Door escutcheon
—The door escutcheon is a molded frame used
to seal the space between the circuit breaker and the compartment
door cutout. It is supplied with a mounting gasket (
Figure 60. Door Escutcheon and Gasket
IP54 waterproof cover
—A hinged dome-shaped waterproof cover
attaches to the metal compartment door to provide waterproof
protection for the circuit breaker.
Mechanical interlock
—A family of mechanical interlocks are avail-
able to interlock the closing of two or three IZM circuit breakers.
The mechanical interlock holds one or more circuit breakers tripped
(prevents closure) when others are closed. A lever assembly is
mounted on each breaker that interfaces with the pole shaft and
the tripper bar. The lever assemblies are interconnected with either
cables, depending upon the relative orientation of the breakers.
Cables can be used for any orientation of the breakers. Mechanical
interlocks are available for both fixed and drawout circuit breakers
and in both two-way and three-way versions. An illustration of
a two-way cable interlock mounted on two drawout circuit breakers
is shown in
.
Mechanical (pop-out) trip indicator
—A red, pop-out mechanical
trip indicator is an IZM feature. It is located above the trip unit on
the breaker’s front faceplate (
). It operates by releasing and
popping out any time the circuit breaker trips due to an overcurrent
condition.
otee:
N
The mechanical trip indicator will not prevent the breaker from
being reclosed.
Figure 61. Cassette-Mounted Two-Way Cable Interlock