Table 11: All Parameters (continued)
PNU
ID
Access
Right
RUN
Designation
Value Range
Factory
Setting
User
Setting
Protective Functions
P8.1
700
—
4 mA reference
value error
0 = Deactivated
1 = Warning
2 = Error, stop according to P6.8
1
P8.3
703
—
Earth-fault
monitoring
Like P8.1
2
P8.4
709
—
Stall protection
Like P8.1
0
P8.5
713
—
Underload
protection
Like P8.1
0
P8.6
704
—
Motor,
temperature
protection
Like P8.1
0
P8.7
705
—
Motor, ambient
temperature
-20 – +100ºC
40
P8.8
706
—
Motor, cooling
factor at zero
frequency
0.0 – 150%
40
P8.9
707
—
Motor,
thermal time
constant
1 – 200 min
45
P8.10
1430
—
4 mA reference
value error
0.0 – 10.0s
0.5
P8.11
1473
—
Thermistor fault,
response
Like P8.1
2
P8.12
714
—
Underload,
load curve at
rated frequency
10.0 – 150%
50.0
P8.13
715
—
Underload,
load curve at
frequency = 0
10.0 – 150%
10.0
PID Controller
P9.1
163
—
PID controller
0 = Deactivated
1 = to drive control
2 = for external application
0
P9.2
118
—
PID controllers,
P gain
0.0 – 1000.0%
100.0
P9.3
119
—
PID controller,
I time
0.00 – 320.00s
10.00
P9.4
167
—
PID controller,
Keypad
reference
0.0 – 100.0%
0.0
P9.5
332
—
PI controller,
set point source
0 = Keypad (P9.4)
1 = Field bus (option)
2 = AI1
3 = AI2
0