4. Power cables connection
4.2 MBP11Ki / MBP11ki31 – with common Normal and Bypass AC source
1. Connect the 2 integrated power cables
(1)
to the UPS I/O terminal blocks, following color coding on the
cables and the UPS I/O cover (blue for UPS Input / red for UPS Output) – refer to the UPS user manual to
check the UPS terminal blocks connection
2. Connect the MBP detection cable
(2)
to the specific UPS connector (MBP detect, refer to the UPS User
Manual)
Only with compatible EATON UPS, contact your Eaton reseller for more information.
3. Slide the MBP I/O cover
(3)
after removing the 5 screws, to access to MBP terminal blocks
4. Insert the Normal AC source cable through the cable gland
5. Connect the wires to the Normal AC source (Input) terminal blocks (do not remove the Input Bypass AC
jumper
(4)
and the UPS Input Bypass jumper inside the UPS I/O cover (refer to the UPS User Manual)
6. Insert the Output cable through the cable gland
7. Connect the wires to the Output terminal blocks
8. Tighten the cable glands
9. Slide back and secure the MBP I/O cover
(3)
with the 5 screws
1
2
3
Utility Power
Load
to UPS output
to UPS input
INPUT
L1
L1
N
t
OUTPUT
L1 N
t
INPUT BP
L1 N
t
3
4
INPUT
L1
L1
N
t
OUTPUT
L1 N
t
INPUT BP
L1 N
t
3
Output cable
Normal AC Source
cable
4
OUTPUT
L1 N
t
INPUT BP
L1 N
t
3
4
OUTPUT
L1 N
t
INPUT BP
L1 N
t
3
Output cable
Normal AC Source
cable
4
MBP11Ki
MBP11Ki31
RJ11 MBP detection