Eaton MEMSHIELD 4 Скачать руководство пользователя страница 3

Reposition x6 

male hinges 

on enclosure. 

Ensure 

existing 

scratch 

washer and 

M5 fixings are 

reused and 

tightened

Fit 
Interphase 
shields

Cableways, Extension/Corner/DIN Boxes and Plinths

Top Entry Conversion

Cableway-

EM4PB68SXB
EM4PB1214SXB
EM4PB1618SXB

Fits either side

Extension/DIN Box-

EM4PB250EX
EM4PB250EXDIN

Fits either end

Plinth

EM4PB100PL
EM4PB100PLCX

Corner Box-

EM4PB300CX

Fits either side

Box fixing, ensure scratch washers are fitted both sides

Cableway - Provision to 

move earth bar into 

cableway, utilising earth 

strap

Plinth 

Fit plinth

gland plate inside panelboard

Lift off front doors and rotate panelboard 180°

New position

Existing position

Utilising the same connectors, screws and washers, reconfigure from Bottom to Top Entry

Ensure connectors are kept in their supplied sets and spring washers are always fitted 

beneath the screws  

Remove shields 

to gain access 

to connectors. 

Remembering 

to replace all 

shields after 

connector 

reconfiguration 

Top Entry

Build Sequence for Top Entry

4

M10 x 40

M10 x30

M10 x30

3

M10 x35

Tightening 

torque for all 

connectors 

30Nm

2 M10 x35

1

M10 x 40

Top 
entry 
neutral 
shield

Reposition Hinges

Fit Incomer

30Nm

30Nm

15Nm

12-16 Way Cableway 

Remove x1 cut-out 

feature in cableway to gain access to 

outgoing chamber

30Nm

With the inner 

cover rotated 
180°, remove 

cut-outs as 

shown

3 pole and N 

MCCB

4 pole MCCB

Bottom Entry

Remove x6 male 

hinges from 

enclosure and 

drill 2.2mmØ 

holes as shown

6mmØ
5mmØ

Remove all

swarf

Содержание MEMSHIELD 4

Страница 1: ...tent electrician in accordance with current electrical engineering Codes of Practice Requirements for the Electrical Installations IET Wiring Regulations BS7671 Construction Design and Management Regu...

Страница 2: ...Cover Blank EM4PBGMBP Fit NZM1 Adaptor Cover Shield When NZM3 is fitted a cableway is required NZM3 3PN Form 4 Type 6 Group Mounted Form 4 Type 2 Compartmentalised EM4PBGMN3N Secure inserted adaptor...

Страница 3: ...ition Existing position Utilising the same connectors screws and washers reconfigure from Bottom to Top Entry Ensure connectors are kept in their supplied sets and spring washers are always fitted ben...

Страница 4: ...xings Fix with 4 x M5 fixings Compartmentalise Module EM4PBCK Fix with 5 x M5 fixings per cover Form 4 Type 2 Compartmentalised Module EM4PBCKN122 EM4PBCKN142 EM4PBCKN242 EM4PBCKN342 Fit compartment w...

Страница 5: ...Adaptor NZM3 NZM2 4P NZM1 4P NZM1 SPN EM4PBCKN346 EM4PBCKN246 EM4PBCKN146 EM4PBCKN126 Form 4 Type 6 Compartmentalised Incoming Module EM4PB80CKINC Remove cut off strip in incoming kit shield For remov...

Страница 6: ...existing M5 screws 3 8Nm Pan Assemblies EM4PBP680 EM4PBP1280 EM4PBP16800EM4PBP1840 Form 4 Type 2 6 Compartmentalised Blanking Way EM4PBCKN12BK EM4PBCKN14BK EM4PBCKN24BK EM4PBCKN34BK Empty Compartment...

Страница 7: ...ottom entry example For top entry the labels are in the same position but rotated through 180 Panelboard Labels Supply label fitted to incoming cover Outgoing Adaptor Labels 2 off labels supplied with...

Страница 8: ...oduct which it manufactures whether or not listed in this leaflet and that it will take legal action against any party found to be manufacturing using or selling any article which infringes the compan...

Отзывы: