![Eaton MEMSHIELD 4 Скачать руководство пользователя страница 3](http://html1.mh-extra.com/html/eaton/memshield-4/memshield-4_installation-instructions-manual_3767521003.webp)
Reposition x6
male hinges
on enclosure.
Ensure
existing
scratch
washer and
M5 fixings are
reused and
tightened
Fit
Interphase
shields
Cableways, Extension/Corner/DIN Boxes and Plinths
Top Entry Conversion
Cableway-
EM4PB68SXB
EM4PB1214SXB
EM4PB1618SXB
Fits either side
Extension/DIN Box-
EM4PB250EX
EM4PB250EXDIN
Fits either end
Plinth
EM4PB100PL
EM4PB100PLCX
Corner Box-
EM4PB300CX
Fits either side
Box fixing, ensure scratch washers are fitted both sides
Cableway - Provision to
move earth bar into
cableway, utilising earth
strap
Plinth
–
Fit plinth
gland plate inside panelboard
Lift off front doors and rotate panelboard 180°
New position
Existing position
Utilising the same connectors, screws and washers, reconfigure from Bottom to Top Entry
Ensure connectors are kept in their supplied sets and spring washers are always fitted
beneath the screws
Remove shields
to gain access
to connectors.
Remembering
to replace all
shields after
connector
reconfiguration
Top Entry
Build Sequence for Top Entry
4
M10 x 40
M10 x30
M10 x30
3
M10 x35
Tightening
torque for all
connectors
–
30Nm
2 M10 x35
1
M10 x 40
Top
entry
neutral
shield
Reposition Hinges
Fit Incomer
30Nm
30Nm
15Nm
12-16 Way Cableway
–
Remove x1 cut-out
feature in cableway to gain access to
outgoing chamber
30Nm
With the inner
cover rotated
180°, remove
cut-outs as
shown
3 pole and N
MCCB
4 pole MCCB
Bottom Entry
Remove x6 male
hinges from
enclosure and
drill 2.2mmØ
holes as shown
6mmØ
5mmØ
Remove all
swarf