Section 4: Master connection diagrams
Secondary contacts and connection diagrams
A maximum of 84 secondary wiring connection points are available
on the Magnum PXR and PD-SB circuit breaker, each dedicated to a
specific function (
) .
Figure 54. Secondary connector protective hood
A proprietary secondary contact connector with 84 plug-in contact
points is mounted on the top rear portion of the circuit breaker . The
plug-in connector is protected by a molded hood (
) . When
the front cover of the circuit breaker is removed, the top of each
plug-in connector is exposed . A label on the connector identifies the
wiring points .
Labels Legend
OTS
Overcurrent trip switch
G
Source ground input
RY
Trip unit programmable relay
+24V/0V
External trip unit power
N
External neutral current input
MM
Maintenance Mode (ARMS)
Z
Zone selective interlocking
MB
MODBUS communications
CM
CAMCOM communications
AQD
(Future use)
RY
(Future use)
VN
External neutral voltage input
ST
Shunt trip
SR
Spring release
M/SC
Charging motor
A/B/C
Auxiliary switches
Figure 55. Top view secondary connectors
Drawout type circuit breakers:
A mating secondary plug-in
connector is mounted on the top front portion of the drawout
cassette (
) . This connector matches and plugs into the
circuit breaker mounted connector . Contact points are wired from
the cassette’s plug-in connectors to cassette-mounted terminal
blocks . The terminal blocks are also mounted on the top front
portion of the cassette . The secondary terminals have finger-proof
hinged covers with small holes for probe testing .
Protective hood