Before You Begin 

Page 13 

Table 1. Voltage Drop 

Current 
Drawn 

Cable Length (Standard 7/0.2 alarm cable) 

 

10m 

20m 

30m 

40m 

50m 

60m 

70m 

80m 

90m 

100m 

60mA 

0.10V 

0.19V 

0.29V 

0.38V 

0.48V 

0.58V 

0.67V 

0.77V 

0.86V 

0.96V 

80mA 

0.13V 

0.26V 

0.38V 

0.51V 

0.64V 

0.79V 

0.90V 

1.02V 

1.15V 

1.28V 

100mA 

0.16V 

0.32V 

0.48V 

0.64V 

0.80V 

0.96V 

1.12V 

1.28V 

1.44V 

1.60V 

120mA 

0.19V 

0.38V 

0.58V 

0.79V 

0.96V 

1.15V 

1.34V 

1.54V 

1.74V 

1.92V 

140mA 

0.22V 

0.45V 

0.67V 

0.90V 

1.12V 

1.34V 

1.57V 

1.79V 

2.02V 

2.24V 

160mA 

0.26V 

0.51V 

0.77V 

1.02V 

1.28V 

1.54V 

1.79V 

2.05V 

2.30V 

2.56V 

180mA 

0.29V 

0.58V 

0.86V 

1.15V 

1.44V 

1.73V 

2.02V 

2.30V 

2.59V 

2.88V 

200mA 

0.32V 

0.64V 

0.96V 

1.28V 

1.60V 

1.92V 

2.24V 

2.56V 

2.88V 

3.20V 

220mA 

0.35V 

0.70V 

1.06V 

1.41V 

1.76V 

2.11V 

2.46V 

2.82V 

3.17V 

3.52V 

240mA 

0.38V 

0.79V 

1.15V 

1.54V 

1.92V 

2.30V 

2.69V 

3.07V 

3.46V 

3.84V 

260mA 

0.42V 

0.83V 

1.25V 

1.66V 

2.08V 

2.50V 

2.91V 

3.33V 

3.74V 

4.16V 

280mA 

0.45V 

0.90V 

1.34V 

1.79V 

2.24V 

2.69V 

3.14V 

3.58V 

4.03V 

4.48V 

300mA 

0.48V 

0.96V 

1.44V 

1.92V 

2.40V 

2.88V 

3.36V 

3.84V 

4.32V 

4.80V 

320mA 

0.51V 

1.02V 

1.55V 

2.05V 

2.56V 

3.07V 

3.58V 

4.10V 

4.61V 

5.12V 

340mA 

0.54V 

1.09V 

1.63V 

2.18V 

2.72V 

3.26V 

3.81V 

4.35V 

4.90V 

5.44V 

360mA 

0.58V 

1.15V 

1.73V 

2.30V 

2.88V 

3.46V 

4.03V 

4.61V 

5.18V 

5.76V 

380mA 

0.61V 

1.22V 

1.82V 

2.43V 

3.04V 

3.65V 

4.26V 

4.86V 

5.47V 

6.08V 

400mA 

0.64V 

1.28V 

1.92V 

2.56V 

3.20V 

3.84V 

4.48V 

5.12V 

5.76V 

6.40V 

Reducing Voltage Drop - Method 1: 

Double up the supply connections (12V and 0V), 
which will halve the resistance on each core and 
therefore halve the voltage drop. When using 
Table 1 to calculate the expected voltage drop, 
simply divide the voltage drop for a single core by 
two. 

Reducing Voltage Drop - Method 2: 

Supply the detection devices from the Aux output 
on separate cores. This is the preferred method of 
reducing voltage drop as detectors generally 
operate at lower voltages (9.5V). When using this 
method, the bus cable must have at least two 
spare cores.  

Remote Power Supplies 

When you cannot reduce voltage drops by 
method 1 or 2, or the demand on the control unit 
power supply exceeds its capacity (see Technical 
Specifications 

–page 33), you should install one or 

more remote power supplies. The supply must 
have a "floating zero volt rail" if connected to the 
bus, otherwise an earth fault will occur. 

Eaton’s 

Security Business recommends the EXP-PSU. 
When installing a remote power supply, fit it close 
to the equipment it is powering. 

Figure 19 shows the recommended method of 
connecting a remote power supply. 

 

Figure 19. Connecting Remote Power Supply Units 

Control unit

Device 1

12V
0V

0V      12V

Bus

Device 2

Remote PSU

Device 4

Device 3

Содержание menvier300

Страница 1: ...Menvier300 Security System Installation Guide Issue 3...

Страница 2: ...ment but will not damage the equipment Caution Describes actions that will physically damage the equipment and prevent its proper function WARNING Describes actions that are hazardous to health or cau...

Страница 3: ...19 Step 5 Connect Control Unit to Mains 19 Mains Cabling 19 Step 6 Connect Wired Zones 20 Four Wire Closed Circuit Connections 20 Two Wire Closed Circuit Connections 20 Fully Supervised Loop Connectio...

Страница 4: ...Menvier300 Page iv This page is intentionally blank...

Страница 5: ...s control unit is designed and approved to be used as part of a Security Grade 3 system The control unit is also approved to operate as part of a Security Grade 2 system If you install any radio devic...

Страница 6: ...rom a PC or laptop connected to the Ethernet port on the control unit PCB The control unit contains a web page server and you can use any web browser to see a complete version of the Installer menu Pl...

Страница 7: ...ition can all affect the signal from a transmitter Please read Eaton s Security Business publication Guidance Notes for Wireless Alarm System Installations obtainable from www coopersecurity co uk for...

Страница 8: ...conducting films These glasses are particularly poor at transmitting radio waves Guided Tour CAUTION All printed circuit boards for the Menvier300 its expanders and keypads have been tested for Electr...

Страница 9: ...ctors 11 RS485 terminator 12 Engineering keypad connector 13 Zone output and Aux power connectors 14 Kickstart pins Batt 1 only 15 Battery connectors two of 16 20Vac connector 17 USB socket Mini B Fig...

Страница 10: ...open the keypad first gently prise off the trim on the front and remove the two screws Next carefully lever the front of the keypad containing the PCB and display away from the keypad rear housing Fig...

Страница 11: ...ly push the bottom edge of the caps in with the end of a small screwdriver to start them Remove the two screws hidden underneath see Figure 9 Gently swing the lower side of the front out from the back...

Страница 12: ...Y EP Terminals for zones 4 Sounder volume control 5 Connector for control unit data bus and output terminal 6 Jumpers for addressing and LED function 6a Addressing 6b LED functions and RS485 bus termi...

Страница 13: ...ker connectors 19 Outputs Figure 15 EXP 10 Wired Expander 1 Cable entry also behind PCB 2 Central keyhole 3 PCB 4 Relay card i rc01 connector 5 Aux power 6 Link to enable disable front rear tamper swi...

Страница 14: ...able front rear tamper switch 6 Lid tamper rear tamper behind PCB 7 Bus termination jumper 8 Addressing button 9 Fixing holes 10 Engineering keypad connector 11 Bus cable connector 12 Sounder 13 Louds...

Страница 15: ...charge required by the example system for PD6662 Grade 3 requirements Note All current drawn from the Aux terminals 12V and 14 4V must be included in the overall calculation CAUTION Ensure that the sy...

Страница 16: ...e only two arms on the star then this is the same as a daisy chain configuration see Daisy Chain 1 in Figure 18 If required fit the termination jumper at the devices on the end of each arm If there ar...

Страница 17: ...V 4 03V 4 61V 5 18V 5 76V 380mA 0 61V 1 22V 1 82V 2 43V 3 04V 3 65V 4 26V 4 86V 5 47V 6 08V 400mA 0 64V 1 28V 1 92V 2 56V 3 20V 3 84V 4 48V 5 12V 5 76V 6 40V Reducing Voltage Drop Method 1 Double up t...

Страница 18: ...and mark the position of the case Also mark the position where the lid back tamper bracket touches the wall There must be enough space around this point to fit the supplied tamper shroud see Figure 21...

Страница 19: ...s the KEY EP or prox readers used by other systems for example access control systems If you mount prox readers closer together than one meter including on the other side of walls then the two prox re...

Страница 20: ...backlights by fitting links over the BRIGHT jumper on the keypad pcb see 1b in Figure 12 or 6b in Figure 14 Jumper OFF The keypad backlights glow at normal intensity Jumper ON The keypad backlights g...

Страница 21: ...cal programming mode and save your changes see below To Disable Enable the Status OK LED 1 Enter Local Programming mode MENU ABCD 2 Press repeatedly until the display shows MENU STATUS OK LED 3 Press...

Страница 22: ...ou do so then the prox readers will interfere and be unable to read tags Opening the External Prox Reader To open the external prox reader see Figure 27 1 Undo the single retaining screw 2 Tilt the ed...

Страница 23: ...nders Addressing Expanders The control unit assigns addresses to all devices connected to the bus cable You can start this process off from the Installer Menu during the initial power up See Initial P...

Страница 24: ...igure 35 shows the wiring for CCL zones on the KEY KPZ01 Figure 35 KEY KPZ01 CCL Zone Wiring Two Wire Closed Circuit Connections With version 4 02 and higher software you can connect two wire CCL dete...

Страница 25: ...examples Figure 39 Wiring FSL Zones on KEY KPZ01 When programming select the FSL resistor values for the control unit in Installer Menu System Options Wired Zone Type To select the resistor values for...

Страница 26: ...By default the terminal is CC If you program the TR terminal as FSL then make sure you connect a 2k2 resistor in series with the wire to the sounder Note If you do not wish to connect a wired externa...

Страница 27: ...or 4k7 4k7 FSL wiring and a single core of standard 6 core alarm cable Fit EITHER a 2k2 resistor if using 2k2 4k7 FSL OR a 4k7 resistor if using 4k7 4k7 FSL Do not use any other FSL resistor combinat...

Страница 28: ...lt is absent Remote Reset Tell Back Input This input is marked RR is designed to allow a plug by communicator to indicate to the control unit that the user can reset the system after a system tamper T...

Страница 29: ...sounders internal loudspeakers and wired sirens MAY give an alarm tone If you are working at the top of a ladder make sure that the sudden noise does not startle you and cause a fall 1 Apply mains pow...

Страница 30: ...one and shows its assigned address on the two digit LED display Replace the lid NOTE 1 DO NOT request a bus address from two different devices at the same time 2 EXP R30 expanders take three bus addre...

Страница 31: ...nt store If you remove all power BEFORE you leave the Installer Menu then the control unit will lose your changes Note that this does not apply if you restore Factory Defaults that change takes place...

Страница 32: ...d to restore the tamper switch The display shows the time and date for example 9 Key in the default user 01 code to silence the sounders The display shows 10 Enter Installer Menu and then leave it aga...

Страница 33: ...see Chapter 5 option to a carry out a walk test of the detectors b test the operation of any other peripherals Program the System Program the system to suit user requirements Page 30 is a summary of t...

Страница 34: ...Edit Exception Delete Exception 4 SYSTEM OPTIONS Wired Zone type Panel Zones All Zones User Access HUA keys active Quick set Quick omit User code reqd 2 Way Replies 2 Way Set Instant Duress Enable Use...

Страница 35: ...ears only when Dynamic Test call disabled 18 Appears only when Report Type Fast Format AND Confirmation Mode Basic 19 Shows None if no module fitted 20 Must be activated by a Eaton s Security Business...

Страница 36: ...wish to find the location of any keypad or expander you can employ the Test Locate Bus Device option in the Installer Menu Use this option to make a selected bus device give a continuous tone from it...

Страница 37: ...ents 1 500 mandatory events 500 non mandatory Stored in EEPROM memory available for at least 10 years without power Internal Clock 10 minutes over one year depending on the accuracy of the mains suppl...

Страница 38: ...t consumption of the control unit and each device that can be fitted to it CIE power requirement 140mA min 220mA max i kp01 power requirement 30mA backlight off 45mA 65mA backlight norm bright 60mA in...

Страница 39: ...nvironmental class II The Menvier300 is suitable for use in systems designed to comply with PD 6662 2010 at grade 3 When installed correctly the Menvier300 is capable of compliance with EN50131 at Gra...

Страница 40: ...output and terminals for external prox reader Setting Unsetting Fobs FOB 2W 4B Two way keyfob i fb01 Four button remote control 727rEUR 00 Four button remote control with encrypted code HUD function n...

Отзывы: