Instruction Leaflet 

IL0131154EN

Effective August 2021

Neutral current sensors 

Magnum PXR ACB trip units 

  

EATON

 www.eaton.com

Section 1: Neutral current sensor installation

Ground fault trip units detect ground fault current through residual 

sensing.  If the system neutral is grounded and residual ground fault 

is desired, but no phase to neutral loads are used, a neutral current 

sensor is not necessary.  
If the system neutral is grounded and phase to neutral loads are 

used, then the neutral current sensor (see 

Figure 1

) must be used 

to account for this load in the residual ground fault sensing.

Figure 1. Neutral current sensor application

Magnum circuit breakers with PXR trip units come with the option 

of connecting either a current transformer (CT) or a Rogowski coil 

as the neutral sensor.  Whichever current sensor is selected, it is 

connected to the same two secondary terminals.  Refer to  

Figure 1

 for connections.  Only the current sensors described in this 

document should be used with Magnum PXR trip units.

Refer to 

Figure 2

 for instructions on how to use the trip unit display 

to select the type of sensor that you are using.  If no sensor is used, 

the CT selection should be made (this is the factory default setting).  

If a Rogowski coil is selected and no coil is connected, false current 

readings and possibly trips will occur.

Figure 2. Current sensor selection

Rogowski primary connections should be made by connecting the 

source neutral connection on the side or terminal where the dot is 

placed.  For the CT there is no dot on the unit.  The source should be 

routed through the side opposite the secondary terminals.  Refer to 

Figures 3

 

& 4

 for dimensional and labeling details.

Table 1.  Catalog number and use details

Frame

Application

Catalog#

Ratings 

Where Used

Details

Standard or 

narrow

Rog bus bar

NRMPN

All

Figure 3

Standard or 

narrow

CT

MSCNCT

All

Figure 4

N

Source 

L  C  R

Neutral 

s

ensor

(CT or Rog coil)

Load

Source 

Gray

White

Load

N

N

.

N

C17 C16

X2*

X1*

*CT connections facing the load

From Main Menu:  

Edit Settings

 [PW] 

 

Neutral Sensor 

 [Rogowski/CT]

Содержание Magnum PXR ACB

Страница 1: ...RE TO FOLLOW THESE STEPS FOR ALL PROCEDURES DESCRIBED IN THIS INSTRUCTION LEAFLET COULD RESULT IN DEATH BODILY INJURY OR PROPERTY DAMAGE m WARNING THE INSTRUCTIONS CONTAINED IN THIS IL AND ON PRODUCT LABELS HAVE TO BE FOLLOWED OBSERVE THE FIVE SAFETY RULES DISCONNECTING ENSURE THAT DEVICES CANNOT BE ACCIDENTALLY RESTARTED VERIFY ISOLATION FROM THE SUPPLY EARTHING AND SHORT CIRCUITING COVERING OR P...

Страница 2: ...the current sensors described in this document should be used with Magnum PXR trip units Refer to Figure 2 for instructions on how to use the trip unit display to select the type of sensor that you are using If no sensor is used the CT selection should be made this is the factory default setting If a Rogowski coil is selected and no coil is connected false current readings and possibly trips will ...

Страница 3: ...trip units EATON www eaton com Figure 3 Rogowski coil busbar type dimensions Figure 4 CT type dimensions load side shown 1 58 n 32 94 144 50 54 1 08 3 59 50 1 00 79 49 98 8Xn 440 3 94 1 57 2 64 3 70 POLARITY MARK 10 RINGTERMINAL AND HARDWARE 2X TORQUETO 20 lb in GRAYWIRE POLARITY MARK WHITE WIRE ...

Страница 4: ...operations Where a question exists consult the specifying engineer and or equipment assembler The grounding points of the system shall be verified to determine that ground paths do not exist that would bypass the sensors High voltage testers and resistance bridges may be used m IMPORTANT THE POLARITY OF THE SENSOR CONNECTIONS IS CRITICAL ALWAYS OBSERVE THE POLARITY MARKINGS ON THE INSTALLATION DRA...

Страница 5: ...5 Instruction Leaflet IL0131154EN Effective August 2021 Neutral current sensors Magnum PXR ACB trip units EATON www eaton com Notes ...

Страница 6: ...r other contractual agreement between Eaton and the purchaser THERE ARE NO UNDERSTANDINGS AGREEMENTS WARRANTIES EXPRESSED OR IMPLIED INCLUDING WARRANTIES OF FITNESS FOR A PARTICULAR PURPOSE OR MERCHANTABILITY OTHER THAN THOSE SPECIFICALLY SET OUT IN ANY EXISTING CONTRACT BETWEEN THE PARTIES ANY SUCH CONTRACT STATES THE ENTIRE OBLIGATION OF EATON THE CONTENTS OF THIS DOCUMENT SHALL NOT BECOME PART ...

Отзывы: