 8 7 5 6 4 10 9 11 12 13 10 1 16 15 14 1 17 18 19 1 Cable entry also be...

Страница 15: ...3 Central keyhole 4 PCB 5 Link to enable disable front rear tamper switch 6 Lid tamper rear tamper behind PCB 7 Bus termination jumper 8 Addressing button 9 Fixing holes 10 Engineering keypad connect...

Страница 16: ...the overall calculation CAUTION Ensure that the system does not demand more than the maximum current available from the control unit during an alarm see page 38 Bus Cabling Requirements Cable Type In...

Страница 17: ...are only two arms on the star then this is the same as a daisy chain configuration see Daisy Chain 1 in Figure 18 If required fit the termination jumper at the devices on the end of each arm If there...

Страница 18: ...0 74V 1 47V 2 21V 2 94V 3 68V 4 42V 5 15V 5 89V 6 62V 7 36V 480mA 0 79V 1 54V 2 30V 3 07V 3 84V 4 61V 5 38V 6 14V 6 91V 7 68V 500mA 0 80V 1 60V 2 40V 3 20V 4 00V 4 80V 5 60V 6 40V 7 20V 8 00V 520mA 0...

Страница 19: ...the wall There must be enough space around this point to fit the supplied tamper shroud see Figure 21 Fitting Plastic Feet and Tamper Sleeve The control unit is supplied from the factory with four pl...

Страница 20: ...20Vac connector on the PCB 11 in Figure 3 Installing the Lid Back Tamper Figure 25 Lid Back Tamper Fit combined lid back tamper bracket and switch provided Ensure that the switch is oriented as shown...

Страница 21: ...riate plastic sections Use 4mm x 25mm countersunk screws with a thread suitable for the wall material in at least three fixing holes when mounting the back of the keypad on the wall i KP01 For i KP01...

Страница 22: ...ith EN50131 1 2006 at Grade 3 disable the ABCD LEDs Backlight Control for KEY K01 KP01 KPZ01 You can control the brightness of the keypad backlights by fitting links over the BRIGHT jumper on the keyp...

Страница 23: ...e following Status OK LED ON MENU STATUS OK LED Status OK LED OFF The green status LED under the navigation key will glow for 20 seconds after the last press this may be useful when the keypad is plac...

Страница 24: ...the single retaining screw 2 Tilt the edge of the fixing plate and then slide it a short distance parallel to the body of the prox reader 3 Slide the fixing plate away from the reader body along the c...

Страница 25: ...g Expanders Addressing Expanders The control unit assigns addresses to all devices connected to the bus cable You must start this process off from the Installer Menu during the initial power up See pa...

Страница 26: ...he wiring for CCL zones on the EXP WCC wired expander Note that the EXP WCC provides connectors for a total of ten separate 4 wire CCL detectors and that there are separate terminals for both alarm an...

Страница 27: ...ed Expander 4K7 Alarmcontacts Tamper contacts 2K2 EOL 4K7 Alarmcontacts Tamper contacts 100 Ohms Figure 41 FSL Zone Wiring EXP WCC The allowed values for Alarm Contact End of Line are the same as for...

Страница 28: ...methods of connection Figure 46 shows an example of a general method of using the outputs to connect a wired sounder It is possible to program the TR terminal on the control unit see item 7 in Figure...

Страница 29: ...on at the expander FSL wiring Connect TR to the left terminal of a zone connector see Figure 49 The left hand terminal is the one next to the Z on the terminal label The maximum length of wire is 50m...

Страница 30: ...e Line Fault Response selected in the Installer Menu Test Calls The control unit can be programmed to make test report calls to an ARC Static test calls can be programmed to occur at set times or inte...

Страница 31: ...ting a line in the UK The internal communicator must be connected to the telephone network by a If the wiring is owned by British Telecom British Telecom b If the wiring is not owned by British Teleco...

Страница 32: ...using a dual path communicator 3 Plug the Communication Wiring Harness onto the communications connector on the main PCB If the system has already been installed 4 Re connect the battery 5 Fit the ca...

Страница 33: ...control unit PCB item 6 in Figure 3 starts flashing The navigation keys on any attached keypad start flashing All connected keypads briefly show the software revision of the keypad itself followed by...

Страница 34: ...u should leave the Installer Menu to save the changes you have made see below Diagnostic LED on Expanders You may notice the DIAGNOSTIC LED flashing on an expander PCB The LED gives one two three or f...

Страница 35: ...including radio HUDs fire alarm zones 24 hour zones and tampers are disabled Note that this does not apply if you are using the web browser interface from a PC If you have logged into the system from...

Страница 36: ...ould now glow green Note The log is protected and cannot be erased by the Installer Restoring Factory Defaults Only If you wish to restore all factory default options without defaulting the user and i...

Страница 37: ...f any other peripherals Program the System Program the system to suit user requirements Page 34 is a summary of the Installer Menu on the control unit Please see the Menvier40 100 300 Engineering Guid...

Страница 38: ...ctive Quick set Quick omit User code reqd 2 Way Replies 2 Way Set Instant Duress Enable User reset Zone alarms 6 Zone tampers System tampers Confirmation Confirmation Mode Basic DD243 BS8243 Confirmat...

Страница 39: ...c Test call disabled 16 Appears only when Dynamic Test call is disabled 17 Appears only when Report Type Fast Format and Confirmation Mode Basic 18 Shows None if no module fitted 19 Must be activated...

Страница 40: ...ish to find the location of any keypad or expander you can employ the Test Locate Bus Device option in the Installer Menu Use this option to make a selected bus device give a continuous tone from its...

Страница 41: ...an connect any combination of these devices to the bus Capacities Menvier100 Zones 100 max with expanders Outputs 100 max with expanders Expanders and Wired Keypads 45 max devices see note Radio Keypa...

Страница 42: ...may have its own power supply For Security Grade 2 the required battery standby time is 12 hours However the total average current available over 12 hours from the 17Ah battery is limited by the powe...

Страница 43: ...868 6625MHz Narrowband EN 300 220 3 EN 300 330 2 Transmitter range The range of the transmitters compatible with this control unit depends on the environment in which they are installed As a guideline...

Страница 44: ...pad with internal prox reader but without zones or external prox reader key ep External prox reader for KEY KPZ01 KP01 KEY K01 keypad KEY KP01 keypad with internal prox reader and terminals for extern...

Отзывы: